General Information
Table A: Basic Data
Table B: Manifold Data
*Hidden solenoid valve located inside of air plenum.
7
Model
No.
Quantity of
Vent Size (in.)
Burners
Gas
Valves Blowers Flue
Intake
992C
11
2 + 1*
2
10
10
1262C
14
3 + 1*
2
12
10
1532C
17
4
2
12
10
1802C
20
4
2
14
10
2002C
23
5
3
14
10
2072C
23
5
3
14
10
2342C
26
5
3
16
10
Model
No.
Burners per Valve
Stages
% Fire at Stages
1 1A 2
3
4
1
2
3
4
1
2
3
4
992C
6
3
2
1
1, 2
1, 2, 3
54 82 100
1262C 5
3
3
3
1
1, 2
1, 2, 3
1, 2, 3, 4
36 57 79 100
1532C 6
4
4
3
1
1, 2
1, 2, 3
1, 2, 3, 4
35 59 82 100
1802C 6
4
5
5
1
1, 2
1, 2, 3
1, 2, 3, 4
30 50 75 100
2002C 4
5
5
5
4
1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 39 61 83 100
2072C 4
5
5
5
4
1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 39 61 83 100
2342C 5
6
5
5
5
1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 42 62 81 100