12
Func.
Name
Description
Range of
Setting
Unit Default
F_089
Delay Time before
Speed Tracing
Set the delay time before the speed tracing and
coast stop+ DC braking.
0.1~5.0 0.1sec
0.5
F_090
The V/F Pattern of
Speed Tracing
Set the percentage of V/F output voltage at the speed
tracing.
0~100%
1%
100
F_091
Error Record
Display the latest 5 error records.
─
─
─
F_092
Parameter Setting
Lock
0: Parameters are changeable. Maximum frequency
cannot exceed 120.0Hz.
1: Parameters are locked. Maximum frequency
cannot exceed 120.0Hz.
2: Parameters are changeable. Maximum frequency
can exceed 120.0Hz.
3: Parameters are locked. Maximum frequency can
exceed 120.0Hz.
0~3
─
0
F_093
Automatic Voltage
Regulation (AVR)
0: Disable
1: Enable
0,1
─
1
F_094
Drive Overload
(OL1)
0: Disable
1: Thermal protection
2: Current limit overload protection
3: Both 1 and 2 enable
0~3
─
3
F_095
Power Source
Set the value according to the actual power source.
190.0~
240.0
0.1V
220.0
(Note3)
340.0~
480.0
380.0
(Note4)
F_096 Holding Frequency
The drive accelerates to the holding frequency and
running at constant speed.
0.0~400.0 0.1Hz
0.5
F_097
Holding Time
Interval
The drive runs at holding frequency by constant
speed and running the time interval.
0.0~25.5 0.1sec
0.0
F_098
Grounding Fault
Protection (GF)
0: Disable
1: Enable(GF)
0, 1
─
1
F_099 External Indicator 1
Select the monitor mode of external indicator 1
0: Disable
0~10
─
1
F_100 External Indicator 2
Select the monitor mode of external indicator 2
0: Disable
0~10
─
5
F_101 External Indicator 3
Select the monitor mode of external indicator 3
0: Disable
0~10
─
2
F_102
V/F Pattern
Selection
0:Linear.
1: Energy-saving mode (auto-adjust V/F pattern
according to the load condition).
2: Square curve.
3: 1.7
th
power curve.
4: 1.5
th
power curve.
0~4
─
0
F_103
Subtracted
Frequency of
Ramp to Stop by
Power Failure
When the power failure, drive will substract the
setting value from the current frequency before ramp
to stop.
(F_078=2 or 3)
0.0~20.0 0.1Hz
3.0
F_104
Deceleration Time 1
of Ramp to Stop by
Power Failure
When the power failure, the deceleration time before
the output frequency decelerates to the turning
frequency set in F_106.
0.0~
3200.0
0.1sec
15.0
(Note5)
F_105
Deceleration Time 2
of Ramp to Stop by
Power Failure
When the power failure, the deceleration time after
the output frequency decelerares to the turning
frequency set in F_106.
0.0~
3200.0
0.1sec
15.0
(Note5)
F_106
Turning Frequency
of Ramp to Stop by
Power Failure
Set the turning frequency level of ramp to stop when
the deceleration time is switched from F_104 setting
value to F_105 setting value.
0.0~400.0 0.1Hz
0.0
F_107
Analog Frequency
Dead Band
When the noise of analog input signal is large,
appropriately increase the dead band to stabilize the
frequency command. But adjusting this function will
reduce the tuning linearity of input signal.
0.00~2.55
0.01
Hz
0.00
F_108
Digital Input
Response Time
When the pulse width of digital signal is lower than
setting time, the signal disabled.
5~16
1ms
10
F_109
Communication
Interface Selection
0: RJ-45
1: DX+ / DX-
0,1
─
1
F_110
Communication
Address
The followers use the address to send and receive
messages. (0: disable)
0~254
─
0
F_111
Communication
Baud Rate
0: 4800bps 1: 9600bps
2: 19200bps 3: 38400bps
0~3
─
1