41
1
This parameter selects the maximum temperature and the fi xed temperature, as shown in the table below:
Nr. 02
Nr. 01
A
b
Without controller
With controller
Without controller
With controller
Fixed temperature
Max temperature
Fixed temperature
Max temperature
A
55°C
55°C
55°C
55°C
b
75°C
75°C
55°C
75°C
C
65°C
65°C
55°C
65°C
d
60°C
60°C
55°C
60°C
E
50°C
50°C
50°C
50°C
F
42°C
42°C
42°C
42°C
H
85°C
7
75°C
40°C
40°C
J
85°C
7
75°C
55°C
75°C
2
See paragraph 3.1.2 SERVICE INDICATOR
3
This parameter is available only if the parameter nr. 04 (Recirculation Pump Output) is set the value “b”.
“Economy mode”: cycles the pump less often, using less energy to maintain the circulaion loop temperature.
“Comfort mode”: cycles the pump more frequently, ensuring the loop temperature remains higher (higher consumption).
4
This parameter is available only if the parameter nr. 07 (Cascade: Identify water heater) is set to “b”.
5
This parameter can increase the maximum fl ow rate:
32L model: “10A” is 37L/min, “10b” is 42L/min
26L model: “10A” is 35L/min, “10b” is 38L/min
To gain the maximum fl ow rate, water pressure must be high and low temperature setting (below 40°C) to open the
by-pass control.
6
When water controller is switched on and the “auto reset” function is activated (b), the water heater automatically
switches on and auto sets at temperature selected before the balck-out happens.
7
This parameter can increase the hot water temperature delivery in case of heat losses due to lack of insulation
of water pipes. Default setting is 0°C: temperature set on water controller is the delivered temperature. If the set
temperature is 85 ° C, the delivered temperature cannot be increased.
8
To set 85°C, parameter No.13 need to be change:
•
change parameter No. “13” from value “A” to value “b”;
•
set parameter No.”1” to value “A”;
•
set parameter No.”2” to value “H”; or “J”
•
Disconnected any optional controller. Once the optional controller is connected, the temperature automatically
reverts to 75 °C
9
This setting can modify normal operation of water heater to keep heating water until outgoing temperature is
“Tset+6°C”; default setting is +3°C.
3.1.2 SERVICE INDICATOR
This water heater includes a service indicator (Service Soon, error “55”), when this error appears, maintenance is
necessary, the heat exchanger must be washed to avoid damage. When Service Soon (55) appears on the controller
display the homeowners should schedule a fl ush procedure with there local service provider. (see paragraph 3.8.2
Flushing the heat exchanger)
With the parameter nr. 3 on PCB it is possible to set the appearance interval by the installer.
Interval selection is based on water conditions or other factors that may aff ect the suggested
maintenance interval.
Service Soon will appear again when the time reach to the interval by setting from reset.
To reset Service Soon (error 55)
Press the “On/Off ” button 5 times.
Service Soon (55) wil display on the controller again when the water heater reaches the
intervaò selected in the parameter settings.
5 times