S
EPARATE
B
YPASS
I
NPUT
(
ONLY FOR
“DI”
VERSIONS
)
THE “DI” VERSION OF THE UPS SERIES HAS A BYPASS LINE SEPARATE FROM THE INPUT LINE.
The UPS series with Separate Bypass allows for making a separate connection between the input line and the bypass line.
The UPS output will be synchronised with the bypass line in such a way that there will not be any incorrect switching between
push-pull voltages if the automatic bypass intervenes or the maintenance bypass switch (SWMB) is closed.
A
DDITIONAL
I
NTERNAL
B
ATTERY
C
HARGERS
(
ONLY FOR
“ER”
VERSIONS
)
THE “
ER”
VERSION OF UPS DIFFERS FROM THE STANDARD VERSION IN THAT ADDITIONAL BATTERY CHARGERS
ARE USED INSTEAD OF THE BATTERIES .
This series of UPS must be used together with an external Battery Box and is suitable for applications requiring long back-up
times .
T
HREE
-
PHASE INPUT
(“TM”
VERSIONS ONLY
)
THE “TM” VERSION OF THE UPS SERIES ALLOWS FOR INSTALLING A UPS POWERED BY A THREE-PHASE OR
SINGLE-PHASE LINE.
In the THREE-PHASE connection, the load current will be split between the three input phases; if the bypass intervenes or in
the bypass mode operation, all the load current will be absorbed by the “L1” input line.