ELECTRICAL SYSTEM

6.2.4 

Connection to room thermostats (on/off)

Connect up the high temperature system room thermostat to 

terminals 9. and 10 (“Figure 11”).

The thermostat for the low temperature system must instead be 

connected to terminals n. 11 and 12 (“Figure 11”)..

6.2.5 

Connection to weather temperature probe

If  you  want  to  use  a  weather  thermoregulator,  the  external 

probe (optional) must be connected up to terminals n.7 and 8 (). 

The external probe must be placed on an outer wall facing north 

to north-east at a height of at least 2.5 metres and at a distance 

from windows, doors and air vents.

Protect the probe from direct exposure to the sun. Contact the 

Technical Assistance Service authorized by 

R

 if the curve has 

to be adjusted or the weather function excluded.

Correspondence table for all sensors

Measured temperatures (°C) - Resistive values of the sensors (

Ω

).

T (°C) R (

Ω

) T (°C) R (

Ω

) T (°C) R (

Ω

) T (°C) R (

Ω

)

-20

67739

13

15912

46

4751

79

1717

-19

64571

14

15289

47

4595

80

1669

-18

61568

15

14694

48

4444

81

1622

-17

58719

16

14126

49

4300

82

1577

-16

56016

17

13582

50

4161

83

1534

-15

53452

18

13062

51

4026

84

1491

-14

51018

19

12565

52

3897

85

1451

-13

48707

20

12090

53

3773

86

1411

-12

46513

21

11634

54

3653

87

1373

-11

44429

22

11199

55

3538

88

1336

-10

42449

23

10781

56

3426

89

1300

-9

40568

24

10382

57

3319

90

1266

-8

38780

25

9999

58

3216

91

1232

-7

37079

26

9633

59

3116

92

1199

-6

35463

27

9281

60

3021

93

1168

-5

33925

28

8945

61

2928

94

1137

-4

32461

29

8622

62

2839

95

1108

-3

31069

30

8313

63

2753

96

1079

-2

29743

31

8016

64

2669

97

1051

-1

28481

32

7731

65

2589

98

1024

0

27279

33

7458

66

2512

99

998

1

26135

34

7196

67

2437

100

973

2

25044

35

6944

68

2365

101

948

3

24004

36

6702

69

2296

102

925

4

23014

37

6470

70

2229

103

901

5

22069

38

6247

71

2164

104

879

6

21168

39

6033

72

2101

105

857

7

20309

40

5828

73

2040

106

836

8

19489

41

5630

74

1982

107

815

9

18706

42

5440

75

1925

108

796

10

17959

43

5258

76

1870

109

776

11

17245

44

5082

77

1817

110

757

12

16563

45

4913

78

1766

6.2.6 

Frost protection

The  heating  unit  electronic  control  includes  a  frost  protection 

function. When the flow temperature sinks to below a minimum 

value, the burners start working at minimum power according 

to the procedure used to set the functional parameters.

The frost protection mode is activated even if the external probe 

(supplied with the appliance) is not connected to the boiler: pa-

rameters 14 (related to the Ch1 high temperature system) and 22 

(Ch2 low temperature system) are in fact in default and set in 

weather function.

Should one not want to connect the probe, the boiler must be 

made to work at a fixed point to avoid problems. The parameter 

14 and 22 settings may only be altered by a Technical Assistance 

Service authorized by 

R

.

 

9

Power and fuel gas supply must be activated and the water 

system at a correct pressure for the frost protection system 

to function.  

 

9

QGlycol can be used as an additive for the system (up to a 

maximum of 50%) there where considered necessary by the 

person responsible for the project, keeping in mind that this 

substantially reduces efficiency as it alters the specific heat 

of the fluid. Furthermore several parts of the system could 

be damaged by altering the pH.

6.2.7 

Connection to 0-10v external 
thermoregulator

An external thermoregulator connection using a 0 – 10 v signal 

could be used by connecting the output signal to terminals n.13 

and 14 (“Figure 11”).

 

9

The positive pole of the signal output must be connected to 

terminal 13 for the device to work correctly.

6.2.8 

Connection to alarm device

A beeping or visual alarm device, to signal any technical faults, 

may be connected outside by a special output with clean con-

tact on the boiler terminal board.

The alarm device must be connected to terminals n.18 and 19 

(“Figure 11”).

6.2.9 

Remote control 

If the remote control is to be used, it must be connected to ter-

minals no. 15, 16 and 17 (”Figure 11”).

6.3 

Emergency mode

The Condexa Pro2 EVO electronic control system includes a func-

tional mode called “Emergency”, which can be activated in case 

of a Master board malfunction.

The master board can in fact be excluded so as to enable the 

system to work with a flow temperature preset in default by the 

manufacturer,  guaranteeing  the  heating  unit  with  continual 

service.

 

9

Qualified personnel only may work on the electrical system 

and in compliance to provisions of the law, with particular 

attention to rules on safety.

The following procedure must be adopted to enable the “Emer-

gency” function:

 

− Disconnect  the  4-pole  J14  connector  from  the  master 

board (see “Figure 12” );

 

− set all four J17 switches located on each Slave of the ther-

mal assembly on the Off position (see “Figure 13” );

 

− Supply power to all the circulators in the system direct-

ly from the mains using the specific relays/change-over 

switches;

 

− Connect terminal X1 or terminal X2 (which are part of the 

J14 connector wiring disconnected during the first step 

of this procedure) to a 24 V ac power supply (see ”Figure 

15”).

Содержание Condexa Pro2 150 Evo IN A

Страница 1: ...cod 20094445 rev 5 12 2015 Condexa Pro2 EVO EN INSTALLATION INSTRUCTIONS...

Страница 2: ...supply 12 6 2 Electrical connections 12 6 2 1 Connection to mains 12 6 2 2 Connection to thermoregulators 12 6 2 3 Connection to pumps 13 6 2 4 Connection to room thermostats on off 14 6 2 5 Connecti...

Страница 3: ...weather conditions after it has been unpacked anyhow to temperatures below 4 C or above 40 C until it has been connected up to the water gas and electricity mains so as to be able to activate the fros...

Страница 4: ...ion for both single 0 0It is forbidden to obstruct the condensate drain 0 0It is forbidden to pull detach twist the wiring coming out of the heating unit even if unplugged from the power supply 0 0It...

Страница 5: ...o the system in parallel posi tion as compared to the others through a flow return gas flue manifold and condensate discharge manifold According to the heat demand the regulation system switches on an...

Страница 6: ...Fan 6 Return detection tap 7 Pump or 2 way valve 8 Control panel 9 Return probe 10 Exhaust flue probe 11 Water differential pressure switch 12 Gas valve 13 Ignition electrode 14 Automatic vent valve 1...

Страница 7: ...o 92 42 EEC Directive Max pressure and temperature Pms NOx class NOx Figure 6 0 0It is forbidden to remove or mishandle the identification plates markings and any other making it difficult to safely i...

Страница 8: ...o evenly dis tribute the limited quantity of initial lime scale 9 9A flushing cycle must be programmed after the plant has been installed to flush out any installation debris 9 9Water used for filling...

Страница 9: ...installation can vary according to specific requirements of space or to the type of the installation itself e g leaned against the wall back to back etc in any case make sure that same necessary spac...

Страница 10: ...s of each unit and in some points of the hydraulic system specific for this purpose For more information on the characteristics of hydraulic system see 5 Installation diagrams in which different types...

Страница 11: ...ly be adapted to the man ufacturing characteristics of the relevant heating unit with the purpose of exploiting the boiler potentials to the full and main tain the entire installation efficient for as...

Страница 12: ...should break call in qualified personnel to replace it Always re fer to the data given in the diagrams in this handbook for operations of an electrical nature Remember that R is not to be held liable...

Страница 13: ...ower on circulators external devices directly from the network with no electrical load passing through the fuse of the board Moreover in case of emergency mode the manual device 0 1 AUTO controls the...

Страница 14: ...14 related to the Ch1 high temperature system and 22 Ch2 low temperature system are in fact in default and set in weather function Should one not want to connect the probe the boiler must be made to...

Страница 15: ...t upper water manifold is equipped with two pock ets where the temperature probe has to be inserted The latter probe continuously checks the flow temperature of the heating circuit Either you are inst...

Страница 16: ...show the flow temperature e g T1 80 C Adjust combustion by the screws shown in Figure 17 until reaching the rated CO2 value see table turning the screws clockwise to reduce the value N B Turn an ti c...

Страница 17: ...ons activated by pressing a button or combination of two buttons pressed together Furthermore each button has a specific function depending on the selected user mode Figure 20 BUTTON KEY DESCRIPTION S...

