1.  Press the “P“ key 
2.  Select the code number with the cursor keys 
3.  Press the “P“ key. This displays the first menu point. The required menu point can be found by repeat-

edly pressing the “P“ key (scrolling). 

4.  The value in the menu point can be changed with the cursor keys. 
5.  Scroll to the next menu point or to the end of the menu, which returns the display to the set point value, 

by pressing the “P“ key.  

 
To exit the menu and return back to the normal display, quickly, depress the “P“ key for 5 seconds. 
 
 

7.2.2 Reset set-point to zero 
for units that do not have I/O keys on the front panel 

 
When a setting has been left in an undesirable state, e.g. hammering of the coil could occur or too high a 
current inrush, causing nuisance tripping, the set-point can be instantly reset to zero in the following manner: 
 
 
Press  the  down  cursor  key  whilst 

switching on the supply using the mains switch. 

 
 
Using this procedure, after resetting to zero, the set-point can be increased again gradually or the frequency 
setting can be changed, for instance. 
 
 

7.2.3 Six key control panel 

 
The  six  buttons  and  a  LED  display  found  in  the 
front  panel  are  used  for  operating  and  setting  up 
the  unit.  All  operating  methods  and  adjustable 
parameters can be set up through this panel. 
The “I“ and “O“ buttons are used for switching the 
unit  ON  and  OFF,  however, 

these  do  not  pro-

vide  mains  isolation, 

they  simply  inhibit  the 

power semiconductors 
The  “P“,  “F“  and  “Cursor  Buttons“  are  used  for 
parameter  adjustment.  Parameters  are  set  by 
using  menu  controls  which  are  called  up  by  en-
tering  operator  codes.  These  are  explained  in 
more detail in the section “setting up instructions“. 
 
The display value can be increased or decreased 
by units, or tenths of units, by a short press of the 
cursor  buttons.  Holding  the  buttons  down  will 
cause the display to change in units often. 
 
 
To  prevent  accidental  or  unauthorized  adjustment  the  parameter  settings  are  stored  under  user  menus.  A 
pass code must be entered to open the menus. Different menu codes are provided for the various function 
groups (refer to controller operating instructions).  

Changed values are saved upon leaving the programming mode or if no keys are pressed for a pe-
riod of 100 seconds. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
12 

 

I

0

P

F

ON

OFF

DISPLAY

PROGRAMMING

MODE / ENTER

              UP

     DOWN

     BACK

Содержание REOVIB series

Страница 1: ...REOVIB Control units for flexible automation Hand book for installing and setting up REOVIB controllers Concepts questions and background information ...

Страница 2: ...Reset set point to zero 12 7 2 3 Six key control panel 12 8 0 General manufactures instructions for the installation of REOVIB control units 13 8 1 Before installation 14 8 1 0 Connection diagram for frequency drives 14 8 1 1 Setting the mechanical vibrating frequency 14 8 2 Setting the feeder throughput 15 9 0 Setting up regulation control of frequency 15 9 0 1 Setup menu for regulation control 1...

Страница 3: ...espondingly gives 3600 and 7200 vibrations min REOVIB control units are equally suitable for operating with either frequency and can be set by using a link switch to match the feeder frequency REOVIB Frequency inverter specially developed for use with vibratory feeders provides a highly stable drive frequency independent of the supply frequency tuned to that of the feeder and adjustable in 0 1Hz s...

Страница 4: ...d to as Linear Feeders Vibratory feeders with a spiral track and a spring coil combination that gives a com posite motion that are used for sorting orientating and feeding parts are known as Bowl Feeders 2 1 The vibration wave form The vibratory motion in the case of a vibratory feeder moves backwards and forwards in a straight line The direction of movement is at a specific angle relative to hori...

Страница 5: ...erent for each product and depends on the vibrating frequency and amplitude An increase of the feeder throughput cannot be achieved by adjustment amplitude alone the correct vibrat ing frequency must also be selected for the product 2 3 Vibrating frequency and resonance Every vibratory system has a resonant frequency which relates to its mass spring constant and product weight If a feeder could be...

Страница 6: ...ation For over critical operation the drive frequency fa is greater than the resonant frequency fres When the damp ing increases the amplitude increases Likewise interlocking products tend to cause a reduction of the feeders resonant frequency In this operating method the power and vibratory movement are phase op posed which dictate the use of a large reaction base and a higher current draw In pra...

Страница 7: ...bration amplitude by varying the output volt age The feeder is always running with the greatest effectiveness when operating in this manner For more information refer to section 9 0 Guidance on using regulation control with frequency inverters 4 0 REOVIB Symbols The following icons are used to denote unit functions Straight line vibratory feeder Vibratory feeder with a spiral track Motor driven pr...

Страница 8: ...ly When a half wave only is used this provides a frequency the same as that of the mains supply A frequency inverter can provide a frequency that is independent of the mains supply frequency Vibrating speed Refers to the derivative of deflection against time Amplitude Deflection Deflection of the feeder mm relative to the static air gap between the coil and armature normally expressed as the entir...

Страница 9: ...omponents drops below set a certain level the pre feeder switches on and tops up the feed system Coarse fine control Operation with two feeder speeds fast and slow Pulsed operation Feeder runs with a pulsing on off action e g to separate components Accelerometer or am plitude sensor A sensor to control the actual amplitude of a vibratory feeder Can be used either for monitoring or as a feedback tr...

Страница 10: ...To reduce overfilling when feeding material to a weighing machine e g packing machines a feeder can be fun slower shortly before reaching the target weight Additional contacts are provided in a weigher for this purpose These contacts switch the controller to a second set point level which reduces the feeder through put Upon reaching the target weight the feeder switches off completely This operati...

Страница 11: ...es and falls around the position of the sensor on the feed track The power output from the controller is switched on after product falls below the sensor position and the switch on time delay has expired t2 When product builds up behind the sensor position t4 and the switch off time delay has expired t5 the power output from the control unit switches off The time delays are reset if gaps in the pr...

Страница 12: ...f time delays are set by using trimmers or a programming menu in display panel 6 8 3 Sensor Time out Additional function available in digital controllers when the sensor switches t1 an additional timer Sensor Time out is started After a preset time e g 30 240 sec the feeder is switched off t3 providing that in the meantime no further product has been detected by the sensor The status signal is ini...

Страница 13: ...Code C143 Parameter US PA Below is an explanation of the main setting components that are provided on controllers 7 2 1 Three key control panel The operation and setting up of the unit is achieved by using three keys in conjunction with an LED display that can be found on the front panel These controls are all that is needed for selecting all operating modes and setting all parameters To prevent a...

Страница 14: ... 7 2 3 Six key control panel The six buttons and a LED display found in the front panel are used for operating and setting up the unit All operating methods and adjustable parameters can be set up through this panel The I and O buttons are used for switching the unit ON and OFF however these do not pro vide mains isolation they simply inhibit the power semiconductors The P F and Cursor Buttons are...

Страница 15: ...of their training experience and position as well as their knowledge of appropriate standards regulations health and safety requirements and working conditions are authorized to be responsible for the safety of the equipment at all times whilst carrying out their normal duties and are therefore aware of and can report possible hazards Definition of qualified employees according to IEC 364 The cont...

Страница 16: ... be a loss of feeder throughput or the coils will overheat The vibrating frequency for thyristor or triac controllers is selected by using a switch normally a link switch depending on the type of controller The programming menu is used in digital controllers 14 F K L1 REOVIB MFS L1 N PE N PE L1 PE A1 A2 Line reactor Recommended for reducing mains distortion PFC and protecting the drive unit under ...

Страница 17: ...ontrol voltage or 0 4 20mA current signal Controllers with digital control panels because of their improved setting abilities do not require this facility It is only necessary to limit the maximum feeder throughput to either protect the coil against hammering or to limit a feeder that is too quick jamming or interlocking parts When an external analogue set point signal is used in conjunction with ...

Страница 18: ... this value is demonstrated when for example a feeder takes a very long time to ramp up after it has been switched on 9 1 Relationship between acceleration and amplitude The sensor measures the momentary acceleration of the feeder It generates a sinusoidal output voltage signal The acceleration gets higher as the frequency increases The sensor signal is greater for a higher frequency and lower amp...

Страница 19: ...ch menu C 008 select Parameter A F S and press a cursor key to start search this will determine the optimum feeder setting When the resonant frequency has been found the controller will complete the search routine and return to the previous throughput setting 0 9 4 Optimizing regulation 9 4 1 Control range adjustment Set Parameter P in menu C 096 to 50 maximum limit Increase the through put A from...

Страница 20: ...t depend on a true sine wave for mains voltage or current should be used a sine wave is only generated at full output with full wave control The output from frequency controllers is generated by an electronic inverter with pulse width modulated switching The voltage and current values cannot be measured with normal instruments Preferably a moving iron measuring instrument analogue meter should be ...

Страница 21: ...use in the controller and replace if necessary Control input Inhibit Enable correctly set Feed equipment has no power Check that the correct vibrating frequency has been selected and change if necessary Check supply frequency 50 60 Hz Vibrating frequency and supply frequency must correspond Setting of trimmer Umax is too low adjust Umax Feed equipment vibrates aggressively coil hammers Incorrect v...

Страница 22: ...played and feeder does not work no enable signal provide enable signal using con tacts or 24VDC signal fit a link between enable termi nals invert parameter En After running for a short time the feeder stops and Error SE flashes in the dis play sensor time out has been activated no mate rial available no track sensor fitted defective track sensor cancel sensor time out parameter EE check sensor ch...

Страница 23: ...check mains voltage control unit may have to be changed for another type contact manufacturer ERROR ACC Sensor fault defective sensor wrong sensor wiring test sensor check wiring ERROR ETP External tempera ture switch external temperature switch has reached his maximum no temperature switch con nected check magnet temperature bypass the magnet tempera ture input ERROR SE Track control sensor time ...

Страница 24: ...o 28 bud 20 PL 04 703 Warszawa Tel 48 0 22 812 3066 Fax 48 0 22 815 6906 E Mail croma croma com pl Internet www croma com pl Spain REO ESPAÑA 2002 S A C Manuel Ventura i Campeny 21B local 9 E 08339 Vilassar de Dalt Barcelona Tel 34 937 509 994 Fax 34 937 509 995 E Mail info reospain com Internet www reospain com Switzerland REO ELEKTRONIK AG Im Halbiacker 5a CH 8352 Elsau Tel 41 0 52 363 2820 Fax ...

Отзывы: