UPS Functional Descriptions
UPS-Manual
9
EN
3.3. Operating Modes & Voltage System
Configurations
Download from
www.rimatrix5.com/dl_power.htm
the “Setting
Tool” and open the Software to see the screen
as below:
3.3.1.
System Configuration Settings
1. System Voltage Selection: Select Input
Voltage 220V
2. Voltage Configurations: Select UPS Output
Voltage 220V/230V/240V
3. UPS Modes: Select Normal/CF50*/CF60*
Mode
4. Output Voltage Fine Tuning : Output Volt-
age Regulation from 0 ~ ±3%
5. Bypass Voltage Windows: Sensitivity: Se-
lect Sensitivity Low/Sensitivity High**
6. Syn-Frequency Window: Select 3Hz/1Hz
Inverter Freq synchronizing range
7. kVA: Key in 1 or 2 or 3 for the UPS kVA
rating
8. Com Port: Select the Com Port of PC
9. Click on “Write” to confirm the configuration
settings. The UPS will beep twice to ac-
knowledge setting is successful.
10. To override the new configurations, make
sure you will turn off the UPS first, then re-
turn on the UPS to get the new configura-
tions working.
Sensitivity Low Sensitivity High
220V System 184V ~ 260V
194V ~ 260V
Note:
*CF50/CF60 = Frequency Converter mode 50
to 60Hz or vice versa
**Sensitivity Low : 184~260V,
High: 194~260V
3.3.2.
Programmable Outlet Setting
The UPS is equipped with 2 programmable
outlets for use to supply to less critical loads.
These outlets can be disabled to shed the less
critical loads during back-up modes or overload
conditions to maintain quality power supply to
the more critical loads connected to the UPS.
Click on the “Programmable outlet setting” bar
to enter to the setting screen as shown below.
1.
Outlet Turn On After Turn on UPS
– select
the time to automatically enable this outlet
within the specified time when the UPS is
powered on. If “0” sec is selected, the outlet
will be enabled once the UPS is powered
on.
2.
Outlet Turn Off After AC Failure
– select
this option to automatically disable the outlet
within the specified time after utility outage
to shed the less critical loads to provide
longer battery back-up time for the other
more critical loads connected to the UPS.
3.
Outlet Turn On After AC Recovered
– se-
lect this option to automatically enable the
outlet within the specified time after the util-
ity is restored.