Advanced Operations 8
Switched Power Distribution Unit
55
EN
Enabling or Disabling a Status trap:
The Set Trap … Status command is used to en-
able or disable Status traps for a Tower, Infeed or
Outlet.
To Enable or Disable a Status trap:
At the Switched PDU: prompt, type set trap
(tower, infeed, outlet, em or ths) status, fol-
lowed by the tower, infeed or outlet name, and on
or off. Press Enter, or\
Type set trap (tower, infeed, outlet, em or ths)
Status all, followed by on or off and press Enter.
Examples
The following command enables the Status trap
for the first tower, using the tower’s absolute
name:
Switched PDU: set trap tower status .a
on<Enter>
The following command enables the Status trap
for the tower named Florida_HQ_1:
Switched PDU: set trap tower status Flor-
ida_HQ_1 on<Enter>
Note!
Enabling lower hierarchical traps auto-
matically enables traps of higher hierar-
chical value: i.e. enabling an Outlet Sta-
tus trap automatically enables the Infeed
and Tower Status traps for that outlet.
Conversely, if a Tower Status trap is
disabled, all associated Infeed Status &
Load and Outlet Status traps will be
disabled.
Enabling or Disabling a Load trap:
The Set Trap Infeed Load command is used to
enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the Switched PDU: prompt, type set trap in-
feed load, followed by the infeed name, and on or
off. Press Enter, or
Type set trap infeed load all, followed by on or
off and press Enter.
Examples
The following command enables the Load trap for
second infeed on the first tower, using the in-
feed’s absolute name:
Switched PDU: set trap infeed load .AB
on<Enter>
The following command disables the Load trap for
all infeeds:
Switched PDU: set trap infeed load all
off<Enter>
Note!
Enabling lower hierarchical traps auto-
matically enables traps of higher hierar-
chical value: i.e. enabling an Infeed
Load trap automatically enables the
Infeed and Tower Status traps for that
infeed.
Setting the Infeed Load limit:
The Set Trap Infeed Loadhigh command is used
to set the upper load limits for an input feed.
To set the infeed load limit:
At the Switched PDU: prompt, type set trap in-
feed loadhigh, followed by the infeed name, and
a value from 0 to 255 in amperes. Press Enter.
Example
The following command sets the infeed load limit
for the second infeed on the first tower to 25 am-
peres, using the infeed’s absolute name:
Switched PDU: set trap infeed loadhigh .ab
25<Enter>
Enabling or Disabling a Change trap:
The Set Trap Outlet Change command is used to
enable or disable an Outlet Change trap.
To Enable or Disable a Change trap:
At the Switched PDU: prompt, type set trap outlet
change, followed by the outlet name and on or off.
Press Enter, or
Type set trap outlet change all, followed by on
or off and press Enter.
Example
The following command enables the Change trap
for the third outlet on the first infeed of the second
tower, using the outlet’s absolute name:
Switched PDU: set trap outlet change .ba3
on<Enter>