LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
The maximum gas supply pressure to
the furnace should be 10.5
Supply Gas Pressure Measurement.
A line pressure tap is on the inlet side
of the gas valve.
1. With gas shut off to the furnace at
the manual gas valve outside the
unit, remove the input pressure tap
plug.
2. Connect a U-Tube manometer to
the pressure tap. See Figure 13.
operate the furnace and all other
gas-fired units on the same gas
line as the furnace.
4. Adjust the line gas pressure to
A. 5” - 10.5” w.c. for natural gas.
5. Shut off the gas at the manual gas
valve and remove the
U-Tube manometer.
6. Replace the pressure tap plug
TYPICAL HOSE CONNECTION TO LINE PRESSURE TAP
Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)