DEFAULT PARAMETER SETTINGS TABLE
NOTE
MENU DE-
SCRIPTION
DESCRIPTION SETTINGS RAN-
GE
DEFAULT
SC ACS 160
DEFAULT
SC ACS 225
NOTE
4. SETTINGS
4.1
T set DHW
30 ÷ 85 °C
45 °C
45 °C
4.2
T max DHW
55 ÷ 95 °C
55 °C
55 °C
4.13
VFS type
1-12, 1-20, 2-40,
5-100, 10-200,
20-400l /min
10-200 l/min 10-200 l/min
RECIRCULA-
TION
4.14
Rercirculation
-
-
-
4.14.1
Rercirculation
Request
/ Periods /
Periods
/ Contin.function.
REQUEST
REQUEST
4.14.2
T min rercircu-
lation
10 ÷ 85 °C
35 °C
35 °C
4.14.3
Recirculation
hysteresis
1 ÷ 30 °C
5 °C
5 °C
4.14.4
Max portata
ricircolo
off ÷ 100 l/min
25 l/min
25 l/min
4.14.5
Max recircula-
tion flow
-
Period re-
circ. settings
Period recirc.
settings
4.16.6
Draw-off sup-
port
-
OFF
OFF
IF 6.12.2.1 ON
4.15
Thermostat
-
-
-
4.15.1
T min storage
10 ÷ 85 °C
50 °C
50 °C
4.15.2
T set storage
45 ÷ 95 °C
55°C
55°C
4.15.3
Hysteresis
1 ÷ 30 °C
5 °C
5 °C
4.15.4
Thermostat
periods
-
Period
therm. set-
tings
Period therm.
settings
SEE 6.9
4.16
Zone valve
-
-
-
4.16.1
DT return stora-
ge
1 ÷ 20 °C
3 °C
3 °C
4.17
Additional
pump
-
-
-
4.17.1
Flow rate ON
20 ÷ 200 l/min
50 l/min
70 l/min
4.17.2
Flow rate Off
10 ÷ 60 l/min
30 l/min
40 l/min
4.17.3
Delay
1 ÷ 60 s
3 s
3 s
MIXING VALVE
4.18
Primary mixer
-
-
-
4.18.1
Primary flow
MIN
46 ÷ 64 °C
48°C
48°C
4.18.2
Primary flow
MAX
51 ÷ 90 °C
65 °C
65 °C
4.18.3
Direction
-
open = right
open = right
4.18.4
Turn time
0.5 ÷ 5.0 s
1 s
1 s
4.18.5
Pause factor
0.1 ÷ 4.0 s
1 s
1 s
4.18.6
Mixer run time
5 ÷ 300 s
20 s
20 s
KIT CASCDE
4.20
Cascade
-
-
-
4.20.1
Fix base station
-
off
off
4.20.2
Station ON flux
10 ÷ 99%
50%
50%
4.20.3
Station OFF
flux
10 ÷ 90%
20%
20%
4.20.4
Delay
1 ÷ 120 s
6 s
6 s
5. ANTI-LEGIO-
NELLA