background image

19

Once the failing safety device is repaired,  in automatic after 1 second, all standard 
commands that were selected, such as step by step, automatic mode, radio commands and 
automatic closing start functioning again.

Note 1:

  during this functioning in dead man mode, in case of damage to the safety strips 

(or photocells) the photocells (or safety strips) still work by interrupting the operation 
in progress.

The dead-man operation is only an emergency operation which must be activated for 
a very short period and with the complete installation at sight so to have a secure and 
safe control of the system. 
As soon as possible however, the failing safety devices must be repaired and 
activated.

BLINKER AND/OR FLASHING LIGHT (DIP5)
With DIP5 set ON =>

 

 it is possible to connect a flasher

 

N.B.:   This electric board can supply power ONLY TO 

BLINKERS WITH (ACG7059) BLINKING CIRCUIT, 
with max. 40W lamps.

With DIP5 set OFF =>

 

 it is possible to connect a lamp for garage lighting (40 W max).

On every command input, the courtesy lamp will lit for 2 minutes. If during the 2 minutes 
time, a second input is generated, the time elapsing will automatically restart for 2 minutes.

PRE-FLASHING FUNCTION
With DIP8 set OFF =>

 

 the FLASHING LIGHT and the motor will start at the same time.

With DIP8 set ON =>

 

 the FLASHING LIGHT starts working 3 seconds before every 
movement of the motor.

AUTOMATIC CLOSING (DIP 3 ON)

The pausing time before the automatic closing is set during the “Time Programming”.
In this case the maximum pausing time available is 5 minutes.
Pause time can be enabled or disabled by DIP3 (ON enabled).

RESTORING OF OPERATION FOLLOWING A POWER SHUT OFF

In case of power shut off the fence stops and the control unit will keep  memory of the 
interrupted motion. 
On restoring of power a further command is necessary. 
Upon command input the interrupted operation is completed (in case of opening, the open 
stroke is completed…).

TECHNICAL DATA

Temperature range 

0±55°C

Moisture 

 <95% without condensation

Power supply voltage  

 230V±10% (120V±10% on request)

Frequency 50/60Hz
Transient power mains drops 20ms
Max. power managed at the motor output  

1CV

Max. load at the blinker output 

40W with resistive load

Max. card power absorption (excluding the accessories)  
 

20mA

Current available for the photocells  

0,4A±15% 24Vdc

Protection degree 

IP54

Weight of the equipment  

0,70 kg

Dimensions  

14,7 x 6 x 18,5cm

TECHNICAL FEATURES OF THE RADIO (CRX MODELS ONLY)

Frequency for the reception  

433,92MHz

Impedance  

52ohm

Sensitivity  

>2,24µV

Energizing time  

300ms

De-energizing time 

300ms

Codes to be memorized 

N° 60

Current available on the radio connector  

200mA 12Vdc

-  All inputs shall be used as clean contacts without earthing, because the power supply is 

generated in the card and is structured in such a way to guarantee the respect of double 
and reinforced insulation to the elements under voltage

-   All inputs are managed by a programmed circuit that carries out a self-control every time 

the door is operated.

TROUBLESHOOTING

After having carried out all connections, by carefully following the layout and having 

positioned the gate in intermediate position, check the correct ignition of LEDS DL3, DL4.

In case of no ignition of the LEDS, always with gate in intermediate position, check the 

following and replace any faulty components.

DL3  switched off   Faulty safety edge (In case the edge is not connected, carry out jumper 

between COM and EDGE)

DL4  switched off  Faulty photocells

During functioning with personnel present, with DIP 1 at ON, check that during opening the 

green DL7 LED switches on and that during closing the red DL6 LED switches on.

If not, invert clamps V and W on the motor terminal board.

G

B

FAULT

SOLUTION

After having carried out the various connections and having supplied voltage, all the  LEDS 
are switched off.

Check the integrity of fuses F1 and F2. 
In case of interrupted fuse use only of adequate value     F2 = 5A    F1 = 100mA.

The motor opens and closes, but it has no strength and moves slowly.

Check trimmer TORQUE adjustment.

The shutter opens but does not close after the time set.

Ensure to have set DIP 3 at ON. 
Button K BUTTON always inserted in automatic functioning mode (DIP 6 OFF). 
Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board and edge feeder.

Attention:

 if not using a feeder for edges, DIP 10 must be at OFF position.

The shutter does not open or close by activating the various K and RADIO buttons.

