background image

Combustion air must be free of acid
forming chemicals; such as sulphur,
fluorine and chlorine. These elements
are found in aerosol sprays,
detergents, bleaches, cleaning
solvents, air fresheners, paint and
varnish removers, refrigerants and
many other commercial and household
products. Vapors from these products
when burned in a gas flame form acid
compounds. The acid compounds
increase the dew point temperature of
the flue products and are highly
corrosive after they condense.

ALL FURNACE INSTALLATIONS
MUST COMPLY WITH THE
NATIONAL FUEL GAS CODE AND
LOCAL CODES TO PROVIDE
ADEQUATE COMBUSTION AND
VENTILATION AIR FOR THE
FURNACE. FAILURE TO DO SO CAN
CREATE HAZARDOUS CONDITIONS
RESULTING IN PROPERTY
DAMAGE, BODILY INJURY OR
DEATH FROM SMOKE, FIRE OR
CARBON MONOXIDE.

Combustion air requirements are
determined by whether the furnace is
in an open (unconfined) area or in a
confined space such as a closet or
small room.

EXAMPLE 1.
FURNACE LOCATED IN AN
UNCONFINED SPACE

Using indoor air for combustion.

An unconfined space must have at
least 50 cubic feet for each 1,000 Btuh
of the total input for all appliances in
the space. Here are a few examples of
the room sizes required for different
inputs. The sizes are based on 8 foot
ceilings.

Btuh

Minimum Sq. Feet

Typical Room Size

Input

With 8' Ceiling

With 8' Ceiling

45,000

281

12

*

x24

*

or 16

*

x18

*

50,000

312

14

*

x24

*

or 18

*

x18

*

67,500

421

15

*

x28

*

or 20

*

x21

*

75,000

469

15

*

x31

*

or 20

*

x24

*

100,000

625

20

*

x31

*

or 25

*

x25

*

125,000

833

23

*

x34

*

or 26

*

x30

*

150,000

938

25

*

x38

*

or 30

*

x31

*

If the open space containing the
furnace is in a building with tight
construction (contemporary
construction), outside air may still be
required for the furnace to operate and
vent properly. Outside air openings
should be sized the same as for a
confined space.

10

WARNING

!

FIGURE 7
AIR FROM ATTIC/CRAWL SPACE

EXAMPLE 2.

FURNACE LOCATED IN A
CONFINED SPACE

A confined space (any space smaller
than shown above as “unconfined”)
must have openings into the space
which are located in accordance with
the requirements set forth in the
following subsections A and B. Size the
openings by how they are connected to
the heated area or to the outside, and
by the input of all appliances in the
space.

If confined space is within a building
with tight construction, combustion air
must be taken from outdoors or area
freely communicating with the
outdoors.

A. USING INDOOR AIR FOR

COMBUSTION

IMPORTANT:

Air should not be taken

from a heated space with a fireplace,
exhaust fan or other device that may
produce a negative pressure.

If combustion air is taken from the
heated area, the openings must
each have at least 100 square
inches of free area. Each opening
must have at least one square inch
of free area for each 1,000 Btuh of
total input in the space. Here are
some examples of typical openings
required.

Btuh

Free Area

Input

Each Opening

45,000

100 Square Inches

100,000

100 Square Inches

150,000

150 Square Inches

B. USING OUTDOOR AIR FOR

COMBUSTION

IMPORTANT: NEVER TAKE
COMBUSTION AIR FROM AN
ATTIC SPACE THAT IS
EQUIPPED WITH POWER
VENTILATION.

The confined space must
communicate with the outdoors
according to Methods 1 and 2. The
minimum air opening dimension
shall not be less than 3 inches.
When using ducts, they shall be of
the same cross-sectional area as
the free area of the openings to
which they connect.

Method 1

Provide two permanent openings,
one located within 12 inches of the
top and one located within 12 inches
of the bottom of the enclosure. Each
opening shall communicate directly,
or by ducts, with the outdoors or
spaces (crawl or attic) that freely
communicate with the outdoors.

a. Where directly communicating

with the outdoors or where
communicating to the outdoors
through 

VERTICAL DUCTS,

each

opening shall have a minimum
free area of 

1 square inch for

each 4000 BTUH

of total

appliance input rating in the
enclosure. Here are typical duct
sizes.

