26
Min. Speed
The minimum speed of the pump is determined here. During the setting, the pump runs in the respective speed and the
flow can be determined.
b
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump
and pump level. 100% is the maximum possible power of the controller.
Signal Settings
Settings from the 0-10V or the PWM pump can be made in this menu.
b
When this menu is selected, you may receive a request to save the speed settings.
Type of pump/ Type of signal
The type of speed controlled pump used can be set here.
0-10V: Control of special pumps (e.g. high efficiency pumps) through a 0-10V signal.
PWM: Control of special pumps (e.g. high efficiency pumps) through a PWM signal.
Pump/ Profile
In this menu, the preset profiles for the pump can be selected or under “manual” all settings can be done personally. The
settings can still be changed after a profile has been selected.
Output Signal
In this menu, the type of pump is set: heating pumps have the greatest output with a small input signal, solar pumps in
contrast have very little output with a small input signal. Solar = normal, heating = inverted.
PWM / 0-10V off
This signal / this voltage is emitted if the pump is turned off (pumps with cable break detection require a minimal voltage
/ a minimum signal).
PWM / 0-10V on
This voltage / this signal requires the pump in order to turn on and to run at a minimum speed.
PWM / 0-10V max.
With this value, the maximum voltage level / maximum frequency can be specified for the highest speed of the energy
saving pump, which is used, for example, during the flushing or manual operation.
Show signal
Represents the set pump signal in a graphic and text overview.
Relay functions for free relays
Free, i.e. in the hydraulic variant unused relays, can be assigned to various additional functions. Every additional function
can only be assigned once. All special functions, which function values can be preset and changed also appear in the
menu "Settings" as soon as they have been activated or assigned.
In order to change the assignment of a relay, the previously assigned additional function must be switched off.
Please pay special attention to the relay’s technical information See " Specifications " on page 5.
Circulation
All required settings for the circulation are done here.
Activate function.
b
Circulation settings are only available if the "Circulation" function is set under Special functions for relays. (Correctly
set by the controller by automatic detection.
Circulation mode of circulation
Continuous operation: The circulation pump is continuously switched on.
Requirement: The circulation pump is switched on as soon as a tapping process is started and remains switched on until
the circulation temperature (circulation Tmin + hysteresis) is reached at the circulation sensor.
Time: The circulation pump is switched on when it is released and the circulation temperature falls below the set minimum
temperature and remains switched on until the circulation target temperature (circulation Tmin + hysteresis) is reached
at the circulation sensor.
Requi time: The circulation pump is switched on when it is released and the set minimum circulation temperature
is undershot or as soon as a tapping process is started. It remains switched on until the circulation target temperature
(circulation Tmin + hysteresis) is reached at the circulation sensor.