Faulty safety edge contact. 
Faulty photocells contact with DIP 4 OFF.
Fix or replace the relative contact.

By activating the K button the shutter does not move.

Impulse K always inserted. 
Check and replace any buttons or micro-switches of the selector switch.

Содержание ABJ7079

Страница 1: ...rrent European Norms ATTENTION DO NOT CONNECT TIMERS If you want the Clock Function must request J with firmware 02 Make sure that any other type of command accessories e g mass detectors used on the installation are set in the IMPULSIVE mode otherwise the rolling shutter will be operated even without the protection of the safety devices Con AUTOTEST costas de seguridad como requerido por la norma...

Страница 2: ...ui ont des ouvertures de largeur supérieure à 50 mm de diamètre LA SOCIETE RIB N ACCEPTE AUCUNE RESPONSABILITE pour d éventuels dommages provoqués par la non observation dans l installation des normes de sécurité et des lois actuellement en vigueur ATTENZIONE PER LA SICUREZZA DELLE PERSONE È IMPORTANTE CHE VENGANO SEGUITE TUTTE LE ISTRUZIONI CONSERVARE CON CURA QUESTE ISTRUZIONI 1 Se non è previst...

Страница 3: ...ES CONSERVAR CUIDADOSAMENTE ESTAS INSTRUCCIONES 1 En el caso de que no sea previsto en la central eléctrica instalar antes de la misma un interruptor de tipo magnetotérmico omnipolar con una apertura mínima de los contactos de 3 mm que dé un sello de conformidad con las normas internacionales Este dispositivo tiene que estar protegido contro cierres accidentales por ejemplo instalándolo dentro de ...

Страница 4: ...RICI NC NO C S AD A A S AD A A 7 6 0 5 4 R POWER CLOSE LSC OPEN LSO COM JOLLY ONE JOLLY BIG JOLLY 20 JOLLY 22 JOLLY 22S JOLLY 24 JOLLY ONE FIN MEC JOLLY BIG FIN MEC S1 J3 TR1 J4 J5 J6 J1 J2 ON J cod AC07081 J CRX cod AC07080 ...

Страница 5: ... aprire con DL7 VERDE ACCESO invertire i fili del motore V e W nel quadro elettronico o i morsetti 5 e 6 sul gruppo finecorsa JOLLY 3 Regolate il finecorsa che ferma l apertura Verificare che a fine apertura il relativo finecorsa elettrico fermi il movimento del motore 4 Dopo 3 sec di lavoro in apertura o chiusura si innesca automaticamente la forza elettronica eseguite la regolazione della forza ...

Страница 6: ...Durante il funzionamento le fotocellule intervengono sia in apertura con ripristino del moto in apertura dopo un tempo di mezzo secondo che in chiusura con ripristino del moto inverso dopo un secondo DIP 4 ON A serranda chiusa se un ostacolo si interpone al raggio delle fotocellule e viene comandata l apertura la serranda apre durante l apertura le fotocellule non interverranno Le fotocellule inte...

Страница 7: ...me contatti puliti perché l alimentazione è generata internamente alla scheda ed è disposta in modo da garantire il rispetto di isolamento doppio o rinforzato rispetto alle parti in tensione Tutti gli ingressi vengono gestiti da un circuito integrato programmato che esegue un autocontrollo ad ogni avvio di marcia RISOLUZIONE PROBLEMI Dopo aver effettuato tutti i collegamenti seguendo attentamente ...

Страница 8: ...nderebbe nullo il funzionamento dell antenna L antenna va installata perpendicolarmente e deve essere in vista del telecomando LAMPEGGIATORE SPARK con scheda intermittente incorporata cod ACG7059 SUPPORTO LATERALE cod ACG7042 ANTENNA SPARK 433 cod ACG5452 PULSANTIERA DA PARETE FLAT APRE CHIUDE Comando per ogni tipo di automazione È dotata di due microswitches con contatti da 15A 250V Dim 59 5x82 5...

Страница 9: ...erie applicabile direttamente alla struttura mobile di porte sezionali e serrande avvolgibili Non è necessario quindi nessun collegamento filare alla centrale Portata segnale infrarosso selezionabile 5 m o 10 m Portata segnale radio 20 m IP54 Batterie non incluse cod ACG8048 Patent EP10706772 EP2345019 Gestisce 1 fotocellula NO TOUCH 868 12 30V ac dc cod ACG6154 2 X 3 6V cod ACG9517 ACCESSORI DI S...

