STARTING AND USE

 

The factory settings of the parameters are shown in the follow-

ing example:

8

40

F03

F06

F05

% Speed

F04

50

60

70

75

80

90

100

10 12 14 16 18 20 22 24 26

27

28

30

32

External air

(S02)

If the water temperature is lower than F07 parameter (15°C), the 

fan runs at max speed F04. 

If  the water  temperature  is  higher  or  same  as  F07  parameter 

(15°C), 3 cases are possible:

1st Case

Tair <= [F05-F06] Fan at max speed or F04

2nd Case

 

[F05-F06] < Tair < [F05] Fan at proportional speed V% 

3rd Case 

Tair > [F05] Fan at minimal speed F03

3 .22 

Defrost management (dFr branch)

It allows to use the unit also with air temperature of about 0°C, 

preventing the formation of ice on the evaporating coil surface. 

It is adjusted by a smart algorithm and is performed through hot 

gas injection (d01=1). Moreover, it can be carried out per time or 

per temperature according to the parameter value (d02).

The defrost is enabled only for heat pump operation.

The activation/deactivation of defrost is a based on the value 

detected by probe S03 and on a series of parameters described 

in dFr branch.

The defrost activation occurs if probe S03 detects a temperature 

lower than the intervention threshold (d03), for a preset interval 

time (d05). This interval is displayed through the flashing of LED 

L5, whereas for the whole duration of the cycle dFr symbol is 

displayed, alternated with the current water temperature.

Similarly, the defrost deactivation occurs if probe S03 detects a 

temperature higher than the defrost end threshold (d04) or pos-

sibly for a maximum time (d07).

NOTE: in the navigation diagram, the instantaneous value of 

such temperature can be displayed near parameter S03 .

3 .23 

Alarms

ALARM E01 - HIGH PRESSURE

The alarm shuts off the unit and the display shows the message 

E01. The reset is automatic until the number of interventions/ 

hour is equal to the value set in the parameter AL7, in which case 

it becomes manual. Manual reset by keyboard pressing the   

[SET] key once the cause of alarm has fixed.

ALARM E03 - PROBE S01 FAILURE

It is active if the sensor S01 (sonda acqua serbatoio) is short cir-

cuited or disconnected. The alarm shuts off the unit and the 

display shows the message E03.

ALARM E04 - PROBE S02 FAILURE

It is active if the sensor So2 (Outdoor air temperature) is short-cir-

cuited or disconnected. The alarm shuts off the unit and the dis-

play shows the message E04.

Machine operation can be forced to MANUAL mode by setting 

H29=0 (i.e. by disabling probe S02, in order to remove the alarm 

condition) and then by pressing   [FUNCTION] key to activate the 

electrical heating element only; obviously, in this condition the 

AUTOMATIC mode is inhibited.

ALARM E05 - HIGH TEMPERATURE

The reset is automatic.

It is activated if the sensor S1 assumes values higher than the 

parameter AL5 for a time longer than the parameter AL6.

The alarm shuts off the unit and the display shows the message 

E05.

ALARM E06 - PROBE S03 FAILURE

It is active if probe S03 (evaporator inlet probe) is short circuited 

or interrupted and if the following conditions are true:

 

− defrost enabled (d01= 1, d01=2)

 

− electronic expansion valve enabled (U00=1).

The intervention implicates the machine switching off and the 

displaying of label E06.

ALARM E07 - PROBE S04 FAILURE

It is active if probe S04 (evaporator outlet probe) is short circuited 

or interrupted and if the electronic expansion valve is enabled 

(U00=1). The intervention implicates the machine switching off 

and the displaying of label E07.

Code

Description

E01

Refrigerant high pressure alarm

E02

Not available

E03

Alarm Probe S01 (water) broken or disconnected

E04

Alarm Probe S02 (air) broken or disconnected

E05

Water high temperature alarm

E06

Alarm Probe S03 (evaporator inlet) broken or discon-

nected

E07

Alarm Probe S04 (evaporator outlet) broken or dis-

connected

 

9

From a state of ALARM, holding down the    [SET], key you 

enter the navigation diagram. 

 

9

If the alarms described repeatedly trigger, switch off the 

machine and contact an authorized Technical Support Ser-

vice, indicating the identification data of the unit contained 

in the relevant plate.

Содержание NexPro Plus

Страница 1: ...cod Doc 0081361 rev 0 10 2016 NexPro Plus EN INSTALLATION AND MAINTENANCE MANUAL...

Страница 2: ...t Riello S p A CONFORMITY R NexPro Plus units comply with the European Directives Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Dir...

Страница 3: ...he operating modes 14 3 6 List of parameters 15 3 6 1 Parameters of electronic board inputs outputs 15 3 6 2 User parameters Utt 15 3 6 3 Installer parameters 15 3 7 Navigation diagram 18 3 8 Automati...

