A - CONNEXIONS
INNER THERMAL OVERLOAD CUT-OUT SWITCHES
(per CEI 2-3/IEC 34-1)
The electrical protections on the SUPER 6000 motor
power line may not be sufficient to protect against
overloads. If the cooling conditions worsen, the
motor overheats but the electrical conditions do not
change, which inhibits line protections.
Installing
the bimetallic device PTO on the L1/R4-CRX control
panel solves this problem.
This is a normally-closed electromechanical device
that opens when the threshold
temperature is reached; it
automatically resets when the
temperature falls below the
threshold level.
TT
TT
IT IS COMPULSORY TO SET THE DIP
13 OF THE CONTROL PANEL IN THE ON
POSITION.
J1
L1 - N
230 Vac 50/60Hz power supply (120Vac 60Hz upon request)
J2
Flashing light (max 40W )
U
Motor common connection
V-W
Motor phases and capacitor connections
J3
R-AUX
Auxiliary relay contact (NO) Max 700 W
SIGNAL
Gate open state (24 Vdc 3 W max)
COM A+
Common contacts / Positive 24 Vdc
J4
A+ COM
+ 24Vdc accessories power supply / Common contacts
A-
- 24Vdc accessories power supply
A+ TEST
+ 24Vdc photocells self-test power supply
J5
COM A+
Common contacts / Positive 24 Vdc
B.I.O.
Contact (NO) dedicated to a clock
PED.
Pedestrian opening contact (NO)
START
Single pulse contact (NO)
CLOSE
Closing impulse contact (NO)
OPEN
Opening impulse contact (NO)
J6
COM A+
Common contacts / Positive 24 Vdc
STOP
STOP impulse contact (NC)
PHOT 1
Photocells contact 1 (NC)
PHOT 2
Photocells contact 2 (NC)
EDGE 1
Edge 1 contact (NC)
EDGE 2
Edge 2 contact (NC)
J7
COM A+
Common contacts / Positive 24 Vdc
LIMIT SWITCH
Limit switches that cuts OFF the motor
J8
PROBE
IS NOT AVAILABLE
J9
ENCODER
IS NOT AVAILABLE
J10
RS485 termination of J11
J11
APP+
Connector for APP+ card
J12
APP
Connector for APP card
J13
SERIAL COM /
SYNC
Connector for serial connection
J14
-
-
J15
RADIO
Connector for radio module ACG8069
J16
RADIO
Connector for radio receiver RIB, 24 Vdc supply
J17
433 MHz Radio antenna
PROG.
Programming button
TCA
Trimmer for automatic closing time adjustment (DISABLED
DEFAULT AND DL11 LED OFF)
LOW SP
IS NOT AVAILABLE
TORQUE
IS NOT AVAILABLE
F1
T5A
Fuse for motor protection
T1 - T2 T
POWER RELAYS FOR THE COMMAND OF THE MOTOR
JA
R-N
SINGLE PHASE POWER SUPPLY - NEUTRAL
CONTACTS FOR THE EARTH CONECTION
U-V-W
MOTOR CONNECTION