8
INStAllAtION
Model
100
125
140
Product dimensions
H
680
680
680
mm
L
1325
1650
1650
mm
P
230
230
230
mm
Weight
33,5
43,0
43,0
kg
2.4
Storage
9
The product must be stored of according to the regulations
in force.
2.5
Handling and removal of the packing
9
before unpacking, personal protective clothing should be
worn and used transport means and tools suitable for the
size and weight of the unit.
The product can be handled manually.
Follow the below instructions for packing removal and product
handling:
—
transport the equipment in the installation place
—
cut strapping bands
—
remove the packaging cover
—
remove the protection elements
—
remove the polyethylene bag
—
remove the document envelope
—
take out the device by lifting it up
—
remove accessories and control panel from the fan com-
partment
9
In manual operation it is compulsory to respect always the
maximum weight per person provided for by the national
laws and standards.
9
Handle with care
9
The packing material must not be disposed of in the sur-
rounding environment and must be kept out of children
reach, as it can be dangerous. It must be disposed of ac-
cording to the regulations in force.
2.6
Place of installation
The location of
R
AMS P
devices must be determined by the
system's designer or by another competent person, and must
take into account the technical requirements, as well as any
current local regulations.
9
The product uses R32 refrigerant gas and must be installed
in rooms with a minimum floor area, as indicated in the
following table, depending on the total refrigerant charge
of the system (given by the sum of the factory charge of the
outdoor unit and, if appicable, the additional charge).
9
The amount of refrigerant charged inside the unit refer to
the INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS of out-
door unit used.
Minimum floor area for ceiling installation
mc
kg
A min
m²
mc
kg
A min
m²
0,2
No requirements
2,1
2,81
0,6
2,2
3,09
0,8
2,3
3,38
1,0
2,4
3,68
1,1
2,5
3,99
1,224
2,6
4,31
1,225
0,96
2,8
5,00
1,3
1,08
3,0
5,74
1,4
1,25
3,4
7,38
1,5
1,44
3,8
9,22
1,6
1,63
4,2
11,26
1,7
1,84
4,6
13,50
1,8
2,07
5,0
15,96
1,9
2,30
5,4
18,61
2,0
2,55
5,8
21,47
mc:
refrigerant charge of the system
A min:
minimum floor area for indoor unit
Minimum floor area for floor installation
mc
kg
A min
m²
mc
kg
A min
m²
0,2
No requirements
2,1
37,84
0,6
2,2
41,53
0,8
2,3
45,39
1,0
2,4
49,42
1,1
2,5
53,63
1,224
2,6
58,00
1,225
12,88
2,8
67,27
1,3
14,50
3,0
77,22
1,4
16,82
3,4
99,19
1,5
19,31
3,8
123,90
1,6
21,97
4,2
151,36
1,7
24,80
4,6
181,56
1,8
27,80
5,0
214,51
1,9
30,98
5,4
250,21
2,0
34,32
5,8
288,65
mc:
refrigerant charge of the system
A min:
minimum floor area for indoor unit
R
AMS P
is designed for indoor ceiling or floor installation:
—
install the indoor unit in the room to be air-conditioned
—
its position must allow for the circulation of treated air in
the whole room
—
consider an area where there are no obstacles to the reg-
ular air delivery and intake
Check that:
—
the support wall is able to support the device weight
—
the wall section does not feature building supporting ele-