The flue gas exhaust and its connection to the stack must be made in compliance with applicable laws and standards,
using heat resistant, condensate resistant and stress resistant rigid pipe and sealed joints.
COMBUSTION GAS EXHAUST
b
The stack must guarantee the minimum draught
specified by applicable technical standards, assu-
ming zero pressure at the connection to the flue
gas exhaust.
b
Inadequate or badly dimensioned stacks and
exhausts can increase combustion noise, cause
condensation problems and affect combustion
parameters
.
b
Uninsulated flue pipes are potentially dangerous
and can cause burns.
b
Joints must be sealed using materials capable of
withstanding temperatures of at least 250°C (e.g.
filler, mastic or silicone based sealant).
g
N
g
NK
DESCRIPTION
MODEL
g
N
3
4
5
6
7
8
9
10
Ø - D
130
130
130
130
130
130
180
180
mm