Circ. Tmin.
Minimum temperature
If this value is undershot and the circulation is approved or there is a request through a tapping process, the circulation
pump is started.
Circ. Hysteresis
Switch-off hysteresis of the circulation pump. If the Circ. Tmin value is exceeded by the value set here, the circulation
pump will be shut down.
Circ. max. Flow rate
Maximum flow rate of the circulation pump. The circulation pump is switched off if the flow sensor detects more than the
value set here during a tapping process.
b
This value is set by the calibration.
Circ. Periods
Period where the circulation pump is enabled.
In this menu, the operating times for circulation are selected, whereby 3 periods can be defined for each day of the week
and copied to the following days.
b
The setting value Circ. Period only appears in the menu if the circulation variant "Periods" or "Time" has
been selected.
b
In periods not defined circulation is inactive. The set periods are only used in the operation mode “Time”.
Tap support
To ensure a constant temperature even with small amount of tap water, the circulation pump can be used as support
pump. Not only does the circulation pump switch on under normal conditions, but also when a small tapping occurs.
When a storage sensor is connected, tap support is only switched on when the min. storagetemp is reached at the stor-
age sensor.
Min. Storagetemp
Tap support is deactivated when the storage temperature drops below „Min. Storagetemp“.
Tap support calibration
For information about the function and calibration procedure, See " Calibration of Tap Support " on page 11.
Storage Heating
To heat up the storage on demand, the necessary parameters can be set here. Activate or deactivate function.
Minimum storage temperature
If this value falls below this value at the associated storage sensor outside the enable times for heating, the heating is
nevertheless started.
Storage target temperature
If this value falls below this value at the associated storage sensor during the enabling times for heating, the heating is
started.
Switch-off hysteresis for storage heating (Sp-Hysteresis)
The storage target temperature is calculated from Tmin or Tset storage at the given operating time plus the hysteresis set
here. If the target temperature at the corresponding storage sensor is reached, storage heating is switched off.
Heating times
Enable period for storage heating. In this menu, the operating times for storage heating are selected, whereby 3 periods
can be defined for each day of the week and copied to the following days.
Storage stratification
The stratification function switches a valve that directs the return flow either to the central or lower storage zone depend-
ing on the temperature.
In this menu, the temperature difference between storage sensor and return flow sensor is set. If the return flow tempera-
ture exceeds the storage temperature by the value set here, the system loads into the central storage zone. If no storage
sensor is connected, a storage tank temperature of 25 °C is set.
Activate or deactivate function