49
20081753
GB
Start-up, calibration and operation of the burner
501
Position of the fuel servomotor in absence of flame
Index 0 = standby position
Index 1 = pre-purging position
Index 2 = post-purging position
3
(°)
Modification
0°
90°
0.1°
0°; 0°; 15°
Service Mode
502
Position of the air servomotor in absence of flame
Index 0 = standby position
Index 1 = pre-purging position
Index 2 = post-purging position
3
(°)
Modification
0°
90°
0.1°
0°; 90°; 45°
Service Mode
503
VSD speed without flame
Index 0 = standby speed
Index 1 = pre-purging speed
Index 2 = post-purging speed
3
(°)
Modification
0°
100°
0.1°
0°; 100°; 50°
Service Mode
522
Acceleration
1
s
Modification
5 s
20s
1s
10s
Service Mode
523
Deceleration
1
s
Modification
5 s
20s
1s
10s
Service Mode
542
VSD/PWM activation
0 = Deactivated
1 = Activated
1
-
Modification
0
1
1
0
Service Mode
545
Minimum modulation limit
Not defined = 20%
1
%
Modification /
zero setting
20%
100%
0.1%
Not defined
Service Mode
546
Maximum modulation limit
Not defined = 100%
1
%
Modification /
zero setting
20%
100%
0.1%
Not defined
Service Mode
600
SERVOMOTORS
606
Tolerance limit for position check (0.1°)
Index 0 = fuel
Index 1 = air
More serious position error, where a defect has cer-
tainly been detected
- > Stop range: (P 606 - 0.6°) a P606
2
(°)
Modification
0.5°
4°
0.1°
1.7°; 1.7°
Service Mode
641
VSD speed standardisation control
Negative value error diagnostics (see error code 82)
0 = standardisation deactivated
1 = Standardisation active
1
-
Modification
-25
1
1
0
Service Mode
642
Standardised speed
Index 0 = speed 1
Index 1 = speed 2
2
-
Reading only
650
6500
0.1
Not defined
Service Mode
645
Analogue exit configuration
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0 / 2...10 V
1
-
Modification
0
2
1
2
Service Mode
700
LOG OF THE ERRORS
701
Error chronology: 701-725.01.Code
25
-
Reading only
0
255
1
0
Info mode
•
Error chronology: 701-725.02.Diagnostic code
25
-
Reading only
0
255
1
0
Info mode
•
Error chronology: 701-725.03.Error class
25
-
Reading only
0
6
1
0
Info mode
•
Error chronology: 701-725.04.Phase
25
-
Reading only
0
255
1
0
Info mode
•
Error chronology: 701-725.05.Start-up meter
25
-
Reading only
0
99999999
1
0
Info mode
725
Error chronology: 701-725.06.Load
25
%
Reading only
0%
100%
0.1%
0%
Info mode
900
PROCESS INFORMATION
903
Actual output
Index 0 = fuel
Index 1 = air
2
%
Reading only
0%
100%
0.1%
0%
Info mode
922
Position of the servomotors
Index 0 = fuel
Index 1 = air
2
(°)
Reading only
-50°
150°
0.01°
0°
Info mode
935
Absolute speed
1
-
Reading only
0
6553,5
0,1
0
Service mode
936
Standardised speed
1
%
Reading only
-200%
200%
0.1%
0%
Info mode
942
Heat source active
1 = output during the definition of the curves
2 = manual output
3 = BACS output
4 = analogue input output
5 = output of the external load regulator contacts
1
-
Reading only 0
255
1
0
Service mode
Parameter
No. of
elements
Unit of
measure-
ment
Modification
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
Description
Min.
Max.
Содержание RS 310/EV BLU FS1