9
20081753
GB
Technical description of the burner
4.4
Technical data
Tab. C
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at the test point of the pressure switch 5) (Fig. 5) with zero pressure in the combustion chamber and at maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
power is evaluated, in line with the regulations, on a spherical surface centred on the burner and with a radius of 1 metre.
4.5
Electrical data
Tab. D
Model
RS 310/EV BLU
RS 410/EV BLU
RS 510/EV BLU
RS 610/EV BLU
Type (FS1/FS2*)
1138T2
1135T2
1136T2
1137T2
Power
(1)
Delivery
(1)
min - max
kW
400/1200 - 3630
500/1500 ÷ 4450
680/1800 ÷ 5250
1000/2200 ÷ 6250
Fuels
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Gas pressure at max. output
(2)
Gas: G20/G25
mbar
50.1/74.7
53.1/79.2
59.7/89.1
77.6/115.8
Operation
FS1: Intermittent (min. 1 stop in 24 hours) - FS2: Continuous (min. 1 stop in 72 hours)
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 50
Combustion air temperature
°C max
60
Noise levels
(3)
Sound pressure
Sound power
dB(A)
78
89
80
91
82.5
93,5
85
96
Model
RS 310/EV BLU
RS 410/EV BLU
RS 310/EV BLU
RS 410/EV BLU
Type (FS1/FS2*)
1138T2
1135T2
1138T2
1135T2
Main electrical supply
3 ~ 230V +/-10% 50 Hz
3N ~ 400V +/-10% 50 Hz
Fan motor IE2
rpm
V
kW
A
2900
230/400
7.5
23.9 - 13.8
2920
230/400
9.2
29.3 - 16.9
2900
230/400
7.5
23.9 - 13.8
2920
230/400
9.2
29.3 - 16.9
Ignition transformer
V1 - V2
I1 - I2
230V - 1 x 8 kV
1A - 20mA
Absorbed electrical power
kW max
9.1
10.8
9.1
10.8
Protection level
IP 54
Model
RS 510/EV BLU
RS 610/EV BLU
Type (FS1/FS2*)
1136T2
1137T2
Main electrical supply
3N ~ 400V +/-10% 50 Hz
Fan motor IE2
rpm
V
kW
A
2880
400/690
12
21.2 - 12.2
2920
380/660
15
29.5 - 17
Ignition transformer
V1 - V2
I1 - I2
230V - 1 x 8 kV
1A - 20mA
Absorbed electrical power
kW max
14
17
Protection level
IP 54
WARNING
*The burner leaves the factory set up for FS1 op-
eration. If FS2 operation is required, see section
“Modify the parameter for continuous/intermittent
operation (FS2/FS1)” on page 40.