TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m s.l.m.
(2) Pressure at test point 7)(A)p.12, with zero pressure in the combustion chambre, an maximum burner output.
(2) Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output, and measured from a dis-
tance of one meter.
VARIANTS:
ACCESSORIES
(optional):
•
KIT FOR LPG OPERATION:
The kit allows the RS 50/M burner to operate on LPG.
•
KIT FOR MODULATING OPERATION
•
POTENTIOMETER KIT FOR THE INDICATION OF LOAD POSITION:
code
3010109
IMPORTANT:
The installer is responsible for the addition of any safety device not forseen in the present manual.
MODEL
RS 50/M
TYPE
26653X 30965X
OUTPUT
(1)
MAX.
kW
285 - 630
245 - 542
Mcal/h
MIN.
kW
80
69
Mcal/h
FUEL
GAS NATURAL: G23 - G25
G20
G25
- Net calorific value
kWh/Sm
3
Mcal/Sm
3
9.45
8.2
8.13
7.0
- Absolute density
kg/Sm
3
0.71
0.78
- Max. delivery
Sm
3
/h
66.5
77.5
- Pressure at max. delivery
(2)
mbar
8.5
11.3
OPERATION
• Intermittent (min. 1 stop in 24 hours)
• Progressive two-stage or modulating by kit (see ACCESSOIRES).
STANDARD APPLICATIONS
Boilers: water. steam. diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
3 ~ 400V / 230 V 1N ~ 230V +/-10%
50 Hz
ELECTRIC MOTOR
rpm
W
V
2800
650
220/240 - 380/415
OPERATING CURRENT
START-UP CURRENT
A
A
3 - 1.7
13.5 - 7.7
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1x8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
W max
750
ELECTRICAL PROTECTION
IP 44
IN CONFORMITY WITH EEC DIRECTIVES
89/336 - 2004/108 - 73/23 - 2006/95 - 2006/42
NOISE LEVELS
(3)
dBA
72
Blast tube lenght mm
261 - 351
Output kW
80 - 630
Code
20008173
OUTPUT POWER REGULATOR KIT RWF40
Two components should be ordered:
• the Output power regulator to install on the burner;
• the Probe to install on the heat generator
Parameter to control
Probe
Output power
regulator
Adjustment field
Type
Code
Type
Code
Temperature
- 100...+500°C
PT 100
3010110
RWF40
3010212
Pressure
0...2.5 bar
0...16 bar
Output probe
4...20 mA
3010213
3010214
GB
COUNTRY
CATEGORY
IT-AT-GR-DK-FI-SE
II
2H3B/P
ES-GB-IE-PT
II
2H3P
NL
II
2L3B/P
FR
II
2Er3P
DE
II
2ELL3B/P
BE
I
2E(R)B,
I
3P
LU
II
2E3B/P
Содержание RS 50/M