Содержание 1x2000

Страница 1: ...e WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Do not return to your home until authorized by the gas supplier or fire department DO NOT RELY ON SMEL...

Страница 2: ...und to electrical panel DC microamp µA flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected to terminals Y C not with wire nuts VENTING Correct vent pipe diameter and length according to AGA GAMA tables Vent connection size Correct venting material according to AGA GAMA tables Correct lining for mason...

Страница 3: ...ecautions 1 Installation Check List 2 Location Requirements and Considerations 4 Combustion and Ventilation Air 10 Vent Pipe Installation 13 Gas Supply and Piping 16 Electrical Wiring 19 Accessories 20 Air Flow 26 Maintenance 29 Troubleshooting 31 Wiring Diagram 33 Installation Instructions are updated on a regular basis This is done as product changes occur or if new information becomes available...

Страница 4: ...oring or by using support brackets See Figure 1 8 IMPORTANT If installing in a utility room be sure the door is wide enough to a allow the largest part of the furnace to pass or b allow any other appliance such as a water heater to pass CLEARANCE ACCESSIBILITY The design of forced air furnaces with input ratings as listed in the tables on the following pages are certified by A G A Laboratories and...

Страница 5: ...150 lbs CLEARANCE TO COMBUSTIBLE MATERIAL INCHES UPFLOW AND UPFLOW HORIZONTAL MODELS TOP LEFT SIDE FRONT RIGHT SIDE BOTTOM 241 2 2613 16 265 8 2411 32 2411 32 19 32 9 16 247 16 281 16 265 8 143 8 111 2 34 13 8 DIA 23 15 20 D 7 8 DIA 7 8 DIA 19 32 19 32 3 4 143 8 111 2 11 4 2317 32 C GAS CONNECTION ELECTRICAL CONNECTION OPTIONAL RETURN AIR CUTOUT EITHER SIDE FOR USE WITH EXTERNAL SIDE FILTER FRAME ...

Страница 6: ...8 0 0 0 1 6 6 120 lbs 12 241 2 2311 32 155 8 23 5 8 0 0 0 1 3 6 140 lbs 15 241 2 2311 32 155 8 23 5 8 0 0 0 1 3 6 150 lbs TOP BOTTOM 241 2 193 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E S A R A 265 8 2613 16 63 16 203 8 233 8 5 8 5 8 3 4 5 8 34 233 8 203 8 63 16 247 16 265 8 201 8 281 16 7 8 DIA 1 2 DIA 13 8 DIA May require 3 to 4 or 3 or 5 adapter May be 0 with type B vent May be ...

Страница 7: ...e furnace If this device is manually operated it must have a means to prevent operation of the other unit unless the damper is in the full heat or cool position IMPORTANT One of the most common causes of forced air heating problems is insufficient return air to the furnace The return system area should be approximately equal to or greater than the area of the warm air discharge CONSULT LOCAL CODES...

Страница 8: ...in the side or back The opening should be cut the full width of the knockouts on the unit NOTE Where the maximum air flow is 1800 CFM or more both sides or the bottom must be used for return air 3 Connect the return duct or return air cabinet to the unit Make the connection air tight to prevent entraining combustion gases from an adjacent fuel burning appliance 4 Be sure to have adequate space for...

Страница 9: ... and 2 or applicable provisions for the local building codes and not obstructed so as to prevent the flow of air to the furnace IMPORTANT Air for combustion and ventilation must not come from a corrosive atmosphere Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage The following types of installation may require OUTDOOR AIR for combustion due to chemical exp...

Страница 10: ...ACE LOCATED IN A CONFINED SPACE A confined space any space smaller than shown above as unconfined must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and B Size the openings by how they are connected to the heated area or to the outside and by the input of all appliances in the space If confined space is within a building...