Страница 18: ...e values and operating status of the various circuits Press the button to scroll forward and view the values set for the individual circuits The values listed below will be displayed in succession by...

Страница 19: ...oint to the desired value e g 40 C 5 Press OK to memorize the new value 6 After 3 secs the display will return to the display mode with the new setpoint If there is no change after pressing Set esc fo...

Страница 20: ...to view and change the user and installer parameters Procedure for accessing the programming mode POS PROCEDURE DISPLAY 1 Manifold delivery temperature T1 e g T1 80 C 2 Press Set esc and OK After 5s t...

Страница 21: ...ated for identifying the errors POS PROCEDURE DISPLAY 1 The display starts to flash to indicate one or more errors 1 b Press the address of the first unit will appear on the display alternating with t...

Страница 22: ...limit preset to 80 C 100 90 80 T_CH_High_foot 70 T_out_min 60 50 T_out_max 40 30 20 10 0 25 20 15 10 5 0 5 10 15 20 T_CH_High Delivery temperature C CLIMATIC CURVE HIGH TEMPERATURE CIRCUIT HEATING RE...

Страница 23: ...mperature Setpoint shut off hysteresis The setpoint in this case coincides with the value set for param eter 1 Setpoint_t_ch_high if the high temperature thermostat contact is closed whereas it is cal...

Страница 24: ...es the Master control unit can only add a new burner when another is on If the Master control unit must increase the number of ignited burners first check that the next burner can be ignited no er ror...

Страница 25: ...temperature or power The analogue input see terminals 13 14 on the wiring diagram on page 35 is only for the Master card and can also be used for the low temperature circuit Par 22 The analogue input...

Страница 26: ...od of time equal to half the value set in Par 29 Time s Collector temperature Figure 25 Temperature Flow Mix C 20 30 40 50 60 Closing Opening Valve s 4 3 2 1 0 1 3 25 35 45 55 2 Open Close default Par...

Страница 27: ...30 1 255 Setpoint of power supplied in hot water mode 8 h w max T 60 C 10 C 80 C Max value hot water setpoint 9 h w Priority 0 0 2 Hot water system priority 0 1 Hot water functioning with heating unti...

Страница 28: ...r valve stand by differential 33 Power control 1 0 1 0 power distributed over min number burners 1 power distributed over max number burners 34 Pump mode 0 0 1 Third pump setpoint 0 Main pump of syste...

Страница 29: ...32 33 Slaves not present Check that the bipolar switches of the individual units are ON Check the addresses on the slave Check the slave BUS connection Replace the Master card Replace the Slave card E...

Страница 30: ...It was pressed more than 7 times in 30 min Wait for the error to disappear If the error did not disappear after max 40 min re place the Slave card E35 35 Water differential pressure switch error cont...

Страница 31: ...J14 1 R1 4 3 T1 o t o m e r r t n o c s u b E o t o m e r r t n o c V 4 2 1 c r i c A T 2 c r i c A T 2 4 J1 PC E D O C R A B C T N 1 1 1 1 J 2 c r i c d n a m C T N 1 c r i c d n a m C T N C T N Pol...

Страница 32: ...n 2 3 4 J6 J14 J15 J2 F1 J8 J7 3 1 5 a 1 2 3 m gv gv 4 gv 1 T1 6 5 J6 a 5 m J2 3 2 1 4 gv 1 T1 Slave n 1 J3 2 3 1 J16 m a TO MAIN POLO GROUND TO MAIN POLO GROUND PUMP GROUND GROUND GROUND NEUTRAL PHAS...

Страница 33: ...ate production per hour 100 50 30 C with G20 gas kg h 22 4 33 6 44 8 Efficiency at rated power 80 60 C 98 1 98 1 98 1 Efficiency at rated power 50 30 C 108 1 108 1 108 1 Efficiency at min power 80 60...

Страница 34: ...fficiency in DHW mode WH Daily electrical energy consumption Qelec kWh Daily fuel consumption Qfuel kWh Annual electrical energy consumption AEC kWh Annual fuel consumption AFC GJ 14 WATER IN CENTRAL...

Страница 35: ...rms to require ments If the quality of water fails to conform to requirements either recondition the old water or separate the water circuits water in the boiler circuit must conform to requirements 3...

Страница 36: ...go VR Tel 0442630111 Fax 044222378 www riello it As part of the company s ongoing commitment to perfecting its range of products the appearance dimensions technical data equipment and accessories may...

Отзывы: