INSTALLATION

 

 

9

The manufacturer will not be held responsible for any 

damage caused by failure to earth the system or by abnormal 

power supply.

Electrical connections to the control panels must be carried out 
by specialised personnel.

2 .7 .1 

Electronic board

ID1

ID2

ID3

ID4

S01

S02

S04

S03

r8

UT

230V~50Hz

AE

GND

r2

r3

r4

SCH

r1

r7

SCH

  Electronic board

F

 Live

N

 Neutral

GND

 Earth/ground

UT

  User interface

AE

  Preset for electronic anode; connect to phase (FA) and 

neutral (NA) terminals to power the electronic anode 

(not supplied) with 230/1/50

Digital inputs

Initials Description

Status

Default

Notes

ID1

High pressure

1 open (alarm)

0 close

0

Connected

ID2

Low pressure

0 close

0

Preset only, 

not avail-

able

ID3

Electrical heater 

remote ON/OFF

1 enabled

0 standby

0

-

ID4

Unit remote ON/

OFF

1 standby

0 enabled

0

-

Analogue inputs

Initials Description

Notes

S01

water temperature probe

Con-

nected

S02

outdoor air temperature probe

Con-

nected

S03

evaporator intake temperature probe

Con-

nected

S04

evaporator output temperature probe

Con-

nected

Relays output

Initials Description

Status

Default

Note

r1

compressor igni-

tion enabling

1 enabled

0 disabled

1

Con-

nected

r2

electrical heater 

ignition ena-

bling

1 enabled

0 disabled

1

Con-

nected

r3

fan ignition 

enabling

1 enabled

0 disabled

1

Con-

nected

r4

solenoid valve 

enabling

1 enabled

0 disabled

1

Con-

nected

Other digital outputs

Initials Description

Status

Default

Notes

r7

volt-free contact 

for boiler ena-

bling

1 enabled

0 disabled

0

-

r8

valve opening 

steps 

electronic 

expansion

-

-

Con-

nected

2 .8 

Filling of the accumulation tank

To fill the accumulation tank of the unit:

 

− open the domestic hot water tap

 

− open the shut-off valve or the tap of domestic cold water, 

located on the safety unit. Check that the drain valve of 

the assembly is in closed position

When the water flows through the hot water tap, the unit is full. 

Close the hot water tap.

2 .9 

Controls before start-up

Before starting the unit, check:

 

− the correct connection of the ground wire.

 

− the presence of electrical protections

 

− that safety devices operate correctly

 

− that the system has been correctly filled.

Содержание NexPro Plus

Страница 1: ...cod Doc 0081361 rev 0 10 2016 NexPro Plus EN INSTALLATION AND MAINTENANCE MANUAL...

Страница 2: ...t Riello S p A CONFORMITY R NexPro Plus units comply with the European Directives Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Dir...

Страница 3: ...he operating modes 14 3 6 List of parameters 15 3 6 1 Parameters of electronic board inputs outputs 15 3 6 2 User parameters Utt 15 3 6 3 Installer parameters 15 3 7 Navigation diagram 18 3 8 Automati...

Страница 4: ...to the unit sit on it and or rest any type of object on it 0 0It is prohibited to spray or jet water directly onto the unit 0 0It is prohibited to open the doors for accessing the internal parts of th...

Страница 5: ...ith double layer glazing capacitor externally wrapped to the accumulation tank free from limescale deposits and gas water contamination auxiliary coil for the use in combination with boilers NexPro 30...

Страница 6: ...700 W Absorbed power in stand by mode 43 W Efficiency Energy WH 5 124 Annual consumption AEC 5 826 kWh Daily consumption QELEC 5 4000 Wh Maximum power input 6 5 A Load profile L Energy class A Refrig...

Страница 7: ...nvolved For handling use depending on the weight appropriate means as required by Directive 2006 42 EC and subsequent amendments 9 9The machine covering cannot withstand significant stress therefore i...

Страница 8: ...n environment and free from obstructions Comply with all applicable laws in force in the country where the machine is installed as regards the use and disposal of the products used for machine cleanin...

Страница 9: ...F Probe well G Cold water 1 F L Anode 1 1 4 F M Electrical heater 1 1 4 F NexPro 300 S Plus 1415 1242 800 845 1040 800 330 168 A M L E F G H I 5D 2D 1025 C A Hot water 1 F C Probe well E Recirculation...

Страница 10: ...er is supplied with a temperature over 50 C on the faucet of use can cause serious burns It therefore requires the use of a thermostatic mixing valve 9 9This valve will be required for solar panel ins...

Страница 11: ...cts must not exceed a total length of 10 meters sum of suction and outlet with diameter of the ducts equal to 160 mm Fan useful static head Pa mc h 0 0 50 100 150 200 250 100 200 300 400 500 600 2 7 E...

Страница 12: ...perature probe Con nected S04 evaporator output temperature probe Con nected Relays output Initials Description Status Default Note r1 compressor igni tion enabling 1 enabled 0 disabled 1 Con nected r...

Страница 13: ...ON OFF 6 Key Function L14 L1 L2 L3 L4 L5 L6 L7 L8 L19 L18 L17 L16 L15 L9 L10 L11 L12 L13 5D 2D L1 Unit activation from remote contact LED ON OFF L2 Compressor activation LED L3 Led electrical heater O...

Страница 14: ...key for 3 seconds to reset the counter of heat pump heating element and total runtime UP key stops the flashing of the LED rel evant to anti legionella treatment and re sets the relevant counter KEY S...

Страница 15: ...nge the parameter the change is automatically confirmed without pressing any other key the setpoint flashes for several seconds and the display shows the water temperature detected by the probe S01 Pa...

Страница 16: ...ual mode 2 H29 1 0 1 numero Enable air probe S02 0 disabled 1 enabled 2 H30 1 0 1 numero Enable digital input ID2 0 disabled 1 enabled 2 H32 1 0 1 Num 1 Anti legionella treatment activation 2 H33 0 0...

Страница 17: ...04 and F03 2 DEFROST BRANCH DFR Parameter Default Limits Unit Description Level d01 0 0 1 2 Num 1 Defrost activation 0 disabled 1 active with hot gas 2 not available 2 d02 1 0 1 Num 1 Defrost exit mod...

Страница 18: ...isualizeActivation Compressor VisualizeActivation Elect Heater VisualizeActivation FAN VisualizeOn Off Elect Heater contactGND RES VisualizeOn Off Unit contactTIMER RES VisualizeValue ChangeValue Visu...

Страница 19: ...or the boiler according to the value of parameter H50 previously seen To ac tivate MANUAL mode press and hold FUNCTION key until LED L18 flashes then press SET key to confirm LED L18 remains steady on...

Страница 20: ...from Monday to Friday according to the following steps press FUNCTION key until flashing LED L10 is displayed press SET to confirm the selection LED L10 is steady on whereas LED L13 ON from time inter...

Страница 21: ...x ternal contact can be displayed near parameter Id4 1 on hold 0 enabled 3 20 Electric heating element function from remote ON OFF If you have a twin rate tariff and a suitable counter you may decide...

Страница 22: ...rd pressing the SET key once the cause of alarm has fixed ALARM E03 PROBE S01 FAILURE It is active if the sensor S01 sonda acqua serbatoio is short cir cuited or disconnected The alarm shuts off the u...

Страница 23: ...d cannot be either casually or accidentally electrically powered Therefore the electrical power must be disconnected any time maintenance work is carried out 9 9The customer must carry out all mainten...

Страница 24: ...pes vibrate The electric heating element does not switch on the start up is not necessary As a general rule however before calling for service try to power cycle the unit 9 9If the user is not able to...

Страница 25: ...25 MAINTENANCE...

Страница 26: ...26 MAINTENANCE...

Страница 27: ......

Страница 28: ...0442630111 Fax 044222378 www riello it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore lia...

Отзывы: