11
INStAllAtION
With false ceiling
1
Hole in false ceiling
2
false ceiling
2
1
1
40
40
10
640
A
Model
100
125
140
template dimensions
A
1204
1530
mm
—
make an opening in the false ceiling
1
Insulating material
1
9
Apply the thermal insulating suitable material to prevent
and the formation of condensation.
—
regulate the height of installation of the unit
—
center the unit over the opening
10 ÷ 15
10 ÷ 15
—
regulate the unit’s position so as to create a slope towards
the condensation drainage
—
tighten the fastening nut
9
Seal the nuts with some liquid thread lock.
9
The support rods must be attached to structures able to
support the weight of the unit.
9
The incorrect positioning of the device can cause water
leakage.
Vertical positioning on floor
1
Anti-vibration mountings
1
before positioning:
—
fasten the anti-vibration supports supplied with the de-
vice