- Set the boiler to OFF
on the REC10 select the status menu and then
BOILER.
42
°C
MENU
STATE
SET
INFO
PLANT
HOT WATER TEMPERATURE
FRI
1.3
bar
18/05/2013
12:17
BOILER
MAIN ZONE
STATE
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
- Through the REC10 it is possible to access, using the TECHNICAL
menu, a series of parameters that can be programmed to allow you to
personalise the operation of the boiler based on the type of system.
- Then set the parameters according to the desired operating modes.
5.2.1
Boiler confi guration
- Access the technical parameters as explained in the section“ Accessing
the technical parameters”.
- Select PARAMETERS with the "
UP
" and "
DOWN
" keys , confirming the
selection.
PARAMETERS
WEATHER COMPENSATION
INSTALLATION
RANGE RATED
CALIBRATION
TECHNICAL
INSTALLER
Ø
- Select from among the options with the “
UP
” and “
DOWN
” keys,
confirming the selection.
ANTI-CYCLE FUNCTION
RESET CH TIMERS
DHW THERMOSTAT
PARAMETERS
INSTALLER
Ø
-
HEATING OFF
This parameter allows you to change the FORCED HEATING TIMING
OFF, regarding the delay time introduced for re-igniting the burner in the
face of an off due to the heating temperature being reached. The factory
setting for this parameter is 3 minutes and can be set to a value between
0 min and 20 min selecting the desired one with the “
UP
” and “
DOWN
”,
keys confirming the selection.
3
MIN
ANTI-CYCLE FUNCTION
-
RESET HEATING TIMES
This parameter allows you to reset the REDUCED HEATING MAXIMUM
OUTPUT TIMING, during which the speed of the fan is limited to 75%
of the maximum heating output that has been set, and the FORCED
HEATING TIMING OFF. The factory setting for this parameter is
FUNCTION INACTIVE, select FUNCTION ACTIVE using the “
UP
” and
“
DOWN
” keys, confirming the decision to reset the timings.
FUNCTION ACTIVE
RESET CH TIMERS
INSTALLER
FUNCTION NOT ACTIVE
-
DOMESTIC HOT WATER THERMOSTATS
This parameter allows you to set the type of DOMESTIC HOT WATER
THERMOSTATS.
The factory setting for this parameter is CORRELATED, i.e. for domestic
hot water the boiler switches off at se5°C and restarts at setpoint
+4°C.
To select the “ABSOLUTE” values, where the boiler for domestic hot
water will still switch off at 65°C and restart at 63°C, use the “
UP
” and
“
DOWN
” keys.