15
Func.
Name
Description
Range of
Setting
Unit Default
F_165
Feedback Signal
Selection
0: Direct proportion signal.
1: Inverse proportion signal.
0,1
─
0
F_166
(2
nd
PI Control)
Active Range
2nd PI control starts when the deviation value is
within the setting range(SV±F_166) (0.0: Disable)
0.0~25.0
0.1
0.0
F_167
(2
nd
PI Control)
Active Time
2
nd
control work with the time duration and then
switching back the primary PI control. (0.0: Disable)
0.0~300.0 0.1
0.0
F_168
Proportional
Gain(P2)
Set the gain for deviation adjustment.(0.0: disabled) 0.0~25.0
0.1
1.0
F_169 Integration Time(I2)
Set the integration time for deviation adjustment.
(0.0: disabled)
0.0~25.0
0.1
2.0
F_170
Display Setting by
Open-Loop
Command
Main display selection when the drive command by
PID and executing open-loop command.
0: PV display 1: According to the value of F_006
0,1
─
0
F_171
Setting Selection by
Open-Loop
Command
Primary speed selection when the drive command by
PID and executing open-loop command.
0~3
─
1
0: Analog input terminals
2: UP/DOWN command
1: Keypad
3: Communication
F_172
Keypad Selection by
Open-Loop
Command
Command can be adjusted by keypad when the drive
control by PID and executing open-loop command.
0: Primary speed 1: “SV” value
0,1
─
0
F_174
(On-Off)
Control Selection
0: Forward control
1: Reverse control
0,1
─
0
F_175
On-Off mode
0: Disable 1: Enable
0,1
─
0
F_176 (On) Range Setting
Drive starts when the “PV” exceeds the “On” range.
-12.8~
12.7
0.1
1.0
F_177 (Off) Range Setting
Drive stops when the “PV” exceeds the “Off” range. 0.0~10.0 0.1
1.0
F_178 (On) Delay Time
After the “PV” exceeds the “On” range and lasts a
duration(F_178), drive starts.
0~250
1sec
0
F_179 (Off) Delay Time
After the “PV” value exceeds the “Off” range and lasts
a duration(F_179), drive stops.
0~250
1sec
0
F_180
(On-Off)
Accel/Decel
Time Selection
0: Primary accel./decel. time
1: Secondary accel./decel. time
0,1
─
1
F_181 (Off) Holding Time
Hold the “Off” condition with the duration.
0~240
1sec
0
F_182
Air conditioning
mode
0: Disable
1: Enable
0,1
─
0
F_183
(Air Conditioning
Mode)
Temperature
Response Time
In the air conditioning mode,the frequency is varied
according to the setting value of temperature
response time.
PV > (SV+F186) , Variation of acceleration:
(Hz/sec) = (F_184/ F183)
PV > (SV+F187)
,
Variation of deceleration:
(Hz/sec) = (F_184/ F183)*4.
0.0~25.0 0.1sec
5.0
F_184
(Air Conditioning
Mode)
Variation Frequency
0.1~25.0 0.1Hz
2.0
F_185
(Air Conditioning
Mode)
Upper Limit Range
of Temperature
Upper limit value = “SV” value + F_185
Lower limit
value = “SV” value + F_186
When the temperature is over upper limit value, drive
outputs the setting value of F_042(Frequency Upper
Limit)
When the temperature is under lower limit value,
drive outputs the setting value of F_043(Frequency
Lower Limit)
F_184~
20.0
0.1
3.0
F_186
(Air Conditioning
Mode)
Lower Limit Range
of Temperature
0~F_184
0.1
1.0
F_187
(Air Conditioning
Mode)
Holding Frequency
Level
When the operation frequency of drive is under
(F_031*F_187) and maintaining F_188 duration,
drive runs at full speed by oper-loop condition and
maintaining a duration(F_189) and then recovering
PID control.
(F_188=0: Disable)
0.00~1.00 0.01
0.50
F_188
(Air Conditioning
Mode)
Time of Holding
Frequency
0.0~25.0 0.1hr
0.0
F_189
(Air Conditioning
Mode)
Full Speed Time
0.0~25.0
0.1
min
1.0
F_190
Feedback Limit
Detection
0: Disable
1: Warning detection
;
Continue operation
2: Warning detection
;
Stop output
3: Error detection
;
Error trip
0~3
─
0