CONNECTION MUST BE MADE AT THE
FURNACE VENT EXIT.
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the
2. A type B-1 gas vent shall terminate
at least 5 feet in vertical height
above the highest connected
equipment draft hood or flue collar.
MANUFACTURER’s position now that
new installations of any HTPV pipe
used in a category
product, should cease immediately.
These shall be assembled in
accordance with the manufacturer’s
instructions. See Figure 9.
5. Any angle greater than 45 degrees
Содержание GLH series
Страница 23: ...23 FIGURE 18 UTEC 1028 928 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION a099301...
Страница 27: ...27 BLOWER PERFORMANCE DATA GPH UPFLOW HORIZONTAL MODELS BLOWER PERFORMANCE DATA GLH DOWNFLOW MODELS...
Страница 28: ...28 BLOWER PERFORMANCE DATA GLJ DOWNFLOW MODELS ONLY BLOWER PERFORMANCE DATA GPJ UPFLOW HORIZONTAL MODELS...
Страница 33: ...33 FIGURE 29 TROUBLESHOOTING FLOWCHART continued on next page PREPURGE...
Страница 34: ...34 FIGURE 29 TROUBLESHOOTING FLOWCHART CONTINUED 92 22744 19 01...