Form I-UDA, P/N 195673 Rev 13, Page 38
APPENDIX
TECHNICAL DATA - Sizes 150 - 400
(Data applies to both Models UDAP and UDAS unless noted otherwise.)
Size
150
175
00
5
50
300
350
400
Input Heating Capacity
BTUH
150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
kw
43.9
51.2
58.6
65.9
73.2
87.8
102.5
117.1
Thermal Efficiency (%)
83
83
83
83
83
83
83
83
Output Heating Capacity
A
BTUH
124,500 145,250 166,000
186,750
207,500
249,000 290,500
332,000
kw
36.4
42.5
48.6
54.7
60.8
72.9
85.1
97.2
Gas Connection (inches)
B
Natural
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
Propane
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
Vent Connection
C
(inches diameter)
5
5
5
5
5
6
6
6
Combustion Air Inlet
C
(inches
6
6
6
6
6
6
6
6
Control Amps (24 volt)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Full Load Amps (115 volt)
3.8
3.8
4.6
7.5
7.5
10.7
10.7
10.7
Maximum Over Current
Protection
D E
Standard 115V
15
15
15
15
15
20
20
20
Optional 208V or 230V
15
15
15
15
15
15
15
15
Normal Power Consumption (watts)
392
392
491
747
747
1086
1086
1086
Discharge Air Temperature Rise (°F)
60
60
60
60
60
60
60
60
Air Volume
CFM
1921
2242
2562
2882
3202
3843
4483
5123
M
3
/minute
54.4
63.5
72.5
81.6
90.7
108.8
126.9
145.1
Discharge Air Opening Area
ft
2
2.6
2.6
2.6
3.5
3.5
4.8
4.8
4.8
M
2
0.2
0.2
0.2
0.3
0.3
0.5
0.5
0.5
Output Velocity
FPM
752
877
1003
820
911
802
936
1069
M/minute
229
267
306
250
278
244
285
326
Fan Motor HP
E
Standard Open
1/6
1/6
1/6
1/4
1/4
1/2
1/2
1/2
Optional Enclosed
1/4
1/4
1/4
1/4
1/4
1/2
1/2
1/2
Fan Motor RPM
1050
1050
1050
1050
1050
1050
1050
1050
Fan Diameter (inches)
18
18
18
20
20
24
24
24
Sound Level
dba @ 15 ft
51
52
53
56
56
59
61
62
A
CSA ratings for altitudes to 2000 ft.
B
Size shown is for gas connection to a single-stage gas valve, not supply line size.
C
Smaller and/or larger vent and combustion air pipe diameters may be permissible. For Model UDAS refer to the Venting Installation
Manual for Separated Combustion Units. For Model UDAP refer to the Venting Installation Manual for Power Vented units. For a Model
UDAP with Option AV6, refer to the Venting Installation Manual for Common Venting.
D
MOCP = 2.25 x (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.
E
Except where indicated, information in this table is based on a heater equipped with a standard 115 volt open fan motor.
TECHNICAL DATA - Sizes 30 - 15
(Data applies to both Models UDAP and UDAS unless noted otherwise.)
Size
30
45
60
75
100
15
Input Heating Capacity
BTUH
30,000
45,000
60,000
75,000 105,000 120,000
kw
8.8
13.2
17.6
22.0
30.8
35.2
Thermal Efficiency (%)
82
83
83
83
83
83
Output Heating Capacity
A
BTUH
24,600
37,350
49,800
62,250
87,150
99,600
kw
7.2
11.0
14.6
18.3
25.6
29.2
Gas Connection (inches)
B
Natural
1/2
1/2
1/2
1/2
1/2
1/2
Propane
1/2
1/2
1/2
1/2
1/2
1/2
Vent Connection
C
(inches diameter)
4
4
4
4
4
4
Combustion Air Inlet
C
(inches diameter) -
UDAS only
4
4
4
4
4
4
Control Amps (24 volt)
1.0
1.0
1.0
1.0
1.0
1.0
Full Load Amps (115 volt)
1.9
2.4
2.4
3.3
3.9
5.1
Maximum Over Current
Protection
D E
Standard 115V
15
15
15
15
15
15
Optional 208V or 230V
15
15
15
15
15
15
Normal Power Consumption (watts)
109
155
155
217
276
354
Discharge Air Temperature Rise (°F)
50
55
60
60
60
60
Air Volume
CFM
456
629
769
961
1345
1537
M
3
/minute
12.9
17.8
21.8
27.5
36.7
45.9
Discharge Air Opening Area
ft
2
1.0
1.0
1.2
1.2
2.0
2.0
M
2
0.1
0.1
0.1
0.1
0.2
0.2
Output Velocity
FPM
475
656
616
770
668
763
M/minute
145
200
188
238
196
245
Fan
Motor HP
E
Standard Open
0.0
0.0
0.0
0.1
1/30
1/20
Optional Enclosed
N.A.
N.A.
N.A.
N.A.
1/4
1/4
Fan Motor RPM
1550
1550
1550
1550
1050
1050
Fan Diameter (inches)
10
10
12
12
16
16
Sound Level
dba @ 15 ft
40
40
40
49
54
55