Form I-UDA, P/N 195673 Rev 13, Page 17
FIGURE 1 - Supply
Wiring Connections at
the Circuit Board (DSI
Integrated Control
Module)
Supply Wiring
Connections
NOTE:
Circuit
board is polarity
sensitive; “hot”
wire MUST BE
connected to
Terminal L1.
For all models, the terminal strip for 24 volt thermostat connections is located on the
outside of the cabinet at the back of the heater (See
FIGURE 13
). Wires from the ter
-
minal strip are factory wired to the circuit board.
7.3 4V Control
Wiring
Connections
�����
�����������
�����
��
����
����
����������
�����������
����������
���
�����
������
������
�
7. Supply Wiring
Check the rating plate on the heater for the supply voltage and current requirements.
A dedicated line voltage supply with disconnect switch should be run directly from the
main electrical panel to the heater. All external wiring must be within approved conduit
and have a minimum temperature rise rating of 60°C
.
Conduit must be run so as not
to interfere with the heater access panel. If the installation requires a stepdown trans
-
former (Option CG), follow the instructions shipped with the option package for attach
-
ing the transformer to the heater.
The electrical supply enters at the rear of the heater (See
FIGURE 13
). Model UDAS
includes a built-in disconnect switch (20A @ 115V; 10A @ 230V Rating). Model UDAS
supply wiring connects to leads located inside a sealed electrical box. To maintain the
sealing feature of the electrical box, always replace the cover plate. Model UDAP sup
-
ply wiring connects directly to leads on the integrated circuit board.
The circuit board (See
FIGURE 1
) is located inside on the bottom of the control com
-
partment. The circuit board is polarity sensitive. It is advisable to check the electrical
supply to be certain that the black wire is the “hot” wire and that the white wire is the
neutral wire. The supply connection made to “L1” on the circuit board must be the “hot”
wire.