Страница 10: ...QUES S1 J3 TR1 J4 J5 J6 J1 J2 ON J code AC07081 J CRX code AC07080 NC NO C S AD A A S AD A A 7 6 0 5 4 R POWER CLOSE LSC OPEN LSO COM JOLLY ONE JOLLY BIG JOLLY 20 JOLLY 22 JOLLY 22S JOLLY 24 JOLLY ONE FIN MEC JOLLY BIG FIN MEC ...

Страница 11: ...ON le voyant lumineux DL1 commencera à clignoter ATTENTION si on n appuie pas sur la touche PROG avant 1 minute le led s éteint mais en restant dans cette configuration voir paragraphe D COMMANDE A HOMME PRESENT 2 Appuyer sans relâcher sur la touche PROG dès à présent le mouvement est effectué en mode homme mort ouvre stop ferme stop ouvre etc la porte doit ouvrir DL7 vert allumé a Si elle se ferm...

Страница 12: ...il est actionné au cours du mouvement de fermeture de la porte il la rouvre FONCTION HORLOGE Pour utiliser la FUNCTION HORLOGE demander J avec firmware 02 ATTENTION UNE HORLOGE CONNECTÉ À J avec fw 03 ou plus ACTIVE LE MOUVEMENT AUTOMATIQUE DE L AUTOMATION SANS SÉCURITÉ ACTIVE Cette fonction est très utile pendant les heures de pointe lorsque la circulation des véhicules est ralentie par exemple e...

Страница 13: ...émorise le mouvement qu il était en train de faire Au retour du courant il reste en attente d une commande En donnant cette commande il exécute la manœuvre qu il était en train de faire au moment de l interruption s il était en train d ouvrir il continue à ouvrir CARACTÉRISTIQUES TECHNIQUES GÉNÉRALES Plages de température 0 55 C Humidité 95 sans condensation Tension d alimentation 230V 10 120V 10 ...

Страница 14: ...e le fil central du câble n entre pas en contact avec l enveloppe extérieure en cuivre dans le cas contraire le fonctionnement de l antenne serait nul L antenne doit être installée de façon perpendiculaire et être en vue de la télécommande FEU CLIGNOTANT SPARK avec carte intermittente incorporée code ACG7059 SUPPORT LATERAL code ACG7042 ANTENNE SPARK 433 code ACG5452 FIT SLIM EN12978 EN13849 2 PHO...

Страница 15: ...teries applicables directement à la structure des portes sectionelles et rideaux a enroulement Donc Il n y a pas besoin d aucune liaison avec des fils au coffret Portée signal infrarouges sélectionnable 5 m ou 10 m Portée signal radio 20 m IP54 Piles non incluses code ACG8048 Patent EP10706772 EP2345019 Il gère 1 PHOTOCELLULE NO TOUCH 868 12 30V ac dc code ACG6154 2 X 3 6V code ACG9517 ACCESSOIRES...

Страница 16: ...ONS S1 J3 TR1 J4 J5 J6 J1 J2 ON J code AC07081 J CRX code AC07080 NC NO C S AD A A S AD A A 7 6 0 5 4 R POWER CLOSE LSC OPEN LSO COM JOLLY ONE JOLLY BIG JOLLY 20 JOLLY 22 JOLLY 22S JOLLY 24 JOLLY ONE FIN MEC JOLLY BIG FIN MEC ...

Страница 17: ...ormed in manned position setting open stop close stop open etc the fence will open DL7 green lit a In case the fence closes instead of opening DL6 RED LIT release immediately the pushbutton PROG and set the close stroke end switch b In case the fence closes instead of opening DL7 GREEN LIT exchange the connection of motor wires V and W on the electrical unit or connection blocks 5 and 6 on the str...

Страница 18: ... the automation or to keep It open as long as the switch is on or the timer is activated When the automation is open all operating functions are inhibited On switch release or at set time the actuator will close RADIO TRANSMITTER If DIP6 is ON It cyclically commands open stop close stop open etc If DIP6 is OFF It opens the door when this is closed If it is operated while the door is opening it has...

Страница 19: ...he photocells 0 4A 15 24Vdc Protection degree IP54 Weight of the equipment 0 70 kg Dimensions 14 7 x 6 x 18 5cm TECHNICAL FEATURES OF THE RADIO CRX MODELS ONLY Frequency for the reception 433 92MHz Impedance 52ohm Sensitivity 2 24µV Energizing time 300ms De energizing time 300ms Codes to be memorized N 60 Current available on the radio connector 200mA 12Vdc All inputs shall be used as clean contac...

Страница 20: ... central wire of the cable to came Into contact with the external copper sheath since this would prevent the antenna from working Install the antenna vertically and in such a way the remote control can reach it SPARK BLINKER WITH IN BUILT INTERMITTENT CARD code ACG7059 LATERAL SUPPORT code ACG7042 SPARK ANTENNA 433 code ACG5452 FIT SLIM EN12978 EN13849 2 PHOTOCELLS for the wall installation code A...

Страница 21: ...rate with batteries fittable directly on the mobile part of sectional garage doors and rolling shutters For this reason It is not necessary any connection to the control board Infrared signal range 5 m to 10 m Radio signal range 20 m IP54 Batteries not included code ACG8048 Patent EP10706772 EP2345019 Manages 1 NO TOUCH 868 photocell 12 30V ac dc code ACG6154 2 X 3 6V code ACG9517 SAFETY ACCESSORI...

Страница 22: ...RICAS S1 J3 TR1 J4 J5 J6 J1 J2 ON J còd AC07081 J CRX còd AC07080 NC NO C S AD A A S AD A A 7 6 0 5 4 R POWER CLOSE LSC OPEN LSO COM JOLLY ONE JOLLY BIG JOLLY 20 JOLLY 22 JOLLY 22S JOLLY 24 JOLLY ONE FIN MEC JOLLY BIG FIN MEC ...

Страница 23: ... persona presente abre stop cierra stop abre etc la puerta debe abrir DL7 verde encendido a Se cierra en lugar de abrir con DL6 ROJO ENCENDIDO soltar inmediatamente el pulsador PROG y ajustar el final de carrera del cierre b Se cierra en lugar de abrir con DL7 VERDE ENCENDIDO invertir los cables del motor V y W en la central o los bornes 5 y 6 del grupo de final de carrera JOLLY 3 Ajustar el final...

Страница 24: ...eloj de tipo día semana en lugar o en paralelo con el pulsador de abertura n a COM K BUTTON es posible abrir y mantener abierto el mecanismo hasta que se apriete el pulsador o el reloj quede activado Estando el mecanismo abierto se inhiben todas las funciones de mando Dejando la botonera o al vencer el tiempo insertado se tendrá el cierre inmediato del mismo MANDO A DISTANCIA Si DIP6 está en ON Ej...

Страница 25: ...ción 230V 10 120V 10 bajo requesta Frecuencia 50 60Hz Microinterrupciones de red 20ms Potencia máxima disponible a la salida del motor 1CV Carga máxima a la salida del destellador 40W con carico resistivo Absorción máxima tarjeta sin accesorios 20mA Corriente disponible para las fotocélulas 0 4A 15 24Vdc Grado de protección IP54 Peso del equipo 0 70 kg Medidas 14 7 x 6 x 18 5 cm CARACTERÍSTICAS TÉ...

Страница 26: ...adioreceptor Importante Controlar con atención que el hilo central del cable no esté en contacto con la protección de cobre externa Esto impediría el funcionamiento de la antena Instale la antena verticalmente y de tal manera el telemando a distancia puede alcanzarla INTERMITENTE SPARK con tarjeta intermitente incorporada cód ACG7059 SOPORTE LATERAL cód ACG7042 ANTENA SPARK 433 cód ACG5452 FIT SLI...

Страница 27: ...tocelulas se pueden fijar directamente a la parte movil de las puertas seccionada o de las puertas enrollables No es por lo tanto necesario ninguna conexion de cables al cuadro de maniobra Alcance señal infrarroja seleccionable 5 m o 10 m Alcance señal radio 20 m IP54 Baterías no incluidas cód ACG8048 Patent EP10706772 EP2345019 Gestiona 1 fotocélula NO TOUCH 868 12 30V ac dc cód ACG6154 2 X 3 6V ...

Страница 28: ...uccessives Sa mise en service est interdite avant que l installation ait été déclarée conforme aux dispositions prévues par la Directive This product can not work alone and was designed to be fitted into a system made up of various other elements Hence it falls within Article 6 Paragraph 2 of the EC Directive 2006 42 Machines and following modifications to which respect we point out the ban on its...

Отзывы: