MAINTENANCE

 

3 .24 

Counter reset

All User and Manufacturer parameters and runtimes are stored 

in memory. The runtime and anti-legionella count stops if pow-

er supply is missing and restarts from the status in which it was 

before power supply interruption. 

Press and hold   [DOWN] key for 3 seconds to reset the counter 

of heat pump, heating element, and total runtime.

3 .25 

Return to factory parameters

To restore the factory defaults you have to run the initialization 

procedure.  Starting  from  STANDBY  mode  (rightmost  point  ON) 

press   [UP] and    [DOWN] keys for 5 seconds.

To  confirm  the  procedure  the  display  will  show  the  message 

“ini”.

3 .26 

Further checks after commissioning

After  having  started  the  unit,  check  the  temperature  of  DHW 

temperature  probes  displayed.  If  the  values  detected  are  not 

correct, check the location of the probes in the probe holder 

socket.

Several days after unit starting, visually check any leaks in the 

water system or any clogging of the condensed water drainage.

MAINTENANCE

4 .1 

Routine maintenance

 

9

Maintenance interventions must be carried out by author-

ised personnel 

R

 or qualified personnel in accordance 

with the provisions of this booklet. Do not modify or tamper 

with the unit as dangerous situations may arise and the unit 

manufacturer will not be liable for any damage caused.

 

9

Before carrying out any maintenance work, make sure that 

the unit is not and cannot be, either casually or accidentally, 

electrically powered. Therefore, the electrical power must be 

disconnected any time maintenance work is carried out.

 

9

The customer must carry out all maintenance operations on 

the heat pump heater.

 

9

If the unit must be disassembled, protect your hands with 

gloves.

4 .1 .1 

Checks

At least once a year or in case of need it is recommended to per-

form the following checks.

 

− Control of the general conditions of the unit.

 

− General check of power consumption during the heat 

pump heater operation.

 

− Overall control of the operation of the electrical heater.

 

− Checking the tightness of all electrical connections.

 

− Control of the settings and programming parameters.

 

− Checking the status of the contacts of the fan and com-

pressor.

 

− Monitoring of air filters in the hydraulic circuit.

 

− Control the sacrificial anode.

 

− Check the operation of safety valve.

 

− Control the preload of expansion tank.

 

− Control of the general conditions of the unit and the in-

stallation  and testing of leaks.

 

− Checking the refrigerant charge.

 

− Control the filter dryer.

 

− Checking the condition of the refrigerant circuit.

 

− Control of the electrical heater.

 

− Check tightness of bolts, nuts, flanges and water connec-

tions that may have been loosened by the vibrations.

Furthermore, for better efficiency of the heat pump heater,, it is 

recommended to perform the following operations:

 

− periodically clean the evaporator using a soft bristled 

brush, taking care of using suitable protections against 

the injury hazard caused by the flaps

 

− check the fan cleaning conditions

 

− clean the condensate drain duct.

Содержание NexPro Plus

Страница 1: ...cod Doc 0081361 rev 0 10 2016 NexPro Plus EN INSTALLATION AND MAINTENANCE MANUAL...

Страница 2: ...t Riello S p A CONFORMITY R NexPro Plus units comply with the European Directives Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Dir...

Страница 3: ...he operating modes 14 3 6 List of parameters 15 3 6 1 Parameters of electronic board inputs outputs 15 3 6 2 User parameters Utt 15 3 6 3 Installer parameters 15 3 7 Navigation diagram 18 3 8 Automati...

Страница 4: ...to the unit sit on it and or rest any type of object on it 0 0It is prohibited to spray or jet water directly onto the unit 0 0It is prohibited to open the doors for accessing the internal parts of th...

Страница 5: ...ith double layer glazing capacitor externally wrapped to the accumulation tank free from limescale deposits and gas water contamination auxiliary coil for the use in combination with boilers NexPro 30...

Страница 6: ...700 W Absorbed power in stand by mode 43 W Efficiency Energy WH 5 124 Annual consumption AEC 5 826 kWh Daily consumption QELEC 5 4000 Wh Maximum power input 6 5 A Load profile L Energy class A Refrig...

Страница 7: ...nvolved For handling use depending on the weight appropriate means as required by Directive 2006 42 EC and subsequent amendments 9 9The machine covering cannot withstand significant stress therefore i...

Страница 8: ...n environment and free from obstructions Comply with all applicable laws in force in the country where the machine is installed as regards the use and disposal of the products used for machine cleanin...

Страница 9: ...F Probe well G Cold water 1 F L Anode 1 1 4 F M Electrical heater 1 1 4 F NexPro 300 S Plus 1415 1242 800 845 1040 800 330 168 A M L E F G H I 5D 2D 1025 C A Hot water 1 F C Probe well E Recirculation...

Страница 10: ...er is supplied with a temperature over 50 C on the faucet of use can cause serious burns It therefore requires the use of a thermostatic mixing valve 9 9This valve will be required for solar panel ins...

Страница 11: ...cts must not exceed a total length of 10 meters sum of suction and outlet with diameter of the ducts equal to 160 mm Fan useful static head Pa mc h 0 0 50 100 150 200 250 100 200 300 400 500 600 2 7 E...

Страница 12: ...perature probe Con nected S04 evaporator output temperature probe Con nected Relays output Initials Description Status Default Note r1 compressor igni tion enabling 1 enabled 0 disabled 1 Con nected r...

Страница 13: ...ON OFF 6 Key Function L14 L1 L2 L3 L4 L5 L6 L7 L8 L19 L18 L17 L16 L15 L9 L10 L11 L12 L13 5D 2D L1 Unit activation from remote contact LED ON OFF L2 Compressor activation LED L3 Led electrical heater O...

Страница 14: ...key for 3 seconds to reset the counter of heat pump heating element and total runtime UP key stops the flashing of the LED rel evant to anti legionella treatment and re sets the relevant counter KEY S...

Страница 15: ...nge the parameter the change is automatically confirmed without pressing any other key the setpoint flashes for several seconds and the display shows the water temperature detected by the probe S01 Pa...

Страница 16: ...ual mode 2 H29 1 0 1 numero Enable air probe S02 0 disabled 1 enabled 2 H30 1 0 1 numero Enable digital input ID2 0 disabled 1 enabled 2 H32 1 0 1 Num 1 Anti legionella treatment activation 2 H33 0 0...

Страница 17: ...04 and F03 2 DEFROST BRANCH DFR Parameter Default Limits Unit Description Level d01 0 0 1 2 Num 1 Defrost activation 0 disabled 1 active with hot gas 2 not available 2 d02 1 0 1 Num 1 Defrost exit mod...

Страница 18: ...isualizeActivation Compressor VisualizeActivation Elect Heater VisualizeActivation FAN VisualizeOn Off Elect Heater contactGND RES VisualizeOn Off Unit contactTIMER RES VisualizeValue ChangeValue Visu...

Страница 19: ...or the boiler according to the value of parameter H50 previously seen To ac tivate MANUAL mode press and hold FUNCTION key until LED L18 flashes then press SET key to confirm LED L18 remains steady on...

Страница 20: ...from Monday to Friday according to the following steps press FUNCTION key until flashing LED L10 is displayed press SET to confirm the selection LED L10 is steady on whereas LED L13 ON from time inter...

Страница 21: ...x ternal contact can be displayed near parameter Id4 1 on hold 0 enabled 3 20 Electric heating element function from remote ON OFF If you have a twin rate tariff and a suitable counter you may decide...

Страница 22: ...rd pressing the SET key once the cause of alarm has fixed ALARM E03 PROBE S01 FAILURE It is active if the sensor S01 sonda acqua serbatoio is short cir cuited or disconnected The alarm shuts off the u...

Страница 23: ...d cannot be either casually or accidentally electrically powered Therefore the electrical power must be disconnected any time maintenance work is carried out 9 9The customer must carry out all mainten...

Страница 24: ...pes vibrate The electric heating element does not switch on the start up is not necessary As a general rule however before calling for service try to power cycle the unit 9 9If the user is not able to...

Страница 25: ...25 MAINTENANCE...

Страница 26: ...26 MAINTENANCE...

Страница 27: ......

Страница 28: ...0442630111 Fax 044222378 www riello it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore lia...

Отзывы: