STARTING AND USE

 

The dynamic setpoint is enabled only for heat pump operation.

Dynamic Set Point parameters:

 

− H34 slope of the compensation line (value between 0.5 

and 2).

 

− H35 outdoor air temperature above which the compen-

sation starts (value between 15 e 25).

 

− H36 excursion of outdoor air temperature on which the 

set point works (value between 5 and 10).

Example:

Ut1=60°C; H34=1; H35=20°C; H36=10°C

When the dynamic set point is enabled (H33=1), we can have 

three cases:

1st Case

 

Tair <= H35 In that case Dynamic Set point = Ut1

2nd Case

 

H35 <Tair < (H35+H36) In that case Dynamic Set point= Ut1-[(Tair-

H35)*H34]

3rd Case

Tair > (H35+H36) In that case Dynamic Set point = Ut1-[H36*H34]

External air

(S02)

Setpoint

15

48

50

52

54

56

58

57

60

16 17 18 19

20

22

23

24 26 28 30 32

H36

Ut1

H35

3 .19 

Unit remote ON/OFF function

IT is possible to set the priority of activation of the various func-

tions, usually according to cost effectiveness. For example, if the 

unit is integrated in a solar system, For example, if the unit is 

integrated in a solar system, it can be advantageous to use solar 

energy as first resource, and when its contribution is no longer 

considerable, activate the heat pump heater.

For this purpose, the unit has a digital NO input (volt-free con-

tact) available on the basic board between the TIMERGND termi-

nals, enabled to receive information from an external source, or 

more generally from a timer.

 

9

It is possible to enable/disable the this function using the 

binary parameter H70.

H70 = 0  Function disabled

H70 = 1  Function enabled

When the function is enabled (H70=1), by pressing   [FUNCTION] 

key two conditions occur:

 

− If the contact (TIMER-GND) is OPEN the unit is OFF waiting 

to receive an input for starting. This condition is shown 

on the display by alternating the water temperature with 

label OFF. Led 1 is flashing.

 

− If the contact (TIMER-GND) is CLOSED, the unit has received 

an input for starting and starts normally. Led 1 is lit.

NOTE: in the navigation diagram, the machine status from ex-

ternal contact can be displayed near parameter Id4 . (1= on 

hold; 0= enabled) .

3 .20 

Electric heating element function from remote 
ON/OFF

If you have a twin rate tariff and a suitable counter, you may 

decide to use the electrical heater only in the hours where the 

use of electricity is more convenient.

For this purpose, the unit has a N.O. digital input (terminals RES-

GND) to enable / disable only the heater.

 

9

it is possible to enable / disable the Remote ON OFF setting 

the parameter H60. The function integration with electrical 

heater parameter H50=1 must be activated.

H60 = 0  Function disabled

H60 = 1  Function enabled

With function enabled (H60=1):

 

− if  contact  RES-GND  is  OPEN  (equivalent  to  Convenient 

two-hourly rate condition), the unit usually operates in 

AUTO mode, in order to activate the compressor or the 

heating element according to its calculation algorithm. 

LED L8 is OFF.

 

− If the input RES-GND is closed (equivalent to the non con-

venient use of electricity), the unit works normally with 

compressor only and the electrical heater never starts. In 

this mode any intervention request of the heating ele-

ment is indicated by LED L8 flashing (showing that the 

heating element activation request is in progress).

NOTE: in the navigation diagram, the heating element status 

from external contact can be displayed near parameter Id3 . (1= 

enabled; 0=on hold) .

3 .21 

Fan management (menu Fan)

The fan status is connected to the compressor one: the fan is 

activated if the compressor is activated.

Parameter F02,define the type of regulation:

 

F02

 = 0 ON/OFF regulation;

 

F02

 = 1 modulating regulation.

Modulating regulation (F02=1) parameters:

 

F03

  Minimum  fan  proportional  speed.  %  of  maximum 

voltage.

 

F04

 Maximum fan proportional speed. % of maximum 

voltage.

 

F05

 Temperature for minimum fan speed. It represents 

the air temperature above which the fan runs at mini-

mum speed.

 

F06

 Temperature for minimum fan speed. It represents 

the differential respect to F5, below which the fan run 

maximum speed (the colder the air, the greater the fan 

speed).

It is also possible, using parameter F07; to fix a value of water 

temperature, below which the fan ignores the adjustment, fol-

lowing the speed fixed to the parameter F04.

Содержание NexPro Plus

Страница 1: ...cod Doc 0081361 rev 0 10 2016 NexPro Plus EN INSTALLATION AND MAINTENANCE MANUAL...

Страница 2: ...t Riello S p A CONFORMITY R NexPro Plus units comply with the European Directives Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Dir...

Страница 3: ...he operating modes 14 3 6 List of parameters 15 3 6 1 Parameters of electronic board inputs outputs 15 3 6 2 User parameters Utt 15 3 6 3 Installer parameters 15 3 7 Navigation diagram 18 3 8 Automati...

Страница 4: ...to the unit sit on it and or rest any type of object on it 0 0It is prohibited to spray or jet water directly onto the unit 0 0It is prohibited to open the doors for accessing the internal parts of th...

Страница 5: ...ith double layer glazing capacitor externally wrapped to the accumulation tank free from limescale deposits and gas water contamination auxiliary coil for the use in combination with boilers NexPro 30...

Страница 6: ...700 W Absorbed power in stand by mode 43 W Efficiency Energy WH 5 124 Annual consumption AEC 5 826 kWh Daily consumption QELEC 5 4000 Wh Maximum power input 6 5 A Load profile L Energy class A Refrig...

Страница 7: ...nvolved For handling use depending on the weight appropriate means as required by Directive 2006 42 EC and subsequent amendments 9 9The machine covering cannot withstand significant stress therefore i...

Страница 8: ...n environment and free from obstructions Comply with all applicable laws in force in the country where the machine is installed as regards the use and disposal of the products used for machine cleanin...

Страница 9: ...F Probe well G Cold water 1 F L Anode 1 1 4 F M Electrical heater 1 1 4 F NexPro 300 S Plus 1415 1242 800 845 1040 800 330 168 A M L E F G H I 5D 2D 1025 C A Hot water 1 F C Probe well E Recirculation...

Страница 10: ...er is supplied with a temperature over 50 C on the faucet of use can cause serious burns It therefore requires the use of a thermostatic mixing valve 9 9This valve will be required for solar panel ins...

Страница 11: ...cts must not exceed a total length of 10 meters sum of suction and outlet with diameter of the ducts equal to 160 mm Fan useful static head Pa mc h 0 0 50 100 150 200 250 100 200 300 400 500 600 2 7 E...

Страница 12: ...perature probe Con nected S04 evaporator output temperature probe Con nected Relays output Initials Description Status Default Note r1 compressor igni tion enabling 1 enabled 0 disabled 1 Con nected r...

Страница 13: ...ON OFF 6 Key Function L14 L1 L2 L3 L4 L5 L6 L7 L8 L19 L18 L17 L16 L15 L9 L10 L11 L12 L13 5D 2D L1 Unit activation from remote contact LED ON OFF L2 Compressor activation LED L3 Led electrical heater O...

Страница 14: ...key for 3 seconds to reset the counter of heat pump heating element and total runtime UP key stops the flashing of the LED rel evant to anti legionella treatment and re sets the relevant counter KEY S...

Страница 15: ...nge the parameter the change is automatically confirmed without pressing any other key the setpoint flashes for several seconds and the display shows the water temperature detected by the probe S01 Pa...

Страница 16: ...ual mode 2 H29 1 0 1 numero Enable air probe S02 0 disabled 1 enabled 2 H30 1 0 1 numero Enable digital input ID2 0 disabled 1 enabled 2 H32 1 0 1 Num 1 Anti legionella treatment activation 2 H33 0 0...

Страница 17: ...04 and F03 2 DEFROST BRANCH DFR Parameter Default Limits Unit Description Level d01 0 0 1 2 Num 1 Defrost activation 0 disabled 1 active with hot gas 2 not available 2 d02 1 0 1 Num 1 Defrost exit mod...

Страница 18: ...isualizeActivation Compressor VisualizeActivation Elect Heater VisualizeActivation FAN VisualizeOn Off Elect Heater contactGND RES VisualizeOn Off Unit contactTIMER RES VisualizeValue ChangeValue Visu...

Страница 19: ...or the boiler according to the value of parameter H50 previously seen To ac tivate MANUAL mode press and hold FUNCTION key until LED L18 flashes then press SET key to confirm LED L18 remains steady on...

Страница 20: ...from Monday to Friday according to the following steps press FUNCTION key until flashing LED L10 is displayed press SET to confirm the selection LED L10 is steady on whereas LED L13 ON from time inter...

Страница 21: ...x ternal contact can be displayed near parameter Id4 1 on hold 0 enabled 3 20 Electric heating element function from remote ON OFF If you have a twin rate tariff and a suitable counter you may decide...

Страница 22: ...rd pressing the SET key once the cause of alarm has fixed ALARM E03 PROBE S01 FAILURE It is active if the sensor S01 sonda acqua serbatoio is short cir cuited or disconnected The alarm shuts off the u...

Страница 23: ...d cannot be either casually or accidentally electrically powered Therefore the electrical power must be disconnected any time maintenance work is carried out 9 9The customer must carry out all mainten...

Страница 24: ...pes vibrate The electric heating element does not switch on the start up is not necessary As a general rule however before calling for service try to power cycle the unit 9 9If the user is not able to...

Страница 25: ...25 MAINTENANCE...

Страница 26: ...26 MAINTENANCE...

Страница 27: ......

Страница 28: ...0442630111 Fax 044222378 www riello it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore lia...

Отзывы: