16
| Linear installation guide 13563-H 08-19
Linear 1500 minimum framing dimensions (mm)
Shaded area denotes a clearance around the fire of approx. 50 mm.
On the RHS this is automatically achieved with the carry bar.
1950
796 min
257 ±5 *
500 **
~ 575
870
1080
990
710
403
300
80**
1120
1195
403 mm assumes a 10 mm wallboard
on both sides of a double-sided unit.
415 mm is the min. for a single-sided
unit to maintain 50 mm clearance to
the back of the fire.
Glass centreline
Front
face to
center of
flue
39 assumes
10 mm wallboard
2065
1195
341*
1516*
2240 (for symmetrical cavity)
•
All dimensions are assuming a 10 mm wallboard
•
Studs and joist are required directly below the support feet of the fire
•
Framing shown is 90 x 45 mm
•
Fire platform shown is 18 mm plywood
•
Allow room underneath the appliance for the gas supply to enter the fire cavity (min. 100 mm)
The framing dimensions have the studs offset. This is because the cavity needs to be
framed based on the centreline of the Linear glass, NOT the opening size
.
Where there is a requirement for a symmetrical installation, the cavity size will need to
increase, refer diagram below.
IMPORTANT
*
Minimum wallboard cutout, refer table on p.29
**
Maintain 25 mm clearance to combustibles for the first 500 mm of flue