CASCADE CONNECTION
4.1.2
Setting the dip-switch
9
Perform this operation only on the cascade-connected
thermal modules such as "DEPENDING".
The dip-swich of all the thermal elements in the system must be
set and each must be set with a unique sequence.
In this way, the central unit of the managing module will be
able to recognize how many thermal elements are present in
the system.
To access the dip-switches, open the hatch using a flat-bladed
screwdriver.
9
The dip-switches must be configured in sequence. The
thermal module 1 will always be correct because the config-
uration has not been changed. From the thermal module 2
onwards, after modifying the configuration (from "MANAG-
ING" to "DEPENDING"), it is necessary to keep the elements
in a sequence.
9
For the configuration of each thermal element refer to the
following table.
Key
Dip switch ON
Dip switch OFF
Setting the Dip-switch
Thermal Element
Configuration
1
ON
DIP
2 3 4 5 6 7 8
3rd element (depending)
1
ON
DIP
2 3 4 5 6 7 8
4th element (depending)
$
$
1
ON
DIP
2 3 4 5 6 7 8
8th element (depending)
1
ON
DIP
2 3 4 5 6 7 8
9th element (depending)
1
ON
DIP
2 3 4 5 6 7 8
1
ON
DIP
2 3 4 5 6 7 8
10th element (depending)
Thermal module
1
M D
1
D
2
D
3
M D
1
D
9
D
8
M D
1
D
4
D
5
D
2
D
3
D
6
D
7
Thermal module
2
Thermal module
3