10
Func.
Name
Description
Range of
Setting
Unit Default
F_050
Motor Slip
Compensation
According to the load condition, set the compensation
for motor running at constant speed. (0.0: off)
-9.9~10.0 0.1Hz
0.0
F_051
Number of Motor
Poles
Determinate the RPM display value of monitor mode.
2~10
2P
4P
F_052
Multi-function
Input Terminal
(X1)
=0:
UP/DOWN frequency
command enter key
±1: Jog command
±2: Secondary accel/decel
time command
±3: Multi-speed level 1
command
±4: Multi-speed level 2
command
±5: Multi-speed level 3
command
±6: Reset command
±7: External fault
command(thr)
±8: Interruption of output
command(bb)
±9: Coast to stop
command(Fr)
±10: Speed tracing from the
maximum frequency
±11: Speed tracing from the
setting frequency
±12: Holding command
±13: UP command
±14: DOWN command
±15: Clear UP/DOWN
frequency command
±16: Analog input source
selection
±17: Stop command with
3-wire start/stop circuit
±18: Under close-loop
control condition
(F_153≠0), open-loop
selection.
±19: Reset the integrator at
close-loop control
condition (F_153≠0)
±20: Stop command
±21: Multi-speed level 4
command
-21~ +21
(Note 7)
─
3
F_053
Multi-function
Input Terminal
(X2)
=0:
DC braking enable
(at stop)
4
F_054
Multi-function
Input Terminal
(X3)
=0:
Current limit enable
1
F_055
Multi-function
Input Terminal
(X4)
=0:
Selection of primary or
secondary frequency
command
(ON: secondary
frequency command)
2
F_056
Multi-function
Input Terminal
(X5)
=0:
Stop command with
3-wire start/stop circuit
(N.O; contact a)
7
F_057
Multi-function
Input Terminal
(X6)
=0:
Stop command with
3-wire start/stop circuit
(N.C; contact b)
6
F_058
Multi-function
Output Terminal
(Y1)
0: Disable
±1: Operation command detection
±2: Constant speed detection
±3: Zero speed detection
±4: Frequency detection
±5: Overload detection(OLO)
±6: Stall prevention detection
±7: Low voltage detection(LE)
±8: Braking detection
±9: Restart after instantaneous power failure
detection
±10: Restart after error condition detection
±11: Error detection
±12: Overheating detection
±13: Upper limit of feedback detection
±14: On-Off dead band detection
±15: On-Off range detection
±16: Fan detection during operation
-16 ~+16
(Note 7)
─
3
F_059
Multi-function
Output Terminal
(Y2)
2
F_060
Multi-function
Output Terminal
(Ta1,Tb1)
11
F_061
Constant Speed
Detection Range Set the bandwidth of constant speed detection range. 0.0~10.0 0.1Hz
2.0
F_062
Frequency
Detection Range Set the bandwidth of frequency detection range.
0.0~10.0 0.1Hz
2.0
F_063
Frequency
Detection Level
Set the frequency detection level of multi-function
output terminal.
0.0~400.0 0.1Hz
0.0
F_064
Automatic Torque
Compensation
Range
According to the load condition, adjust the output
voltage of the V/F pattern. (0.0: off)
0.0~25.5
0.1
1.0