Страница 4: ...to the unit sit on it and or rest any type of object on it 0 0It is prohibited to spray or jet water directly onto the unit 0 0It is prohibited to open the doors for accessing the internal parts of th...

Страница 5: ...ith double layer glazing capacitor externally wrapped to the accumulation tank free from limescale deposits and gas water contamination auxiliary coil for the use in combination with boilers NexPro 30...

Страница 6: ...700 W Absorbed power in stand by mode 43 W Efficiency Energy WH 5 124 Annual consumption AEC 5 826 kWh Daily consumption QELEC 5 4000 Wh Maximum power input 6 5 A Load profile L Energy class A Refrig...

Страница 7: ...nvolved For handling use depending on the weight appropriate means as required by Directive 2006 42 EC and subsequent amendments 9 9The machine covering cannot withstand significant stress therefore i...

Страница 8: ...n environment and free from obstructions Comply with all applicable laws in force in the country where the machine is installed as regards the use and disposal of the products used for machine cleanin...

Страница 9: ...F Probe well G Cold water 1 F L Anode 1 1 4 F M Electrical heater 1 1 4 F NexPro 300 S Plus 1415 1242 800 845 1040 800 330 168 A M L E F G H I 5D 2D 1025 C A Hot water 1 F C Probe well E Recirculation...

Страница 10: ...er is supplied with a temperature over 50 C on the faucet of use can cause serious burns It therefore requires the use of a thermostatic mixing valve 9 9This valve will be required for solar panel ins...

Страница 11: ...cts must not exceed a total length of 10 meters sum of suction and outlet with diameter of the ducts equal to 160 mm Fan useful static head Pa mc h 0 0 50 100 150 200 250 100 200 300 400 500 600 2 7 E...

Страница 12: ...perature probe Con nected S04 evaporator output temperature probe Con nected Relays output Initials Description Status Default Note r1 compressor igni tion enabling 1 enabled 0 disabled 1 Con nected r...

Страница 13: ...ON OFF 6 Key Function L14 L1 L2 L3 L4 L5 L6 L7 L8 L19 L18 L17 L16 L15 L9 L10 L11 L12 L13 5D 2D L1 Unit activation from remote contact LED ON OFF L2 Compressor activation LED L3 Led electrical heater O...

Страница 14: ...key for 3 seconds to reset the counter of heat pump heating element and total runtime UP key stops the flashing of the LED rel evant to anti legionella treatment and re sets the relevant counter KEY S...

Страница 15: ...nge the parameter the change is automatically confirmed without pressing any other key the setpoint flashes for several seconds and the display shows the water temperature detected by the probe S01 Pa...

Страница 16: ...ual mode 2 H29 1 0 1 numero Enable air probe S02 0 disabled 1 enabled 2 H30 1 0 1 numero Enable digital input ID2 0 disabled 1 enabled 2 H32 1 0 1 Num 1 Anti legionella treatment activation 2 H33 0 0...

Страница 17: ...04 and F03 2 DEFROST BRANCH DFR Parameter Default Limits Unit Description Level d01 0 0 1 2 Num 1 Defrost activation 0 disabled 1 active with hot gas 2 not available 2 d02 1 0 1 Num 1 Defrost exit mod...

Страница 18: ...isualizeActivation Compressor VisualizeActivation Elect Heater VisualizeActivation FAN VisualizeOn Off Elect Heater contactGND RES VisualizeOn Off Unit contactTIMER RES VisualizeValue ChangeValue Visu...

Страница 19: ...or the boiler according to the value of parameter H50 previously seen To ac tivate MANUAL mode press and hold FUNCTION key until LED L18 flashes then press SET key to confirm LED L18 remains steady on...

Страница 20: ...from Monday to Friday according to the following steps press FUNCTION key until flashing LED L10 is displayed press SET to confirm the selection LED L10 is steady on whereas LED L13 ON from time inter...

Страница 21: ...x ternal contact can be displayed near parameter Id4 1 on hold 0 enabled 3 20 Electric heating element function from remote ON OFF If you have a twin rate tariff and a suitable counter you may decide...

Страница 22: ...rd pressing the SET key once the cause of alarm has fixed ALARM E03 PROBE S01 FAILURE It is active if the sensor S01 sonda acqua serbatoio is short cir cuited or disconnected The alarm shuts off the u...

Страница 23: ...d cannot be either casually or accidentally electrically powered Therefore the electrical power must be disconnected any time maintenance work is carried out 9 9The customer must carry out all mainten...

Страница 24: ...pes vibrate The electric heating element does not switch on the start up is not necessary As a general rule however before calling for service try to power cycle the unit 9 9If the user is not able to...

Страница 25: ...25 MAINTENANCE...

Страница 26: ...26 MAINTENANCE...

Страница 27: ......

Страница 28: ...0442630111 Fax 044222378 www riello it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore lia...

Отзывы: