Linear installation guide 13563-H 08-19 |
43
Wall terminal assembly
Only the ASPDFK, and the ESPIPE900/ESWTERM can be used to create a wall terminal
Cutting components at a wall penetration
1.
Measure and mark the outer pipe at a point flush with the surface of the wall penetration PLUS
an additional 50 mm.
2. Cut the outer pipe to the required length. Take care not to cut the inner pipe.
3.
From the ‘new’ end of the outer pipe measure and mark off an additional 12 mm
1
on the inner
pipe. Cut the inner pipe at this mark. Take care to keep the cut parallel to the outer pipe.
1
The additional 12 mm on the inner pipe is needed to connect to the wall terminal.
Steps to create a wall terminal
Exterio
r wall
Exterio
r wall
Exterio
r wall
1.
Fit the supplied external wall plate over the outer pipe of the flue
protrusion (arrow points up)
Once the external wall plate is in the correct position secure it to the
wall using the three 22 mm screws into the wall plate holes. Secure
the wall plate to the outer pipe using the two horizontal holes and the
two 7 mm screws provided.
2. Carefully cut through the outer and inner pipes (refer previous page).
Take care to avoid cutting the external wall plate, and keep the cuts
of the internal and external pipes as parallel as possible. Remove all
burrs and swarf from the cut ends.
3.
Align the arrows of the metal flue terminal and wall plate to point in the same direction (must
always point up) and screw the terminal to the external wall plate using the 22 mm screws into
the holes provided.
12 mm
Length to wall
50 mm
12 mm
300 mm
Min. ASPDFK
length
Allow 50 mm
beyond any
wall penetration
Required wall
penetration
12 mm
2
°
fall to the outside
—
arrow
points up