9
GENERAL INFORMATION
1.7
Technical specifications
Description
Steel Pro Power
U.M.
114-2 P/V
140-2
P/V
180-2
P/V
230-2
P/V
270-2
P/V
TYPE OF APPLIANCE
Appliance type
Condensing boiler heating system
B23, B53; B53P
Fuel
G20-G25-G30-G31
Combustion chamber
vertical
Flue exhaust homologations
B23, B23P, B53P, C13(*), C33(*), C53(*), C63(*)
Device category according to UNI 10642
II2H3P
POWERS AND EFFICIENCY
Nominal rated heat input (PCI)
114
136
180
223,2
262
kW
Nominal rated heat input (PCS)
126
152
200
248
292
kW
Maximum rated heat output (80°-60°C)
G20
111,4
134
176,6
219,6
258
kW
Maximum rated heat output (60-40°C)
G20
119,2
142,8
187,6
232,4
274,6
kW
Maximum rated heat output (50-30°C)
G20
123,8
147,8
194,8
242,2
284,2
kW
Minimum rated heat input (PCI)
G20
13,7
13,7
19,4
22,4
26,3
kW
Minimum rated heat input (PCS)
G20
15
15
21,6
24,9
29
kW
Minimum thermal output 80/60°C
G20
13,5
13,5
19,2
22,1
26
kW
Minimum thermal output 50/30°C
G20
14,9
14,9
21,1
24,5
28,9
kW
Useful efficiency at nominal heat output 80-60°C (PCI)
97,72
98,53
98,11
98,40
98,47
%
Useful efficiency at minimum heat output 80-60°C (PCI)
98,9
98,9
98,8
99,2
99,1
%
Useful efficiency at nominal heat output 50/30°C (PCI)
108,6
108,1
108,3
108,6
108,3
%
Useful efficiency at minimum heat output 50/30°C (PCI)
109,3
109,3
109,2
110
110
%
Useful efficiency 30% - 50/30°C PCS (PCI)
98,94
(109,36)
97,81
(109,31)
98,00
(108,89)
98,39
(108,93)
98,17
(109,41)
%
Combustion efficiency
99,0
99,0
99,0
99,3
99,3
%
Chimney losses with burner off
0,1
0,1
0,1
0,1
0,1
%
Chimney losses with burner on P. max. 80-60°C
2,3
2,3
2,5
2,5
2,6
%
Chimney losses with burner on at 30% Pn 50-30°C
0,5
0,5
0,6
0,5
0,6
%
Chimney losses with burner on P. min. 80-60°C
0,12
0,11
0,22
0,1
0,1
%
Losses through the casing with average T 70°C and burn-
er on
0,5
0,5
0,5
0,5
0,5
%
Losses through the casing with average T 70°C and burn-
er off
0,5
0,5
0,5
0,5
0,5
%
Flue gas temperature at max power and min power 80-
60°C
71 - 61
72 - 61
76 - 62
75 - 61
77 - 61
°C
Flue gas temperature at max power and min power 50-
30°C
45 - 33
46 - 33
47 - 35
45 - 33
48 - 35
°C
Air index
λ
at max power
G20
1,27
1,27
1,27
1,27
1,27
no.
G31
1,29
1,29
1,29
1,29
1,29
no.
Air index
λ
at min power
G20
1,27
1,27
1,27
1,27
1,27
no.
G31
1,29
1,29
1,29
1,29
1,29
no.
Max Flue flow at max-min power
G20
53 - 6
64 - 6
84 - 9
104 - 10
122 - 12
g/s
G31
51 - 6
62- 6
82 - 9
101 - 10
119 - 12
g/s
Flue Residual prevalence at min power
35
35
32
30
28
Pa
Flue gas residual head with max power
510
630
560
500
353
Pa
Maximum rated heat input (LCV)
G25
106
130
170
214
254
kW
Minimum rated heat input (LCV)
G25
13
13
18,1
21,4
24,5
kW
(*)
Configurations possible only with the installation of the dedicated accessories (available separately).
Содержание 20138572
Страница 109: ...109 SYSTEM MANAGER RECYCLING AND DISPOSAL...
Страница 110: ...110 SYSTEM MANAGER RECYCLING AND DISPOSAL...
Страница 111: ...111 SYSTEM MANAGER RECYCLING AND DISPOSAL...