19
ELECTRICAL SCHEMATIC 120V
Motor
NOTES:
1. PB1 “RAISE” Switch Is 1 HP Rated.
2. For Field Wiring See Dwg. #AI-1839.
Use Minimum #12 Gage, 60
°
/ 75
°
C Copper
Wire/100 Ft. Of Run – 20 Amp Circuit 120V.
Consult Local Code.
G (Green)
G (Green)
G (Green)
1L2 (White)
T1 (Black)
1L2 (White)
T5
T4
T2
T8
T3
P2
P1
T1/ P1 (Black)
Thermal Overload
Motor
Motor – 3/4 HP
@2850/3450 R.P.M.
120V 1 PH 50/60 Hz
Intermittent Duty
(Thermally Protected
With Automatic Reset)
– Wire Termination
Wire Nut Or Equal Device
MOTOR LEAD CONNECTIONS
MOTOR JUNCTION BOX
PUSHBUTTON
CONTROL BOX
BRANCH
CIRCUIT
DISCONNECT
L1
N
G
1L1
N
G
One Leveler Per Overload Protection Device.
(Ref. N.E.C. 1996 Para. 430-110 (C)) Consult Local Code.
A Branch Circuit Disconnect Shall Be Located No More
Than 50' From The Control Box And Must Be Visible.
(Ref. N.E.C. 1996 Para. 430-102 (A) And Article 100).
From Customer Main Power & Safety
Protection Device 120V 1 PH 50/60 Hz.
(Fused Disconnect Supplied By Others)
(Must Use Either 20 Amp Dual Element
Fuse Or 20 Amp Inverse Time Circuit
Breaker).
4422
4422 Rev D
FIGURE 21 — ELECTRICAL SCHEMATIC – 120V
APB-1000/Rev5 6/1/00 7:48 AM Page 19