5.5.2.  Inverter/Internal Over temperature

If  the  UPS  experiences  internal  over-tempera-
ture  when  Utility  is  normal,  it  will  switch  to  by-
pass loop. The UPS will switch back to inverter
mode  when  the  over-temperature  situation  is
eliminated.  If  over  temperature  occurs  when
Utility  is  abnormal,  the  buzzer  will  beep  con-
tinuously and the Fault LED 

 will light up. The

UPS will cut off supply to the loads.

5.5.3.  Inverter  Over-current  and  Inverter

Output Voltage Out of tolerance

If  the  UPS  inverter  delivers  over-current  and
out-of-tolerance  voltage  to  its  outlets,  the  UPS
is  out  of  order.  The  UPS  will  switch  to  bypass
loop  when  Utility  is  normal.  The  Utility 

  LED

and Fault 

 LED will light up.

If  these  two  fault  conditions  occur  when  Utility
is  abnormal,  the  UPS  will  cut  off  the  supply  to
its outlets and the Fault 

 LED will light up.

6.  Maintenance Guide

6.1. Trouble Shooting

When the UPS becomes faulty or malfunctions
during  operation,  you  may  check  the  fault  lists
below  for  respective  solutions.  Should  the
problem  persists,  please  contact  your  local
dealer for assistance.

Situation

Check Items

Solution

UPS Fault 

 LED

Read 

the 

error

code from the LCD
display.

1.Er05, Er25,

2. Overload

3.Er11 (UPS Over
Temperature)

4.Site
wiring/Ground
fault 

5.Er14 (Fans out
of order)

6.Other error
codes

1. Check battery

connection if is
properly done.
Measure Battery
voltage to ensure
batteries are
charged or healthy.
Recharge batteries
for 8 hours if
necessary. Simulate
Utility outage to
verify if UPS is able
to provide DC back-
up. Otherwise
consult your local
dealer right away.

2. Disconnect some

non critical loads
form the UPS output
until overload
ceases. Check if
there is any short
circuit between
cables due to broken
cable insulator.
Replace the cables
in necessary.

3. Remove any objects

obstructing the
ventilation louvers.
Verify if the cooling
fans are working
properly. Contacts
your local dealer to
replace the fans if
necessary.

4. Verify if the “L” & “N”

phase of the Utility
AC source has been
wrongly wired or if
the Ground-Neutral
Voltage exceeded
the limits

5. Verify if the

ventilating fans are
functioning properly.
Do not attempt to
replace the fans by
yourself. Contact
your local dealer for
replacement.

6. Consult your local

dealer for
assistance.

Содержание PMC 12

Страница 1: ...nversion true online UPS System 1 3kVA FRIDHELM LOH GROUP R i t t a l GmbH Co KG Auf dem Stützelberg D 3 5 7 4 5 H e r b o r n Deutschland Germany Email Info rittal de http www rittal com Service Tel 49 0 2772 505 0 Service Fax 49 0 2772 505 2319 A 38333 03 IT 74e doc ...

Страница 2: ...Important Safety Instruction UPS Manual 2 EN Microsoft Windows is a registered trademark of Microsoft Corporation Acrobat Reader is a registered trademark of Adobe Systems Incorporated ...

Страница 3: ...uration Setup 12 4 4 OPERATION 13 4 4 1 Start Up In Normal Mode 13 4 4 2 Start up in Battery Mode Cold Start 13 4 4 3 Check Measured Values Figures detected by UPS 14 4 4 4 UPS Default Data and Special Function Execution 14 4 4 5 UPS Default Settings and Their Alternatives 16 4 4 6 UPS Is Off Due to Unknown Reason and Its Trouble Shooting 16 4 4 7 Shut Off 17 4 5 STATUS ALARM BUZZER 17 4 6 BATTERY...

Страница 4: ...the unit yourself contact your local supplier or your war ranty will be void 4 If liquids are split onto the UPS or for eign objects dropped into the unit the warranty will be null and void 5 Do not install the UPS in an environ ment with sparks smoke or gas 6 This UPS is equipped with an EMI filter To prevent potential leakage current hazard ensure that the AC main supply is securely grounded 7 T...

Страница 5: ...d safety regulations 16 Use only genuine or recommended parts and accessories see Chapter 4 The use of other parts can void the li ability for any resulting consequences 1 5 Storage Instruction For extended storage in moderate climate the batteries should be charged for 12 hours every 3 months interval by connecting the UPS to the utility supply and switch on input breaker lo cated at UPS rear pan...

Страница 6: ...raints 1 This UPS is equipped with fully digitalized control logic for greater functionality and enhanced high level of power protection Digital signal processing DSP also pro vides the UPS with powerful communica tion capability which enhances the flexibil ity for easy remote control and monitoring 2 Wide input voltage tolerance from 184V 288V allows under voltage or over voltage correction witho...

Страница 7: ... Switch Special functions log in out Go to next page Go to previous page or change the setting of the UPS To re confirm the change of UPS Setting 3 1 1 Symbols on the LCD Display Panel Item Symbol Description 1 LINE Utility or Bypass Source 2 Battery Low 3 Battery Abnormal 4 UPS Overloading 5 Site Wiring Fault 6 UPS Working in Service Mode 7 OFF UPS Shutoff 8 FAIL UPS Abnormal Lock 9 UPS Flow Char...

Страница 8: ...32 Port 3 Emergency Power Off EPO Dry Contact Signal inputs 4 Communication Card Options Slot 5 External Battery Connector 6 AC power connection socket 7 AC Outlets 8 Two programmable outlets 9 Utility Input fuse holder 10 Cooling Fans 11 Output fuse holders 12 Output fuse holders for two programmable outlets ...

Страница 9: ...Sensitivity High 220V System 184V 260V 194V 260V Note CF50 CF60 Frequency Converter mode 50 to 60Hz or vice versa Sensitivity Low 184 260V High 194 260V 3 3 2 Programmable Outlet Setting The UPS is equipped with 2 programmable outlets for use to supply to less critical loads These outlets can be disabled to shed the less critical loads during back up modes or overload conditions to maintain qualit...

Страница 10: ...tware of the UPS is compatible with many operating systems such as Windows 98 2000 ME NT XP and Vista For other applications such as Novell NetWare Unix Li nux please contact your local dealer for suit able software All the communication ports including optional cards can be active use simultaneously to monitor the UPS status However only 1 com munication interface at any one time with the highest...

Страница 11: ...S communication software with RS232 and USB cable 1 set of Tower Rack Accessories Kit 4 2 Selecting Installation Position Warning The UPS is heavy Select a location sturdy enough to handle the UPS weight To ensure proper operation and long operating life always position the UPS according to the following requirement 1 Keep minimum 20cm 8 inches distance clearance from the rear panel of the UPS to ...

Страница 12: ...Installation and Operation UPS Manual 12 EN 4 3 2 Power Module Battery Module Step 1 Step 2 4 3 3 Rack Mount Configuration Setup Step 1 Step 2 Step 3 Step 4 ...

Страница 13: ...ng C 5 In case of failure in self test the LCD display will illustrate as drawing D then an error code or error status will be shown on the screen drawing D drawing E 6 Your start up operation of the UPS is com pletely now as illustrated as drawing E Make sure the UPS is plugged onto the wall receptacle for charging at least 8 hours and the batteries of the UPS are fully charged 4 4 2 Start up in ...

Страница 14: ... will illustrate in se quence from drawing E Input Voltage drawing J Input Frequency drawing K UPS Output Voltage drawing L UPS Output Fre quency drawing M UPS Output Load per centage drawing N UPS Battery Voltage drawing O UPS inner temperature drawing J drawing K drawing L drawing M drawing N drawing O 4 4 4 UPS Default Data and Special Function Execution 1 After UPS is turned on successfully us...

Страница 15: ...y will show in sequence drawing P1 buzzer drawing Q1 self test drawing R1 Bypass Voltage drawing S Output Fre quency Synchronized Window drawing T Inverter Output Voltage drawing U1 UPS Operation Mode drawing V Output Voltage Fine Tuning drawing Q1 drawing Q2 drawing R1 drawing R2 drawing S drawing T drawing U1 drawing U2 drawing U3 drawing V ...

Страница 16: ... Output Voltage of which voltage is 220V 230V or 240V for 220V AC system 6 Drawing U1 U2 and U3 mean the operation modes of the UPS of which alternative is Online fixed 50Hz Output or fixed 60Hz Output 7 Drawing V means the adjustments of the Inverter Output which may be calibrated as 0 1 1 2 2 3 or 3 8 When all the setting changes are done you have to press enter key pad to save all the changes w...

Страница 17: ...of the common UPS statuses with respect to their buzzer beep descriptions 4 6 Battery Replacement Step 1 Step 2 Step 3 Status Definitions Buzzer Beep Descriptions UPS faulty Inverter shutdown All functions inhabited Long Continuous Beep UPS faulty loads continue to be supplied via Inverter or Bypass Single successive beep with 2 sec interval battery mode Single short successive beep with 1 sec int...

Страница 18: ...nvert DC to AC and supply to loads with clean stable power LEDs remain illuminated Mains Absent under or over voltage Rectifier and charger stop operating Battery discharge via DC DC boost circuit and supply to Inverter Loads continue to receive supply from Inverter Alarm buzzer beeps UPS now on battery mode LED Nr 2 off Mains Absent Battery low voltage Rectifier and charger stop operating Battery...

Страница 19: ...ly modern day electronics IT equipment generate an inrush current when switching on The amount of inrush current varies from equipment to equipment some can be as high as 6 times its rated capacity while others produce negligible inrush To prevent severe damage to its Inverter cause by the inrush produce by the loads the UPS is equipped with electronics overload protec tion feature as standard If ...

Страница 20: ... the problem persists please contact your local dealer for assistance Situation Check Items Solution UPS Fault LED Read the error code from the LCD display 1 Er05 Er25 2 Overload 3 Er11 UPS Over Temperature 4 Site wiring Ground fault 5 Er14 Fans out of order 6 Other error codes 1 Check battery connection if is properly done Measure Battery voltage to ensure batteries are charged or healthy Recharg...

Страница 21: ...wer source Check that the battery connectors are fully engaged Allow the battery to recharge if the batter is weak If problem persist after recharging replace the battery If problem persist consult your local dealer Rittal or customer service for technical assistance Note When the Fault LED is illuminated the error code is shown in the LCD display Check the error code 6 2 Error Codes and Their Des...

Страница 22: ... whole parallel system or specific values from the single modules 8 1 SNMP Adapter The adapter may be configured via Telnet HTTP Web Browser or serial connection Terminal For normal operation at least one network connection Ethernet is required The SNMP adapter can be used utilising the RCCMD send function for an automatic net work wide shut down or just for informing con nected users The shut dow...

Страница 23: ... PMC Software Our SNMP Interfaces are compatible to RCCMD 9 Customer Service If you have any technical questions or ques tions concerning our product spectrum contact the following service address Tel 49 0 2772 505 1855 http www rimatrix5 com E mail info rittal de ...

Страница 24: ...ge High Line Comeback 230V 278Vac Frequency 50 60 Hz auto select 5Hz Phase Single phase with ground PF 0 99 at full ratedlinearload Typical Transfer Time 0ms AC Leakage current 230V 3 5mA Surge Protection 230V 300 joules Output Voltage 230V 230V adjustable to 220 230 240 Voltage Regulation 1 until low battery warning Frequency Synchroniz ed Range 3Hz or 1Hz setting by software Frequency Battery Mo...

Страница 25: ... Sealed non spillage maintenance free lead acid Transfer Time AC to DC Zero Inverter to Bypass 2 5ms Typical Zero DC Start Yes Self Diagnostics By button of the panel or Software Control Front Panel LED Load Level Battery Level Battery Mode Normal Mode Bypass Mode Self Test Weak Bad Battery Site Wiring Fault Fault Overload Programmable Outlet1 Programmable Outlet2 Key ON Button OFF Button Test Ala...

Страница 26: ...ry 1 5 seconds Low Battery Sounding once every 0 2 seconds Overload Sounding once every 3 second Fault Continuously Sounding or Sounding once every 3 second Physical Dimensions HxWxD in mm 88 2U x440x405 88 2U x440x 650 88 8 2U x440x 650 Weights 15 7kg 34 5Ib 29 4kg 64 7Ib 29 7kg 65 3Ib Input Connection 10A IEC 320 C14 10A IEC 320 C14 16A IEC 320 C20 Output Connection 230V 6 10A IEC 320 C13 4 10A ...

Страница 27: ...Module Load 100 66min 34min 30min 80 90min 52min 46min 60 120min 69min 60min 40 180min 109min 95min 1 extended Battery module 20 350min 210min 180min Load 100 130min 66min 60min 80 160min 90min 75min 60 220min 160min 109min 40 325min 180min 160min 2 extended Battery module 20 630min 350min 310min ...

Страница 28: ...Technical Informations UPS Manual 28 EN ...

Отзывы: