Form I-UDA, P/N 195673 Rev 13, Page 

8. Controls and 

Operation

8.1 Thermostat

Use either an optional thermostat available with the heater or a field-supplied 24-volt 

thermostat. Install according to the thermostat manufacturer’s instructions, paying par

-

ticular attention to the requirements regarding the location of the thermostat. 
Make sure that the heat anticipator setting on the thermostat is 0.6 amps (or in accor

-

dance with the amperage value noted on the wiring diagram of your heater).
Make thermostat connections at the terminal strip on the back of the heater. The strip 

has four terminals, R, G, W1, and W2; refer to the wiring diagram.

IMPORTANT:

 

All units MUST be operated by a 4-volt thermostat.

 Never use a line 

voltage disconnect switch as a means of operating the heater. Operating Model Sizes 

30-125 by means other than a 24-volt thermostat may result in the flame rollout switch 

tripping. 

Unit Mounted Thermostat, Option CM3

 - 

If the heater was ordered with Option CM3, 

a kit for mounting the thermostat on the rear of the heater is shipped separately. Follow 

the instructions in the option package to attach the bracket. 

Select a snap-action thermostat when using the unit mounted thermostat bracket. Do 

not use a mercury switch thermostat because the vibration may cause excessive unit 

cycling. Be careful with the thermostat leads; shorting the thermostat wires to a metal 

surface will cause the transformer to fail.

Sizes 30-125 are equipped with a temperature activated manually reset flame rollout 

switch. The flame rollout switch is located at the top of the burner assembly. It is factory 

set and is non-adjustable. If the setpoint is reached, the flame rollout acts to interrupt 

the electric supply to the gas valve. If the flame rollout switch activates, identify and cor

-

rect the cause before resetting the switch. Refer to the Maintenance Section, Paragraph 

10.2.10,  for  information  on  probable  causes  and  instructions  on  resetting  the  flame 

rollout switch. (For location, see 

FIGURE 18

, page 30.)

DANGER: If the manual reset flame rollout switch activates, 

identify  and  correct  the  cause  before  resetting  the  switch. 

Never bypass the flame rollout switch; hazardous conditions 

could result. See Hazard Intensity Levels, page .

7.5.3 Door Switch - 

Model UDAS only

All sizes of Model UDAS heaters are equipped with a door switch which prevents the 

heater  from  operating  when  the  service  door  panel  is  open. The  service  panel  of  a 

Model UDAS is equipped with a pliable gasket material that fully seals the door to pro

-

vide added protection from building air entering the combustion zone of the heater. (For 

switch location, see 

FIGURE 18

, page 30.) 

7. Electrical 

Supply and 

Wiring (cont’d)

7.5 Electrical 

Operating 

Components 

(cont’d)

The main operating gas valve is powered by the 24-volt control circuit through the ther

-

mostat and safety controls. The main control valve is of the diaphragm type providing 

regulated gas flow preset at the factory. (For location, see 

FIGURE 18

, page 30.)

WARNING: The operating valve is the prime safety shutoff. 

All gas supply lines must be free of dirt or scale before con-

necting the unit to ensure positive closure. See Hazard Lev-

els, page . 

7.5.4 Gas Valve

7.5.5 Fan Motor

The fan motor is equipped with thermal overload protection of the automatic reset type. 

Should the motor refuse to run, it may be because of improper current characteristics. 

Make certain that the correct voltage is available at the motor. 

NOTE:

 If the unit is equipped with an optional totally enclosed motor or optional volt

-

age, the horsepower may be larger than the standard motor. Refer to the motor name

-

plate to verify horsepower. 

7.5. Flame Rollout Switch - Sizes 30-15 

only

7.5.6 Venter Motor

The venter motor is assembled to the venter wheel and operates to provide combustion 

airflow. Operation is controlled by the ignition control module (circuit board); refer to 

ignition system in Paragraph 8.3.

Содержание UDAP

Страница 1: ...iately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call your fire department FOR YOUR SAFETY Do not store or use gasolin...

Страница 2: ...ration maintenance and service of this heater Definitions of Hazard Intensity Levels in this Manual Contents 1 General 2 4 1 1 Hazard Labels and Notices 2 1 2 General Installation Information 3 1 3 Wa...

Страница 3: ...BOTH this manual and the correct venting manual are REQUIRED for installation of this heater 1 2 General Installation Information WARNING Do not use this appliance if any part has been under water Imm...

Страница 4: ...garages in accordance with ANSI NFPA No 88B latest edition Standard for Repair Garages In Canada installations in aircraft hangars should be in accordance with the require ments of the enforcing auth...

Страница 5: ...24 16 29 93 21 15 28 94 24 17 31 105 20 18 34 113 17 10 ft 14 24 69 32 17 29 87 27 17 31 91 25 15 27 82 30 17 30 90 26 16 28 89 29 18 32 103 25 20 35 110 21 12 ft 14 24 64 39 18 29 84 32 18 31 88 30 1...

Страница 6: ...tions cont d 3 Uncrating and Preparation 3 1 Uncrating and Inspecting This unit was test operated and inspected at the factory prior to crating and was in operating condition If the heater has incurre...

Страница 7: ...60 75 100 125 150 175 200 225 250 300 350 400 High Altitude Switch P N 197031 197032 197031 201160 Negative Pressure OFF Setpoint w c 0 4 0 5 0 4 1 1 Label color Purple Pink Purple Brown Model UDAP CV...

Страница 8: ...1 4 5 7 16 6 1 2 25 11 16 1 3 8 8 3 16 22 3 16 16 3 8 225 250 26 1 8 38 3 16 22 23 42 35 3 8 13 1 16 8 13 16 9 6 1 2 25 11 16 1 3 8 8 3 16 22 3 16 15 5 8 300 350 400 34 1 8 41 30 23 42 35 3 8 17 1 16...

Страница 9: ...35 3 8 8 1 2 8 1 4 5 7 16 6 1 2 25 11 16 1 3 8 8 3 16 22 3 16 16 3 8 4 1 8 8 5 16 225 250 26 1 8 38 3 16 22 23 42 35 3 8 13 1 16 8 13 16 9 6 1 2 25 11 16 1 3 8 8 3 16 22 3 16 15 5 8 5 9 16 8 5 16 300...

Страница 10: ...spending the heater check the supporting structure to be used to verify that it has sufficient load carrying capacity to support the weight of the unit Model UDAP Size 30 45 60 75 100 125 150 175 200...

Страница 11: ...Retainers either two or four point suspension Be sure the threaded hanger rods are locked to the heater as illustrated Length of threaded rod extending into the heater MUST NOT exceed 1 2 13mm If ord...

Страница 12: ...service NEVER TEST FOR LEAKS WITH AN OPEN FLAME Failure to comply could result in personal injury property damage or death Capacity of Piping Cubic Feet per Hour based on 0 3 w c Pressure Drop Specif...

Страница 13: ...c and a maximum of 14 w c Before attempting to measure or adjust valve outlet gas pressure the inlet supply pressure must be within the specified range both when the heater is in operation and on sta...

Страница 14: ...above 6000 ft 1830M a high altitude pressure switch is required see Paragraph 3 2 1 Manifold Pressure Settings by Altitude for the UNITED STATES Altitude Natural Gas inches w c Propane Gas inches w c...

Страница 15: ...500 124915 105350 7001 8000 2136 2440 88200 74088 61740 100800 84672 70560 126000 104580 88200 147000 122010 102900 8001 9000 2441 2745 86100 72324 60270 98400 82656 68880 123000 102090 86100 143500 1...

Страница 16: ...outside air ducts voids the warranty and could cause hazard ous operation See Hazard Levels page 2 Do not install a unit in a confined space without providing wall openings leading to and from the spa...

Страница 17: ...he installation requires a stepdown trans former Option CG follow the instructions shipped with the option package for attach ing the transformer to the heater The electrical supply enters at the rear...

Страница 18: ...Form I UDA P N 195673 Rev 13 Page 18 7 Electrical Supply and Wiring cont d FIGURE 14A Typical Wiring Diagram for Model UDAP or Model UDAS Single Stage 7 4 Wiring Diagrams...

Страница 19: ...Form I UDA P N 195673 Rev 13 Page 19 FIGURE 14B Typical Wiring Diagram for Model UDAP or Model UDAS Single Stage with Optional Air Recirculation...

Страница 20: ...Form I UDA P N 195673 Rev 13 Page 20 FIGURE 14C Typical Wiring Diagram for Model UDAP or Model UDAS Two Stage Gas Valve 7 Electrical Supply and Wiring cont d 7 4 Wiring Diagrams cont d...

Страница 21: ...e vent system Hazardous conditions could result See Hazard Intensity Levels page 2 Model UDAP Startup Cold Equilibrium Hot Setpoint OFF Setpoint ON Label Color Switch P N Model UDAS Startup Cold Equil...

Страница 22: ...ce Section Paragraph 10 2 10 for information on probable causes and instructions on resetting the flame rollout switch For location see FIGURE 18 page 30 DANGER If the manual reset flame rollout switc...

Страница 23: ...trol offers a wide variety of input and output points that can be configured to meet a wide range of building management applications User selectable input types are Thermis tor 4 20 milliamp 1 5 volt...

Страница 24: ...lame has not been sensed during the first 16 seconds the control de energizes the spark output and keeps the gas valve energized for an additional one second flame proving period If flame is not prese...

Страница 25: ...tion If flame is not established on the second trial for ignition the control de energizes the gas valve energizes the fan blower motor on heat speed and venter motor remains energized The fan blower...

Страница 26: ...l flash rapidly when lockout is due to undesired flame Gas Valve Relay Fault If the control senses the gas valve as energized for more than one second when the control is not attempting to energize th...

Страница 27: ...rty damage personal injury or loss of life This appliance does not have a pilot It is equipped with an igni tion device which automatically lights the burner Do not try to light the burner by hand Bef...

Страница 28: ...performed turn off all electric power to the appliance 3 Open the access door 4 Turn the gas control knob clockwise to OFF Do not force 5 Close the access door FIGURE 17 Gas Valve ON OFF Control Knob...

Страница 29: ...soundness Clean openings Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 7 for replacement wiring requirements 10 1 Maintenance Sc...

Страница 30: ...tion of dirt dust and or lint clean the compartment and follow the instructions below to remove and clean the burner Burner Removal Instructions Refer to FIGURE 19 CAUTION Use of eye protection is rec...

Страница 31: ...the burner ribbons Holding the burner assembly so that any foreign material will fall away from the burner use a stiff bristle brush to loosen and remove any foreign material s If the burner is excess...

Страница 32: ...to 1 8 See FIGURE 21 IMPORTANT When re assembling the brown ground wire must remain attached to the ignitor Ignitor CAUTION Due to high voltage on the spark wire and electrode do not touch when ener g...

Страница 33: ...fan guard Rotate the fan blade to check for adequate clearance If adjustment is required loosen the mounting screws re position the fan guard and tighten the screws Rotate the fan blade and re check f...

Страница 34: ...With the manual valve turned off to prevent flow to the gas valve connect a manometer to the 1 8 outlet pressure tap in the valve NOTE A manometer fluid filled gauge is recommended 3 Turn the manual...

Страница 35: ...ace If the flame rollout switch trips again determine and correct the cause before resetting the switch If there is damage to the control compartment repairs must be made before resetting the switch I...

Страница 36: ...Is the sensor located in flame correctly Replace flame sesnsor Reposition flame sensor Is gas flowing Is the ignitor position correct in the gas flow Check gas pressure and supply voltage If either ar...

Страница 37: ...Supply pressure should be 5 14 w c for natural gas or 11 14 w c for propane gas d Cracked ceramic at sensor d Replace sensor Burner cycle on and off 1 Gas pressure too high or too low 1 Supply pressu...

Страница 38: ...y line size C Smaller and or larger vent and combustion air pipe diameters may be permissible For Model UDAS refer to the Venting Installation Manual for Separated Combustion Units For Model UDAP refe...

Страница 39: ...lights 24 Limit Control 21 34 Limit Switch 25 Literature Bag 29 Location 5 Unit Heater Location 4 Location of Controls 30 Lockout 26 Optional vertical louvers 6 M Maintenance Procedures 30 Maintenanc...

Страница 40: ...____________________________________________________ Phone _________________________________ Model ________________ Serial No ______________________________Date of Installation ____________ SPECIFIC I...

Отзывы: