Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
•
Largest motor load is included in single circuit and multiple circuit 1.
•
If non-standard fuse size is specified, use next size larger fuse size.
•
J Voltage (230V) signal phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting
3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block. Cap, insulate and fully secure the
third lead.
•
?Heater Kit Connection Type A=Breaker B=Terminal Block C=Pullout Disconnect
RXBH-1724?05J
Single
208/240
1/60
3.6/4.8
17.3/20.0
1.7
25/30
24/28
2421HT
RXBH-1724?07J
Single
208/240
1/60
5.4/7.2
26.0/30.0
1.7
35/40
35/40
RXBH-1724?10J
Single
208/240
1/60
7.2/9.6
34.6/40.0
1.7
50/60
46/53
RXBH-1724?05J
Single
208/240
1/60
3.6/4.8
17.3/20.0
4.9
30/35
28/32
RXBH-1724?07J
Single
208/240
1/60
5.4/7.2
26.0/30.0
4.9
40/45
39/44
RXBH-1724?10J
Single
208/240
1/60
7.2/9.6
34.6/40.0
4.9
50/60
50/57
Single
208/240
1/60
10.8/14.4
51.9/60.0
4.9
80/90
72/82
3624HT
RXBH-1724A15J
MULTI. CKT 1
208/240
1/60
3.6/4.8
17.3/20.0
4.9
30/35
28/32
MULTI. CKT 2
208/240
1/60
7.2/9.6
34.6/40.0
0
45/50
44/50
Single
208/240
1/60
12.8/17
61.6/70.8
4.9
90/100
84/95
RXBH-1724A18J
MULTI. CKT 1
208/240
1/60
6.4/8.5
30.8/35.4
4.9
45/60
45/51
MULTI. CKT 2
208/240
1/60
6.4/8.5
30.8/35.4
0
40/45
39/45
RXBH-1724?05J
Single
208/240
1/60
3.6/4.8
17.3/20.0
4.9
30/35
28/32
RXBH-1724?07J
Single
208/240
1/60
5.4/7.2
26.0/30.0
4.9
40/45
39/44
RXBH-1724?10J
Single
208/240
1/60
7.2/9.6
34.6/40.0
4.9
50/60
50/57
Single
208/240
1/60
10.8/14.4
51.9/60.0
4.9
80/90
72/82
RXBH-1724A15J
MULTI. CKT 1
208/240
1/60
3.6/4.8
17.3/20.0
4.9
30/35
28/32
MULTI. CKT 2
208/240
1/60
7.2/9.6
34.6/40.0
0
45/50
44/50
Single
208/240
1/60
12.8/17
61.6/70.8
4.9
90/100
84/95
4824HT
RXBH-1724A18J
MULTI. CKT 1
208/240
1/60
6.4/8.5
30.8/35.4
4.9
45/60
45/51
MULTI. CKT 2
208/240
1/60
6.4/8.5
30.8/35.4
0
40/45
39/45
Single
208/240
1/60
14.4/19.2
69.2/80.0
4.9
100/110
93/107
RXBH-24A20J
MULTI. CKT 1
208/240
1/60
7.2/9.6
34.6/40.0
4.9
50/60
50/57
MULTI. CKT 2
208/240
1/60
7.2/9.6
34.6/40.0
0
45/50
44/50
Single
208/240
1/60
18.0/24.0
87.0/99.9
4.9
125/150
115/132
RXBH-24A25J
MULTI. CKT 1
208/240
1/60
6.0/8.0
29.0/33.3
4.9
45/50
43/48
(4-ton only)
MULTI. CKT 2
208/240
1/60
6.0/8.0
29.0/33.3
0
40/45
37/42
MULTI. CKT 3
208/240
1/60
6.0/8.0
29.0/33.3
0
40/45
37/42
RXBH-1724?07J
Single
208/240
1/60
5.4/7.3
26.0/30.0
4.9
40/45
39/44
RXBH-1724?10J
Single
208/240
1/60
5.4/7.2
26.0/30.0
4.9
40/45
39/44
Single
208/240
1/60
10.8/14.4
51.9/60.0
4.9
80/90
72/82
RXBH-1724A15J
MULTI. CKT 1
208/240
1/60
3.6/4.8
17.3/20.0
4.9
30/35
28/32
MULTI. CKT 2
208/240
1/60
7.2/9.6
34.6/40.0
0
45/50
44/50
Single
208/240
1/60
12.8/17
61.6/70.8
4.9
90/100
84/95
RXBH-1724A18J
MULTI. CKT 1
208/240
1/60
6.4/8.5
30.8/35.4
4.9
45/60
45/51
MULTI. CKT 2
208/240
1/60
6.4/8.5
30.8/35.4
0
40/45
39/45
Single
208/240
1/60
14.4/19.2
69.2/80.0
4.9
100/110
93/107
6024HT
RXBH-24A20J
MULTI. CKT 1
208/240
1/60
7.2/9.6
34.6/40.0
4.9
50/60
50/57
MULTI. CKT 2
208/240
1/60
7.2/9.6
34.6/40.0
0
45/50
44/50
Single
208/240
1/60
18.0/24.0
87.0/99.9
4.9
125/150
115/132
MULTI. CKT 1
208/240
1/60
6.0/8.0
29.0/33.3
4.9
45/50
43/48
RXBH-24A25J
MULTI. CKT 2
208/240
1/60
6.0/8.0
29.0/33.3
0
40/45
37/42
MULTI. CKT 3
208/240
1/60
6.0/8.0
29.0/33.3
0
40/45
37/42
RXBH-24A30J
Single
208/240
1/60
21.6/28.8 103.8/120.0
4.9
136/156
150/175
MULTI. CKT 1
208/240
1/60
7.2/9.6
34.6/40.0
4.9
49/56
50/60
RXBH-24A30J
MULTI. CKT 2
208/240
1/60
2-4.8
34.6/40.0
0
44/50
45/50
MULTI. CKT 3
208/240
1/60
7.2/9.6
34.6/40.0
0
44/50
45/50
Model Size
(-)H2V
Manufacturer
Model Number
Type Supply
Circuit
Voltage
PH/HZ
Heater
kW
Heater
AMPS
Motor
Ampacity
Maximum
Circuit
Protection
Minimum
Circuit
Ampacity
4.10 ELECTRIC HEAT ELECTRICAL DATA (-)H2V
Installation of the UL Listed original equipment manufacturer provided heater kits listed in the table below is
recommended for all auxiliary heating requirements.