- 39 -
PROBLEM
POSSIBLE CAUSE
SOLUTION
THE DISPLAY SHOWS
THE FOLLOWING CODE:
C01
THE JUMPER IS MISSING
FROM THE R.E.P.O.
CONNECTOR OR IT IS NOT
INSERTED CORRECTLY
Assemble the jumper or make sure that it is inserted
correctly.
THE DISPLAY SHOWS
THE FOLLOWING CODE:
C05
MAINTENANCE BYPASS
ISOLATOR (SWMB) CLOSED
Open the isolator (SWMB).
THE JUMPER IS MISSING
FROM THE TERMINALS
“SWITCH BYPASS”
Insert the jumper
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A30, A32
AND THE UPS DOES
NOT START UP
AMBIENT
TEMPERATURE < 0°C
Heat the environment,
wait for the heat sink temperature
to rise above 0°C and then start up the UPS
FAULT IN HEAT SINK
TEMPERATURE PROBE
Activate the maintenance bypass (SWMB) if present,
turn the UPS
off and back on again and exclude the
maintenance bypass. If the problem persists, contact the
nearest service centre
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F09, F10
THE VOLTAGE VALUE OF
PHASE 1 IS NOT SUFFICIENT
TO PRE-LOAD THE UPS
Wait for the input network voltage values to stabilise
within the ranges accepted by the UPS.
FAULT IN THE UPS INPUT
STAGE
Activate the maintenance bypass (SWMB) if present,
turn the UPS off then back on again. Exclude the
maintenance bypass. If the problem persists, contact the
nearest service centre.
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F11, F14, F17, L06, L07,
L08, L09, L14, L17, L20
ANOMALOUS LOADS APPLIED
Remove the load. Insert the maintenance bypass
(SWMB) if present, turn the UPS off and back on again.
Exclude the maintenance bypass. If the problem
persists, contact the nearest service centre
FAULT IN THE INPUT OR
OUTPUT STAGE OF THE UPS
Activate the maintenance bypass (SWMB) if present,
turn the UPS off and back on again. Exclude the
maintenance bypass. If the problem persists, contact the
nearest service centre
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F03, F04, F05, A08, A09,
A10
CONNECTION MISSING ON
ONE OR MORE PHASES
(ONLY FOR TM VERSION)
With the three-phase connection the switch must be in
position “
↑
3~”.
Check the connection of Phase 2 and Phase 3.
CHECK THE POSITION OF
THE SWITCH ON THE REAR
OF THE UPS
(ONLY FOR TM VERSION)
With the single-phase connection the switch must be in
position “
↓
1~”.
Check the position of the switch selector.
INTERNAL PROTECTION
FUSES ON THE PHASE OR
ON THE INPUT RELAY
BROKEN
Contact the nearest service centre