Start-up, calibration and operation of the burner
6.6
Pressure switch adjustment
6.6.1
Maximum gas pressure switch
Adjust the maximum gas pressure switch (Fig. 31) after perform-
ing all other burner adjustments with the maximum gas pressure
switch set to the end of the scale.
With the burner operating at maximum output, lower the adjust-
ment pressure by slowly turning the relative knob anticlockwise
until the burner locks out.
Now turn the knob clockwise by 2 mbar and repeat burner start-
up to ensure it is uniform.
If the burner locks out again, turn the knob clockwise again by 1
mbar.
6.6.2
Minimum gas pressure switch
Adjust the minimum gas pressure switch (Fig. 32) after perform-
ing all the other burner adjustments with the pressure switch set
to the start of the scale.
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner stops.
Now turn the knob anticlockwise by 2 mbar and repeat burner
start-up to ensure it is uniform.
If the burner locks out again, turn the knob anticlockwise again by
1 mbar.
6.6.3
PVP pressure switch kit
Adjust the pressure switch for the leak detection control (PVP
kit)(Fig. 33) according to the instructions supplied with the kit.