5.2 Electrical material
•
A minimum conductor cross-section of 1.5 mm² is applicable to the cables in the general
wiring diagrams. For the used components, electrical material and cable lengths the necessary
conductor cross-section can be different.
RW243/245/400/600\RW800\RW70/140 [RSU]
•
Motor-current connection through the RSU limit-switch system is
not permitted
!
The limit-switch system is applicable for the currents that follow:
•
45 mA–130 mA
at 24 V AC/DC
• A
maximum
of
100 mA
at 115/230/240 V.
RW45\RW241/242 [RLS]
•
Motor-current connection or control-circuit connection through the RLS limit-switch
is permitted
.
The limit-switch system is applicable for the currents that follow:
•
45 mA–130 mA
at 24 V AC/DC
• A
maximum
of
4 A
at 115 V
• A
maximum
of
2.25 A
at 230/240 V.
Use only applicable components and electrical material.
Always refer to the related information and manuals.
The RSU limit-switch system is NOT applicable for motor-current
connection through the limit switches.