ADJUSTING THE FUNCTIONAL PARAMETERS

2 DHW_Type

 

Boiler type (parameter 6)

0 = No DHW service

1 = Quick exchanger with sensor

2 = Boiler with sensor

6 = Boiler with thermostat

In the case of a boiler with a thermostat, if the input is a closed 

contact, the DHW demand is activated, if it is an open contact 

the demand stops.

Preset to 0.

3 DHW_Priority

 

DHW priority (parameter 9)

0 = Shifting priority A

The purpose of shifting priority function A is that the system can 

also serve heating if the heating demand is low.

The system responds to the heating demand if:

(Setpoint_Ch - 50°C) < Temp_collettore < (Setpo 1°C)

Setpoint_Ch = Setpoint of the high or low temperature circuit 

depending on demand.

1 = Shifting priority B

The  purpose  of  shifting  priority  function  B  is  that  the  system 

never stops the heating service for too much time.

The system responds to the heating demand if:

(SetpoT_Tank_extra) - 50°C < Temp_collettore < (Set-

poi T_tank_extra) + 1°C

T_tank_extra = Par. 10 = preset to 30°C.

2 = Absolute priority (only DHW service)

Preset to 0.

9.3 

Heat control setting

1 Attenuation_High

 

HIGH TEMPERATURE circuit attenuation function (parameter 

21)

There are 2 cases:

 

− Fixed point operation Par. 14=0

 

− Operation with climatic control Par. 14=1.

FIXED POINT OPERATION, PAR. 14=0

With the high temperature circuit attenuation disabled, Par21=0 

when  the  high  temperature  circuit  thermostat  is  closed,  the 

heating demand is activated. When opened, the system turns 

off.

The  Master  control  unit  activates  the  high  temperature  circuit 

pump PZ1 and the system pump PZ2 (if parameter P34=0).

On the Master control unit it is possible to set the high tem-

perature circuit setpoint, Setpoint_T_CH_High = Par. 1, preset to 

70°C and settable from 10°C to T_CH_high_limit=Par 17, which is 

in turn preset to 80°C. The setpoint used will be the one set with 

parameter 1.

The burner is on when:

Manifold temperature <=Setpoint – ignition hysteresis.

Ignition hysteresis can be set, CH_High_hyst_on = Par. 19, preset 

to 7°C, can be set between 0 and 20°C.

The Master control unit converts the heat demand into power 

demand for each slave control unit.

The burners are off when:

Manifold temperature >=Se shut-off hysteresis .

Shut-off hysteresis can be set (CH_High_Hyst_off=Par. 20, preset 

to 3, can be set between 0 and 20°C).

With the high temperature circuit attenuation parameter, Par. 

21

0, the high temperature thermostat contact is ignored and a 

heat demand is present for the high temperature circuit when:

Manifold temperature <=Setpoint – ignition hysteresis

The heat demand stops when:

Manifold temperature >=Se shut-off hysteresis .

The setpoint in this case coincides with the value set for param-

eter 1 (Setpoint_t_ch_high) if the high temperature thermostat 

contact is closed, whereas it is calculated as the value set for 

parameter 1 less the attenuation (Setpoint_t_ch_high-Attenua-

tion_high) if the contact is open.

OPERATION WITH CLIMATIC CONTROL, PAR. 14=1

If the high temperature circuit attenuation is equal to 0 , Atten-

uation_high=Par. 21=0, its behaviour is the same as the previous 

paragraph,  with  the  exception  that  the  setpoint  is  calculated 

based on the outdoor temperature.

If the outdoor temperature = Tout_min=Par. 37, preset to 0°C, 

then setpoint =setpoint_T_Ch_high.

If the outdoor temperature = Tout_max=Par. 38, preset to 18°C, 

then setpoint T_ch_high_ foot=Par. 18, preset to 50°C.

The setpoint is calculated linearly between the 2 outdoor tem-

perature values.

Preset to 0.

2 Attenuation_Low

  LOW TEMPERATURE circuit attenuation function (parameter 

25)

This paragraph is similar to the previous paragraph for the low 

temperature circuit.

There are 2 cases:

 

− Fixed point operation Par. 22=0

 

− Operation with climatic control Par. 22=1.

FIXED POINT OPERATION, PAR. 22=0

With low temperature circuit attenuation disabled, Par. 25=0 at 

the closure of the low temperature circuit thermostat, heating 

demand is activated. When opened, the system turns off.

The  Master  control  unit  activates  the  low  temperature  circuit 

pump if the parameter for the third pump is set to 1 (P34=1).

On the Master control unit, it is possible to set the low temper-

ature circuit setpoint, Setpoint_T_CH_Low = Par. 3, preset to 40°C 

and can be set between 10°C and T_CH_low_limit=Par. 23, which 

in turn is preset to 50°C. The setpoint used will be the one set 

with parameter 3.

The burner is on when:

Manifold temperature <=Setpoint – ignition hysteresis.

Ignition hysteresis can be set, CH_Low_hyst_on = Par. 26, preset 

to 5°C, can be set between 0 and 20°C.

The Master control unit converts the heat demand into power 

demand for each slave control unit.

The burners are off when:

Manifold temperature >=Se shut-off hysteresis .

Shut-off hysteresis can be set (CH_Low_Hyst_off=Par. 27, preset 

to 3, can be set between 0 and 20°C).

With  the  low  temperature  circuit  attenuation  parameter,  Par. 

25

0, the low temperature thermostat contact is ignored and a 

heat demand is present for the low temperature circuit when:

Manifold temperature <=Setpoint – ignition hysteresis

The heat demand stops when:

Manifold temperature >=Se shut-off hysteresis .

The setpoint in this case coincides with the value set for param-

eter  3  (Setpoint_t_ch_low)  if  the  low  temperature  thermostat 

contact is closed, whereas it is calculated as the value set for 

parameter 3 less the attenuation (Setpoint_t_ch_low-Attenua-

Содержание Condexa Pro2 150 Evo IN A

Страница 1: ...cod 20094445 rev 5 12 2015 Condexa Pro2 EVO EN INSTALLATION INSTRUCTIONS...

Страница 2: ...supply 12 6 2 Electrical connections 12 6 2 1 Connection to mains 12 6 2 2 Connection to thermoregulators 12 6 2 3 Connection to pumps 13 6 2 4 Connection to room thermostats on off 14 6 2 5 Connecti...

Страница 3: ...weather conditions after it has been unpacked anyhow to temperatures below 4 C or above 40 C until it has been connected up to the water gas and electricity mains so as to be able to activate the fros...

Страница 4: ...ion for both single 0 0It is forbidden to obstruct the condensate drain 0 0It is forbidden to pull detach twist the wiring coming out of the heating unit even if unplugged from the power supply 0 0It...

Страница 5: ...o the system in parallel posi tion as compared to the others through a flow return gas flue manifold and condensate discharge manifold According to the heat demand the regulation system switches on an...

Страница 6: ...Fan 6 Return detection tap 7 Pump or 2 way valve 8 Control panel 9 Return probe 10 Exhaust flue probe 11 Water differential pressure switch 12 Gas valve 13 Ignition electrode 14 Automatic vent valve 1...

Страница 7: ...o 92 42 EEC Directive Max pressure and temperature Pms NOx class NOx Figure 6 0 0It is forbidden to remove or mishandle the identification plates markings and any other making it difficult to safely i...

Страница 8: ...o evenly dis tribute the limited quantity of initial lime scale 9 9A flushing cycle must be programmed after the plant has been installed to flush out any installation debris 9 9Water used for filling...

Страница 9: ...installation can vary according to specific requirements of space or to the type of the installation itself e g leaned against the wall back to back etc in any case make sure that same necessary spac...

Страница 10: ...s of each unit and in some points of the hydraulic system specific for this purpose For more information on the characteristics of hydraulic system see 5 Installation diagrams in which different types...

Страница 11: ...ly be adapted to the man ufacturing characteristics of the relevant heating unit with the purpose of exploiting the boiler potentials to the full and main tain the entire installation efficient for as...

Страница 12: ...should break call in qualified personnel to replace it Always re fer to the data given in the diagrams in this handbook for operations of an electrical nature Remember that R is not to be held liable...

Страница 13: ...ower on circulators external devices directly from the network with no electrical load passing through the fuse of the board Moreover in case of emergency mode the manual device 0 1 AUTO controls the...

Страница 14: ...14 related to the Ch1 high temperature system and 22 Ch2 low temperature system are in fact in default and set in weather function Should one not want to connect the probe the boiler must be made to...

Страница 15: ...t upper water manifold is equipped with two pock ets where the temperature probe has to be inserted The latter probe continuously checks the flow temperature of the heating circuit Either you are inst...

Страница 16: ...show the flow temperature e g T1 80 C Adjust combustion by the screws shown in Figure 17 until reaching the rated CO2 value see table turning the screws clockwise to reduce the value N B Turn an ti c...

Страница 17: ...ons activated by pressing a button or combination of two buttons pressed together Furthermore each button has a specific function depending on the selected user mode Figure 20 BUTTON KEY DESCRIPTION S...

Страница 18: ...e values and operating status of the various circuits Press the button to scroll forward and view the values set for the individual circuits The values listed below will be displayed in succession by...

Страница 19: ...oint to the desired value e g 40 C 5 Press OK to memorize the new value 6 After 3 secs the display will return to the display mode with the new setpoint If there is no change after pressing Set esc fo...

Страница 20: ...to view and change the user and installer parameters Procedure for accessing the programming mode POS PROCEDURE DISPLAY 1 Manifold delivery temperature T1 e g T1 80 C 2 Press Set esc and OK After 5s t...

Страница 21: ...ated for identifying the errors POS PROCEDURE DISPLAY 1 The display starts to flash to indicate one or more errors 1 b Press the address of the first unit will appear on the display alternating with t...

Страница 22: ...limit preset to 80 C 100 90 80 T_CH_High_foot 70 T_out_min 60 50 T_out_max 40 30 20 10 0 25 20 15 10 5 0 5 10 15 20 T_CH_High Delivery temperature C CLIMATIC CURVE HIGH TEMPERATURE CIRCUIT HEATING RE...

Страница 23: ...mperature Setpoint shut off hysteresis The setpoint in this case coincides with the value set for param eter 1 Setpoint_t_ch_high if the high temperature thermostat contact is closed whereas it is cal...

Страница 24: ...es the Master control unit can only add a new burner when another is on If the Master control unit must increase the number of ignited burners first check that the next burner can be ignited no er ror...

Страница 25: ...temperature or power The analogue input see terminals 13 14 on the wiring diagram on page 35 is only for the Master card and can also be used for the low temperature circuit Par 22 The analogue input...

Страница 26: ...od of time equal to half the value set in Par 29 Time s Collector temperature Figure 25 Temperature Flow Mix C 20 30 40 50 60 Closing Opening Valve s 4 3 2 1 0 1 3 25 35 45 55 2 Open Close default Par...

Страница 27: ...30 1 255 Setpoint of power supplied in hot water mode 8 h w max T 60 C 10 C 80 C Max value hot water setpoint 9 h w Priority 0 0 2 Hot water system priority 0 1 Hot water functioning with heating unti...

Страница 28: ...r valve stand by differential 33 Power control 1 0 1 0 power distributed over min number burners 1 power distributed over max number burners 34 Pump mode 0 0 1 Third pump setpoint 0 Main pump of syste...

Страница 29: ...32 33 Slaves not present Check that the bipolar switches of the individual units are ON Check the addresses on the slave Check the slave BUS connection Replace the Master card Replace the Slave card E...

Страница 30: ...It was pressed more than 7 times in 30 min Wait for the error to disappear If the error did not disappear after max 40 min re place the Slave card E35 35 Water differential pressure switch error cont...

Страница 31: ...J14 1 R1 4 3 T1 o t o m e r r t n o c s u b E o t o m e r r t n o c V 4 2 1 c r i c A T 2 c r i c A T 2 4 J1 PC E D O C R A B C T N 1 1 1 1 J 2 c r i c d n a m C T N 1 c r i c d n a m C T N C T N Pol...

Страница 32: ...n 2 3 4 J6 J14 J15 J2 F1 J8 J7 3 1 5 a 1 2 3 m gv gv 4 gv 1 T1 6 5 J6 a 5 m J2 3 2 1 4 gv 1 T1 Slave n 1 J3 2 3 1 J16 m a TO MAIN POLO GROUND TO MAIN POLO GROUND PUMP GROUND GROUND GROUND NEUTRAL PHAS...

Страница 33: ...ate production per hour 100 50 30 C with G20 gas kg h 22 4 33 6 44 8 Efficiency at rated power 80 60 C 98 1 98 1 98 1 Efficiency at rated power 50 30 C 108 1 108 1 108 1 Efficiency at min power 80 60...

Страница 34: ...fficiency in DHW mode WH Daily electrical energy consumption Qelec kWh Daily fuel consumption Qfuel kWh Annual electrical energy consumption AEC kWh Annual fuel consumption AFC GJ 14 WATER IN CENTRAL...

Страница 35: ...rms to require ments If the quality of water fails to conform to requirements either recondition the old water or separate the water circuits water in the boiler circuit must conform to requirements 3...

Страница 36: ...go VR Tel 0442630111 Fax 044222378 www riello it As part of the company s ongoing commitment to perfecting its range of products the appearance dimensions technical data equipment and accessories may...

Отзывы: