RIB2312 Sapphire Gas Log Flame Fire
- 12 -
1/3/18 ©Rinnai
COMMISSIONING INSTRUCTIONS
5. Press the 'Set Button'
, once to save the setting. The display
, should now be displaying 'PH', (Main
burner stage 7). Refer to chart below for correct gas settings, (data plate values override values printed in this
instruction).
6. Press the 'UP' button,
or "DOWN' button
to adjust to the required value.
7. Press the 'Set Button',
, once to save the setting.
8. The display
will now show '7'. If the display does not change to '7' there was an error in pressure setting
and the pressure setting procedure should be repeated from step 1 onward after turning the appliance 'OFF'
9. With display
, showing '7' Press the 'ON/OFF' button
.
10. Setting main burner pressure is now complete. Remove the manometer hose and replace the inlet test point
screw. Check for leaks using soapy water solution.
PCB Control Panel
Step 3 . Checking and setting Pilot burner pressure
1. Remove the pilot flame gas test point screw
and connect a positive pressure manometer hose.
2. Press the 'ON/OFF' button
on the PCB control panel to start the ignition sequence, the appliance will
ignite normally. Refer to the PCB control image on the previous page.
3. Press the 'TEST' button
, twice on the PCB control panel, the igniter will spark and the appliance will light to
its lowest setting, (Main burner - stage 1), and the display
, will show 'PL'.
4. Adjust the pilot flame gas pressure to the value for the gas type as listed in the table below via the 'Pilot Flame
Pressure Adjustment' screw
.
5. Press the 'ON / OFF' button
once to stop the appliance operation. Refer to the PCB control panel image
above.
6. Disconnect the manometer hose and replace the pilot flame gas test point screw.
7. Check for gas leaks using soapy water, setting or checking pilot burner pressure is now complete.
Natural Gas
Propane Gas
P L (stage 1)
0.15
0.50
P L (stage 7)
0.71
1.80
Pilot Flame Pressure
Natural Gas
Propane Gas
1.00 kPa
2.00 kPa
Always check gas pressure values to those recorded on this appliances data plate, values on the
data plate override values printed in this instruction.