20081753
48
GB
Start-up, calibration and operation of the burner
223
Maximum repeats of minimum gas pressure switch
intervention
1 = No repetition
2...15 = Number of repetitions
16 = Constant repetitions
1
-
Modification
1
16
1
16
Service Mode
225
Gas: pre-purging time
1
s
Modification
20s
60 min
0.2s
20s
Service Mode
226
Gas: pre-ignition time
1
s
Modification
0.4 s
60 min
0.2s
2s
Service Mode
230
Gas: interval 1
1
s
Modification
1s
60s
0.2s
2s
Service Mode
232
Gas: interval 2
1
s
Modification
0.4 s
60s
0.2s
2s
Service Mode
233
Gas: post-combustion time
1
s
Modification
0.2s
60s
0.2s
8s
Service Mode
234
Gas: Post-purging time (no extraneous light test)
1
s
Modification
0.2s
108 min
0.2s
0.2s
Service Mode
236
Gas: Minimum gas pressure switch input
0 = deactivated
1 = minimum gas pressure switch (upstream of the
fuel valve 1 (V1))
2 = valve control via the minimum pressure switch
(between fuel vale 1 (V1) and 2 (V2))
1
-
Modification
1
2
1
1
Service Mode
237
Gas: Maximum gas pressure switch / POC Input
0 = deactivated
1 = Maximum gas pressure switch
2 = POC
1
-
Modification
1
2
1
1
Service Mode
239
Gas: Intermittent operation
0 = deactivated
1 = activated
1
-
Modification
0
1
1
1
Service Mode
241
Gas: Valve leak detection test
0 = test deactivated
1 = valve leak detection test at start up
2 = valve leak detection test at shutdown
3 = valve leak detection test at start-up and at shut-
down
1
-
Modification
0
3
1
2
Service Mode
248
Gas: Post-purging time (t3)(at deactivation of the load
(LR)) - ON
1
s
Modification
1s
108 min
0.2s
1s
Service Mode
261
Oil: selection of flame sensor
0 = QRB.../ QRC...
1 = ION / QRA...
1
-
Modification
0
1
1
0
Service Mode
265
Oil: pre-purging time
1
s
Modification
15s
60 min
0.2s
15s
Service Mode
266
Oil: pre-ignition time
1
s
Modification
0.6s
60 min
0.2s
2s
Service Mode
270
Oil: interval 1
1
s
Modification
0.4 s
60 min
0.2s
2s
Service Mode
272
Oil: interval 2
1
s
Modification
0.4 s
60 min
0.2s
2s
Service Mode
273
Oil: post-combustion time
1
s
Modification
0.2s
60s
0.2s
8s
Service Mode
274
Oil: Post-purging time (no extraneous light test)
1
s
Modification
0.2s
108 min
0.2s
0.2s
Service Mode
276
Oil: Minimum input oil pressure switch
0 = deactivated
1 = activated from phase 38
2 = activated from safety time (TSA)
1
-
Modification
1
2
1
1
Service Mode
277
Oil: Maximum oil pressure switch / POC Input
0 = deactivated
1 = Maximum oil pressure switch
2 = POC
1
-
Modification
1
2
1
1
Service Mode
279
Oil: Intermittent operation
0 = deactivated
1= activated
1
-
Modification
0
1
1
1
Service Mode
281
Oil: selection transformer ignition phase TA
0 = brief pre-ignition (Ph38)
1 = long pre-ignition (with fan)(Ph22)
1
-
Modification
0
1
1
1
Service Mode
284
Oil: Post-purging time (t3)(at deactivation of the load
(LR)) - ON
1
s
Modification
1s
108 min
0.2s
1s
Service Mode
400
AIR / FUEL MODULATION CURVES
401
Checking servomotor fuel (only curve setting)
13
(°)
Modification
0°
90°
0.1°
0°; 0°; 15°;
Not defined
Service Mode
402
Checking servomotor air (only curve setting)
13
(°)
Modification
0°
90°
0.1°
0°; 90°; 45°;
Not defined
Service Mode
403
VSD control curve ratio (only curve setting)
13
(°)
Modification
20°
100°
0.1°
0°; 100°;
50°; Not
defined
Service Mode
500
POSITIONING OF SERVOMOTORS
Parameter
No. of
elements
Unit of
measure-
ment
Modification
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
Description
Min.
Max.
Содержание RS 310/EV BLU FS1
Страница 2: ...Translation of the original instructions...