Страница 11: ...R USING A HORIZONTAL INLET OUTLET Method 2 One permanent opening located within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance The opening shall directly communicate with the outdoors or communicate through a vertical or horizontal duct to the outdoors or spaces craw...

Страница 12: ...ITHER RIGID OR SUITABLE FLEXIBLE CONSTRUCTION THAT CARRIES A U L LISTING COMMON VENTING IS ALLOWED WITH VERTICAL B 1 VENT SYSTEMS AND LINED MASONRY CHIMNEYS FOLLOW THE NATIONAL FUEL GAS CODE ANSI Z223 1 AND OR THE NATURAL GAS INSTALLATION CODE CAN CGA B149 1 2 FOR PROPER INSTALLATION PRACTICES IMPORTANT WHEN COMMON VENTING USE B 1 VENT CONNECTORS SINGLE WALL VENT CONNECTORS TO B 1 VENT OR MASONRY ...

Страница 13: ... 8 feet from a vertical wall or similar obstruction Terminate all other gas vents not less than 2 feet above the highest point where they pass through the roof and at least 2 feet higher than any portion of a building within 10 feet 2 Terminate a type B gas vent at least 5 feet in vertical height above the highest connected equipment draft hood or flue collar DO NOT CONNECT THIS FURNACE TO A CHIMN...

Страница 14: ...ppliances the venting is likely to be too large to properly vent the remaining attached appliances The following steps shall be followed with each appliance that remains connected to the common venting system while the other appliances that remain connected to the common venting systems are not in operation NOTE WHEN THE VENT TABLE PERMITS MORE THAN ONE DIAMETER OF PIPE FOR A CONNECTOR OR VENT THE...

Страница 15: ...ne and manual gas valve must be adequate in size to prevent undue pressure drop and never smaller than the pipe size to the com bination gas valve on the furnace Refer to Table 2 for the recom mended pipe size for natural gas and Table 3 for LP gas pipe sizes WARNING HORIZONTAL IMPORTANT It is permissible to run flexible gas connector inside the unit to a piece of black pipe Install a ground joint...

Страница 16: ...0 Equivalent length of pipe 60 ft 3 4 IPS required SETTING GAS PRESSURE The maximum gas supply pressure to the furnace should be 10 5 w c natural gas or 13 w c LP gas The minimum supply gas pressure to the gas valve should be 5 w c natural gas or 11 w c LP gas A properly calibrated U Tube manometer is required for accurate gas pressure measurements Supply Gas Pressure Measurement A line pressure t...

Страница 17: ...g 5 Turn the gas supply back on and check for proper operation and manifold pressure 6 Attach the notice label alerting the next service technician that the furnace has been converted to LP gas 17 RATING PLATE ELEVATION INPUT BTU HR 0 TO 7 999 FT 8 000 FT AND ABOVE NATURAL GAS HEATING VALUE 1 000 BTU FT3 SPECIFIC GRAVITY 0 62 MANIFOLD PRESSURE 3 5 W C 50 000 42 43 75 000 42 43 100 000 42 43 125 00...

Страница 18: ...ale Ontario Canada M92 1R3 WARNING WARNING ELECTRICAL WIRING ELECTRONIC NIGHT SETBACK THERMOSTATS ARE COMPATIBLE WITH THE FURNACE CONTROL SYSTEM SOME MAY REQUIRE AN ISOLATION RELAY If an isolation relay is needed install it as close to the control board as possible Use a single pole single throw relay with a 24 volt operating coil The relay contacts should be designed for 24 volt loads Connect one...

Страница 19: ...e second control respectively d Both control boards must have Twin switch 3 in ON position e Adjust the heat anticipator current to 0 15 amps NOTE Leave Switch 4 in the OFF position It does not affect the twinning operation HIGH ALTITUDE KIT Models with inputs over 50 000 btu hr installed at altitudes of 5 000 feet and above require a low fire pressure switch change These may be ordered under Opti...

Страница 20: ...20 FIGURE 16 UTEC NO 1095 100 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION I685 ...

Страница 21: ...21 FIGURE 17 UTEC NO 1095 100 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I684 ...

Страница 22: ...will run for 60 seconds on low stop momentarily and then restart b The ignition process goes through one more try on low fire If this fails there are two tries on high fire with a 30 second interpurge between trials During high fire ignition attempts the inducer steps to high speed the high pressure switch closes both pressure switch closes both pressure switches are now closed and the gas valve s...

Страница 23: ...if the required HEAT and COOL speeds are the same IMPORTANT Do not connect any leads to the HEAT or COOL terminals if the HEAT COOL terminal is used 5 M1 Connect unused motor lead 6 M2 Connect unused motor lead The unit comes from the factory set to stop the blower 120 seconds after the thermostat is satisfied in heating and 45 seconds after the thermostat is satisfied in cooling This timing can b...

Страница 24: ...egulators Set the furnace manifold pressure at 10 W C at the gas control valve For elevations up to 8 000 feet rating plate input ratings apply For high altitudes elevations 8 000 and over the orifice spud must be changed To change orifice spuds 1 Shut off the manual main gas valve and remove the gas supply piping from the gas valve RATING PLATE ELEVATION INPUT BTU HR 0 TO 7 999 FT 8 000 FT AND AB...

Страница 25: ...he thermometer in the supply air duct stops rising approximately five minutes subtract the return air temperature from the supply air temperature The difference is the temperature rise 5 Compare the measured temperature rise to the approved temperature rise range listed on the furnace name plate See Figure 21 If the measured temperature rise is above the approved range the air flow is too low More...

Страница 26: ...5 1515 1480 1440 150 000 11 x 10 3 4 MED HI 2010 1985 1960 1915 1850 1800 1730 HI 2340 2275 2215 2145 2080 2010 1940 MODEL BTU 1 2 3 4 5 6 7 BLOWER SIZE MOTOR H P BLOWER SPEED CFM AIR DELIVERY EXTERNAL STATIC PRESSURE INCHES WATER COLUMN LOW 735 715 690 660 635 605 575 MED LO 1025 1015 995 975 955 930 905 50 000 11 x 6 1 2 MED HI 1185 1165 1150 1130 1100 1075 1040 HI 1345 1330 1310 1295 1265 1235 ...

Страница 27: ...cause of inadequate combustion air DO NOT reset the flame roll out switch without taking corrective action to assure that an adequate supply of combustion air is maintained under all conditions of operation Replace this switch only with the identical replacement part PRESSURE SWITCHES This furnace has two pressure switches for sensing a blocked vent condition One is for high pressure and the other...

Страница 28: ...nt of filter and frame to get proper width for a side filter TABLE 5 FILTER SIZES 28 MAINTENANCE WARNING FIGURE 23 RESIZING FILTERS FRAME NOTE Some filters must be resized to fit certain units and applications SOLID BOTTOM MAY BE ORDERED AS AN OPTION FROM THE FACTORY UPFLOW FILTER SIZES FURNACE INPUT BOTTOM SIDE QUANTITY WIDTH BTUH SIZE SIZE 14 50 121 4 X 25 153 4 X 25 1 171 2 75 100 153 4 X 25 15...

Страница 29: ...29 FIGURE 25 FILTER RETAINING RODS SIDE RETURN FIGURE 26 DOWNFLOW FILTER INSTALLATION ...

Страница 30: ...and set the thermostat lever to the lowest temperature 2 Shut off the gas supply to the furnace either at the meter or at a manual valve in the supply piping 3 Remove burner door On downflow models the blower door and burner door flange must also be removed 4 Disconnect gas supply piping from gas valve 5 Remove screws 4 connecting the burner tray to the center panel 6 Disconnect wiring to the gas ...

Страница 31: ... FIGURE 27 INTEGRATED FURNACE CONTROL IFC TROUBLESHOOTING GUIDE FOR UTEC 1095 101 31 ...

Страница 32: ...32 ...

Страница 33: ... FIGURE 28 UTEC 1095 101 INTEGRATED FURNACE CONTROL 33 ...

Страница 34: ...34 ...

Страница 35: ...35 ...

Страница 36: ...36 CM 599 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas ...

Отзывы: