53
NOTE:
The wiring diagrams in this manual show all
standard options. Refer to the large wiring diagram
provided with your heater for options installed on
your specific unit(s).
the system. The OUT START is typically set to the desired building temperature.
Outdoor Design (
OUT DESIGN
)
The OUT DESIGN is the outdoor air temperature that is the typical coldest annual temperature where the building is located. This
temperature is used when completing heat loss calculations for the building.
Boiler Design (
Boil DESIGN
)
The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as the
OUT DESIGN temperature.
Warm Weather Shut Down (
WWSD
)
When the outdoor air temperature rises above the WWSD setting, the
control turns on the WWSD segment in the display. When the control is in
Warm Weather Shut Down, the Dem 1 segment is displayed if there is a
heat demand. However, the control does not operate the boiler to satisfy
this demand. The control continues to respond to DHW demands.
Decreasing Outdoor Temperature
In
cr
ea
sin
g
W
at
er
T
em
pe
ra
tu
re
Boil
START
OUT
DESIGN
Boil DESIGN
START
OUT
Reset Ratio
The controller uses the following four settings to cal-
culate the Reset Ratio (RR):
For example, when using the default values, the RR
is:
RR = (70 - 10) / (180 - 70) = 0.55
Therefore, the RR is 0.55:1 (Outdoor:Water).
RESET RATIO =
(OUTDOOR START – OUTDOOR DESIGN)
(BOILER DESIGN – BOILER START)
Fig. 48: Reset Ratio
Содержание Raypak Hi Delta 1262C
Страница 54: ...54 Wiring Diagram Models 992C 1262C...
Страница 55: ...55 Wiring Diagram Models 1532C 2342C...
Страница 69: ...69...
Страница 70: ...70...
Страница 71: ...71...
Страница 72: ...72 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...