ELECTRICAL SYSTEM

ELECTRICAL SYSTEM

6.1 

Power supply

A detailed wiring diagram of the heating unit is shown in “12 

Wiring diagrams” page 31, at the diagram and technical data 

section.

Installation of the heating unit requires connection to a 230V - 

50Hz grid system and must be done with good workmanship in 

conformity to the electrical regulatory provisions in force.

It is best to install a differential circuit-breaker switch along the 

line supplying power to the boiler.

 

9

Adapters, multiple sockets, extensions to feed the appliance 

are not allowed.

The thermal generator must always be connected to the “master 

board” which contains the board that governs the system and 

manages probes of the circuit, pumps and accessories.

The  “Figure 11” is shown the terminal of the master board, with 

the connections to different external devices.

 

9

Always  check  the  effectiveness  of  the  electricity  earthing 

system,  compulsory  for  the  appliance  and  used  for  con-

necting up to the heating unit. The electronics could in fact 

put the entire heating unit into safety shutdown should the 

latter not be compatible.

 

9

Make sure that the water and heating pipes have not been 

used as earths for the electrical installation. They are abso-

lutely unsuited for this usage.

 

9

Wiring at a voltage of 230 V must be separated from those at 

a voltage of 24V, using raceways or separate PVC tubes.

 

9

Make  sure  that  the  electrical  features  (volt,  absorption, 

starting current, etc.) of the external electrical components 

(thermoregulators,  solenoid  valves,  weather  probes,  etc.) 

are compatible with the inlets and outlets available before 

connecting them up.

Relays and/or ancillary contactors are to be used to connect up 

the external electrical components, which must be installed on 

a special electrical board externally.

This solution also enables circulators, valves, etc. to function in 

emergency mode, i.e. should the boiler master board not be 

serviceable.

 

0

Do not touch the electrical apparatus with parts of the body 

wet or damp or with bare feet.

 

0

Do not leave the appliance exposed to atmospheric agents 

(rain, sun, wind, etc.) unless it is the special model for out 

of doors.

 

0

It is forbidden to pull, detach, twist the wiring coming out of 

the heating unit, even if unplugged from the power supply.

 

9

Do not allow people without experience to use the appliance 

and switch off the heating unit if the power cable should 

break; call in qualified personnel to replace it. Always re-

fer to the data given in the diagrams in this handbook for 

operations of an electrical nature. Remember that R is not 

to be held liable for any damages caused by ignoring the 

information given in the wiring diagrams of this manual.

 

0

Never  turn  off  the  boiler  while  it  is  functioning  normally 

(with burner ignited) suddenly cutting off the power supply 

with  the  on-off  switch.  This  could  cause  abnormal  over-

heating in the primary exchanger. Use a room thermostat 

or remote control to turn off (whilst heating system is on).

6.2 

Electrical connections

 

9

Qualified personnel only may work on the electrical system 

and in compliance to provisions of the law, with particular 

attention to rules on safety.

 

0

Lock the cables in their cable clamp designed to ensure the 

latter are always in the correct position inside the appliance.

6.2.1 

Connection to mains

When installing a single Condexa Pro2 EVO Series the connection 

must be made in accordance with current regulations regarding 

electrical safety, using a multi sheathed cable H05 VV-F-3GI with 

minimum section of the conductors of 1,5 mm

2

, suitably protect-

ed against moisture, abrasions and incidental contact.

The power cord must be connected to the terminal block on the 

left side of the instrument panel.

Fix the cable by its cable clamp and supplied anchorages to en-

sure it is correctly in place inside the appliance and to prevent 

it  from  coming  into  contact  with  parts  at  high  temperatures 

(burner, etc.).

 

9

The  length  of  the  grounding  cord  should  be  higher  than 

other conductors (phase, neutral). In case of disconnection 

of the power cord the cables of the conductors are strained 

before the grounding one

 

9

The  rubber  cableguides  placed  on  the  structure  of  the 

equipment have not to be removed because their purpose 

is to protect the cables from wear that occurs in direct con-

tact between cable and frame equipment. To pass a cable is 

sufficient to drill the cableguides.

6.2.2 

Connection to thermoregulators

Condexa Pro2 EVO heating units are equipped with an extreme-

ly versatile control and operating system, able to operate three 

independent systems functioning at different temperatures. The 

procedure for connecting up the output signal to the specific 

points on the terminal board will be illustrated in the following 

pages (see “Figure 11” ).

H05-VV-F type cables with minimum external diameter of 5mm 

and adequate conductor section may be used for thermoregu-

lation and low voltage systems, being careful to fix the latter to 

their cable guides.

Содержание Condexa Pro2 150 Evo IN A

Страница 1: ...cod 20094445 rev 5 12 2015 Condexa Pro2 EVO EN INSTALLATION INSTRUCTIONS...

Страница 2: ...supply 12 6 2 Electrical connections 12 6 2 1 Connection to mains 12 6 2 2 Connection to thermoregulators 12 6 2 3 Connection to pumps 13 6 2 4 Connection to room thermostats on off 14 6 2 5 Connecti...

Страница 3: ...weather conditions after it has been unpacked anyhow to temperatures below 4 C or above 40 C until it has been connected up to the water gas and electricity mains so as to be able to activate the fros...

Страница 4: ...ion for both single 0 0It is forbidden to obstruct the condensate drain 0 0It is forbidden to pull detach twist the wiring coming out of the heating unit even if unplugged from the power supply 0 0It...

Страница 5: ...o the system in parallel posi tion as compared to the others through a flow return gas flue manifold and condensate discharge manifold According to the heat demand the regulation system switches on an...

Страница 6: ...Fan 6 Return detection tap 7 Pump or 2 way valve 8 Control panel 9 Return probe 10 Exhaust flue probe 11 Water differential pressure switch 12 Gas valve 13 Ignition electrode 14 Automatic vent valve 1...

Страница 7: ...o 92 42 EEC Directive Max pressure and temperature Pms NOx class NOx Figure 6 0 0It is forbidden to remove or mishandle the identification plates markings and any other making it difficult to safely i...

Страница 8: ...o evenly dis tribute the limited quantity of initial lime scale 9 9A flushing cycle must be programmed after the plant has been installed to flush out any installation debris 9 9Water used for filling...

Страница 9: ...installation can vary according to specific requirements of space or to the type of the installation itself e g leaned against the wall back to back etc in any case make sure that same necessary spac...

Страница 10: ...s of each unit and in some points of the hydraulic system specific for this purpose For more information on the characteristics of hydraulic system see 5 Installation diagrams in which different types...

Страница 11: ...ly be adapted to the man ufacturing characteristics of the relevant heating unit with the purpose of exploiting the boiler potentials to the full and main tain the entire installation efficient for as...

Страница 12: ...should break call in qualified personnel to replace it Always re fer to the data given in the diagrams in this handbook for operations of an electrical nature Remember that R is not to be held liable...

Страница 13: ...ower on circulators external devices directly from the network with no electrical load passing through the fuse of the board Moreover in case of emergency mode the manual device 0 1 AUTO controls the...

Страница 14: ...14 related to the Ch1 high temperature system and 22 Ch2 low temperature system are in fact in default and set in weather function Should one not want to connect the probe the boiler must be made to...

Страница 15: ...t upper water manifold is equipped with two pock ets where the temperature probe has to be inserted The latter probe continuously checks the flow temperature of the heating circuit Either you are inst...

Страница 16: ...show the flow temperature e g T1 80 C Adjust combustion by the screws shown in Figure 17 until reaching the rated CO2 value see table turning the screws clockwise to reduce the value N B Turn an ti c...

Страница 17: ...ons activated by pressing a button or combination of two buttons pressed together Furthermore each button has a specific function depending on the selected user mode Figure 20 BUTTON KEY DESCRIPTION S...

Страница 18: ...e values and operating status of the various circuits Press the button to scroll forward and view the values set for the individual circuits The values listed below will be displayed in succession by...

Страница 19: ...oint to the desired value e g 40 C 5 Press OK to memorize the new value 6 After 3 secs the display will return to the display mode with the new setpoint If there is no change after pressing Set esc fo...

Страница 20: ...to view and change the user and installer parameters Procedure for accessing the programming mode POS PROCEDURE DISPLAY 1 Manifold delivery temperature T1 e g T1 80 C 2 Press Set esc and OK After 5s t...

Страница 21: ...ated for identifying the errors POS PROCEDURE DISPLAY 1 The display starts to flash to indicate one or more errors 1 b Press the address of the first unit will appear on the display alternating with t...

Страница 22: ...limit preset to 80 C 100 90 80 T_CH_High_foot 70 T_out_min 60 50 T_out_max 40 30 20 10 0 25 20 15 10 5 0 5 10 15 20 T_CH_High Delivery temperature C CLIMATIC CURVE HIGH TEMPERATURE CIRCUIT HEATING RE...

Страница 23: ...mperature Setpoint shut off hysteresis The setpoint in this case coincides with the value set for param eter 1 Setpoint_t_ch_high if the high temperature thermostat contact is closed whereas it is cal...

Страница 24: ...es the Master control unit can only add a new burner when another is on If the Master control unit must increase the number of ignited burners first check that the next burner can be ignited no er ror...

Страница 25: ...temperature or power The analogue input see terminals 13 14 on the wiring diagram on page 35 is only for the Master card and can also be used for the low temperature circuit Par 22 The analogue input...

Страница 26: ...od of time equal to half the value set in Par 29 Time s Collector temperature Figure 25 Temperature Flow Mix C 20 30 40 50 60 Closing Opening Valve s 4 3 2 1 0 1 3 25 35 45 55 2 Open Close default Par...

Страница 27: ...30 1 255 Setpoint of power supplied in hot water mode 8 h w max T 60 C 10 C 80 C Max value hot water setpoint 9 h w Priority 0 0 2 Hot water system priority 0 1 Hot water functioning with heating unti...

Страница 28: ...r valve stand by differential 33 Power control 1 0 1 0 power distributed over min number burners 1 power distributed over max number burners 34 Pump mode 0 0 1 Third pump setpoint 0 Main pump of syste...

Страница 29: ...32 33 Slaves not present Check that the bipolar switches of the individual units are ON Check the addresses on the slave Check the slave BUS connection Replace the Master card Replace the Slave card E...

Страница 30: ...It was pressed more than 7 times in 30 min Wait for the error to disappear If the error did not disappear after max 40 min re place the Slave card E35 35 Water differential pressure switch error cont...

Страница 31: ...J14 1 R1 4 3 T1 o t o m e r r t n o c s u b E o t o m e r r t n o c V 4 2 1 c r i c A T 2 c r i c A T 2 4 J1 PC E D O C R A B C T N 1 1 1 1 J 2 c r i c d n a m C T N 1 c r i c d n a m C T N C T N Pol...

Страница 32: ...n 2 3 4 J6 J14 J15 J2 F1 J8 J7 3 1 5 a 1 2 3 m gv gv 4 gv 1 T1 6 5 J6 a 5 m J2 3 2 1 4 gv 1 T1 Slave n 1 J3 2 3 1 J16 m a TO MAIN POLO GROUND TO MAIN POLO GROUND PUMP GROUND GROUND GROUND NEUTRAL PHAS...

Страница 33: ...ate production per hour 100 50 30 C with G20 gas kg h 22 4 33 6 44 8 Efficiency at rated power 80 60 C 98 1 98 1 98 1 Efficiency at rated power 50 30 C 108 1 108 1 108 1 Efficiency at min power 80 60...

Страница 34: ...fficiency in DHW mode WH Daily electrical energy consumption Qelec kWh Daily fuel consumption Qfuel kWh Annual electrical energy consumption AEC kWh Annual fuel consumption AFC GJ 14 WATER IN CENTRAL...

Страница 35: ...rms to require ments If the quality of water fails to conform to requirements either recondition the old water or separate the water circuits water in the boiler circuit must conform to requirements 3...

Страница 36: ...go VR Tel 0442630111 Fax 044222378 www riello it As part of the company s ongoing commitment to perfecting its range of products the appearance dimensions technical data equipment and accessories may...

Отзывы: