Buttons Enabled
-
This setting removes Local/Manual control via the Touch Pads. The operation
of the Actuator this can be re
-
instated through the Android App when paired via Bluetooth to the
RIFT® 200 and the electronics will need to be manually Re
-
Set on completion of this feature being
enabled or disabled.
“
Write To Flash
”
sets the custom settings into the Actuators Flash Memory. Notice of Writing to
Flash will appear briefly at the bottom of the screen
“
Reset Board Without Changing Settings
”
(Manual Re
-
Set)
this is a soft re
-
set, Similar to pressing
Ctrl/Alt/Del on a standard computer please note that the features & settings that have already
been set, will not be lost)
“
Restore All Default Values
”
Hard Factory Re
-
Set. This should be a
“
Last Resort Option
”
as all paid
for Features & Settings will have to be re
-
applied and implemented
TORQUE LIMIT.
This function will allow the customisation of the maximum torque the RIFT® 200 actuator will be allowed
to move to. The selection of this primarily is to offer protection to the valve the actuator is fitted to.
Torque Limit Back off allows the user to specify the angle that the actuator will back off if the Torque Limit
is reached.
The RIFT® 200 will display an Orange
on the top indicating that the Torque Limit has been reached.
This is a calculated function derived from Amperage draw from the Battery and the objective of the
movement, this feature should not be used below an agreed threshold and should be discussed with the
factory for further information.
FAIL SAFE.
This function will allow the RIFT® 200 Actuator to move the valve to a desired Safe position in the event of
external power failure when in Remote Control.
Fail Open
-
On Power Loss the Actuator will move to the Open Position
Fail Closed
-
On Power Loss the Actuator will move to the Closed Position
Fail to Specific Angle
-
This allows the User to specify the desired angle to move to on Loss of External
Power
Failsafe Angle
-
Enter the Angle between 0° and 360° (0°
-
90° in normal operations)
(If the actuator is being used in Multi
-
Turn Mode and a larger angle than 360° can be set as the Failsafe
Angle)
If the RIFT® 200 Actuator is in the Manual/Local Mode Failsafe will not action as Manual/Local Mode is a
safety feature and can only be removed manually via the touch pad or Android App (button)