![RIFT Actuators RIFT 200 Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/rift-actuators/rift-200/rift-200_installation-operation-and-maintenance-instructions-manual_1460503018.webp)
18
MANUALLY RE
-
SETTING THE ACTUATOR ON FAILURE TO OPERATE
If the actuator is powered and fails to respond to either an open or closed command the electronics can
be soft re
-
set (similar to a computer via Ctrl/Alt/Del. You will either need to remove the lid will either (6 x
M4 Cap Head Bolts) to access the PCB or via the Android App. The Manual Re
-
Set Button (See Page 16) is
located next to the Bluetooth module and close to the Open Touch Capacity Pad The electronics will
re
-
set and an audible tune will sound. Please note any features that have been set or purchased will not
be lost. This is could be an over torque protection situation, the electronics might have stopped working
to self
-
protect.
OVER
-
TORQUE INDICATION
The RIFT® 200 has the ability to protect the gears, motors, electronics and battery from exceeding the
maximum safety torque of the actuator. This feature is not only to protect the actuator but also the valve
is fitted onto, within its operational torque bands. If the maximum torque is exceeded through either
blockage, or trying to exceed the operational design the LED
’
s on the Lid and on the Android App, if
Bluetooth connected, will indicate a cross pattern of flashing Orange LED
’
s.
To resolve this, either select remotely the reverse direction allowing the blockage to clear the valve, or
via local control, by selecting manual mode RED Flashing LED (at the 8 O
’
clock position) move the actua-
tor in the reverse direction or if unsure of direction of movement, when over torque occurred. Select the
open direction first then close, allowing the blockage time to clear. The RIFT® 200 when reverted back to
remote control will automatically move to the last remote selected position.
3 WAY BALL VALVES
-
DEFAULT FLOW
PATTERNS
(Based on actuator and valve orientation as shown)
Side entry, 90° operation
-
Default flow pattern
L Port 3 way valves
LED Indication
Bottom entry, 180° operation
-
Default
flow pattern
L Port 3 way valves
LED Indication