9.2 Specifications
Item
Description
Specification
A
Maximum input voltage
500V
B
Range of input operating voltage
200-450V
C
Maximum input current (dc)
2*10A
D
Maximum array short circuit current (dc)
2*12.5A
E
Maximum utility backfeed current (ac)
50A
F
Output power factor rating (ac)
1
G
Operating voltage range (ac)
215-265V
H
Operating freq. range or single freq.
59.3-60.5Hz
J
Nominal output voltage (ac)
240V
K
Normal output frequency
60Hz
L
Maximum continuous output current (ac)
20.8A
M
Maximum continuous output power (ac)
5000W
N
Maximum output fault current (ac)
58A
O
Maximum output overcurrent protection
50A
P
Peak Power Tracking Voltage
250–440 V
Q
Number of Inputs
4
R
PV Start Voltage
250V
S
Peak Inverter Efficiency
97%
T
Dimensions
L x W x H -
(mm) 532 x 458 x 218
(in) 8.6' x 20.9' x 18'
U
Weight
27 kg / 59 lb
V
Ambient Temperature Range
−25 C to 60 C
-14° F to 140° F
W
Power consumption
0 W nighttime,
≤ 8W operating